| 2006-12-26 14:40:41 | ** UNSAT *** |
| | |
| | 1) NOTE: PLEASE COMPLETE RISER WITH NEW CONDUIT SIZE |
| | BEING STUBBED OUT FOR FUTURE GENERATOR. PLEASE SEE AS |
| | THE CONDUCTOR SIZES FOR FUTURE AND FOR EDP ARE NOT |
| | SHOWN ON PLANS AS SUBMITTED, UNABLE TO VERIFY AT THIS |
| | TIME. |
| | 240.4, 310.16, TABLE(S) CHAPTER 9. |
| | |
| | 2) NOTE: PLEASE SEE LOAD CALCULATIONS ON THE BOTTOM |
| | PART OF DPB SHOW CONNECTED LOAD AT 221 KVA AND DEMAND |
| | LOAD THE SAME AT 221 KVA, YET THE DEMAND LOAD ON THE |
| | MDP IS OF THE DEMAND LOAD OF 209KVA. |
| | PLEASE CORRELATE. |
| | FBC 104.1.2 |
| | ADMIN SECTION. |
| | |
| | 3) NOTE: PLEASEKNOW BASED ON AS MANY REVISION ARE |
| | BEING DONE TO THIS JOB AND SCOPE OF WORK INVOLVED, |
| | PLEASE KNOW IF THE SERVICE ENTRANCE CONDUCTORS WHICH |
| | HAVE BEEN SHOWN AS EXISTING TO THE EXISTING 2500A MCB |
| | MDP ARE RE-PULLED OR TOUCHED IN ANY WAY, THEY WILL BE |
| | REQUIRED TO BE BROUGHT UP TO CODE. PLEASE SEE 240.4(C) |
| | WHICH HAS ALWAYS REQUIRED CONDUCTORS FEEDING DEVICES |
| | RATED OVER 800A?S TO MEET OR EXCEED THE RATING THAT |
| | DEVICE. |
| | PLEASE KNOW THIS WAS NOT A CHANGE IN ANY CODE OVER THE |
| | PAST 15 YRS AND EVEN IF EXISTING, IF THEY ARE RE-PULLED |
| | AS NOTED FOR ANY REASON OR CHANGED, THEY WILL BE |
| | REQUIRED TO MEET THE 2500A BREAKER OR BREAKER WOULD BE |
| | REQUIRED TO BE BROUGHT DOWN TO 2000A OCP. |
| | 90.4 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |