Plan Review Notes
Plan Review Notes For Permit 05070627
Permit Number 05070627
Review Stop E
Sequence Number 10
Notes
Date Text
2006-12-26 14:40:41** UNSAT ***
  
 1) NOTE: PLEASE COMPLETE RISER WITH NEW CONDUIT SIZE
 BEING STUBBED OUT FOR FUTURE GENERATOR. PLEASE SEE AS
 THE CONDUCTOR SIZES FOR FUTURE AND FOR EDP ARE NOT
 SHOWN ON PLANS AS SUBMITTED, UNABLE TO VERIFY AT THIS
 TIME.
 240.4, 310.16, TABLE(S) CHAPTER 9.
  
 2) NOTE: PLEASE SEE LOAD CALCULATIONS ON THE BOTTOM
 PART OF DPB SHOW CONNECTED LOAD AT 221 KVA AND DEMAND
 LOAD THE SAME AT 221 KVA, YET THE DEMAND LOAD ON THE
 MDP IS OF THE DEMAND LOAD OF 209KVA.
 PLEASE CORRELATE.
 FBC 104.1.2
 ADMIN SECTION.
  
 3) NOTE: PLEASEKNOW BASED ON AS MANY REVISION ARE
 BEING DONE TO THIS JOB AND SCOPE OF WORK INVOLVED,
 PLEASE KNOW IF THE SERVICE ENTRANCE CONDUCTORS WHICH
 HAVE BEEN SHOWN AS EXISTING TO THE EXISTING 2500A MCB
 MDP ARE RE-PULLED OR TOUCHED IN ANY WAY, THEY WILL BE
 REQUIRED TO BE BROUGHT UP TO CODE. PLEASE SEE 240.4(C)
 WHICH HAS ALWAYS REQUIRED CONDUCTORS FEEDING DEVICES
 RATED OVER 800A?S TO MEET OR EXCEED THE RATING THAT
 DEVICE.
 PLEASE KNOW THIS WAS NOT A CHANGE IN ANY CODE OVER THE
 PAST 15 YRS AND EVEN IF EXISTING, IF THEY ARE RE-PULLED
 AS NOTED FOR ANY REASON OR CHANGED, THEY WILL BE
 REQUIRED TO MEET THE 2500A BREAKER OR BREAKER WOULD BE
 REQUIRED TO BE BROUGHT DOWN TO 2000A OCP.
 90.4
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  