Plan Review Notes
Plan Review Notes For Permit 05070627
Permit Number 05070627
Review Stop G
Sequence Number 10
Notes
Date Text
2007-09-15 05:49:10GAS REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.--MANY LENGTHS MISSING FOR MANY CUT
 SECTIONS.--INDICATE THE LENGHTS OF PIPE FROM THE
 REGULATORS TO THE GAS APPLIANCES AND ALL SECTIONS IN
 BETWEEN. ALSO CHECK RED LINE SECTIONS ON ONE SHEET
 SUBMITTED FOR REVISION.
  
 2. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.--A UNION IS REQUIRED
 DOWNSTREAM OF ALL SHUT OFF VALVES FOR REGULATORS AND/OR
 SOLENOID VALVES. PLEASE INDICATE THE REQUIRED UNIONS.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES.--ALL PIPE SIZES ARE NOT
 INDICATED ON THE REVISION. SHOW ALL PIPE SIZES.
  
 4. INDICATE THE MAXIMUM BTUS ALLOWED FOR FUTURE FIXTURE
 E13 PER TABLE 402.4(2) FOR TOTAL DEVELOPED LENGTH FROM
 THE REGULATOR TO THE MOST REMOTE GAS APPLIANCE, (E13).
  
  
 5. SHT P5.1 BUILDING GAS REQUIREMENTS TABLE/SCHEDULE.
 RECHECK ADDITION AFTER LEG #2 THRU LEG #5. SUBTOTALS &
 TOTAL INCORRECT. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]