| Date |
Text |
| 2005-08-13 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT A1.1 EMPLOYEE RESTROOM SHALL BE |
| | ACCESSIBLE PER SECTION 11-4.24. |
| | 2. PLANS SHALL BE ROUTED TO DBPR |
| | DIVISION OF HOTELS AND RESTURANTS FOR |
| | REVIEW. ALL SETS OF PLANS SHALL BE |
| | REVIEWED AND STAMPED WITH TWO PAGE |
| | "WORKSHEETS" ATTACHED TO EACH SET PRIOR |
| | TO RESUBMITTING TO CITY WPB FOR REVIEW. |
| | SECTION 101.4.7. |
| | 3. SHT A1.1 STEAM ROOMS 160 AND 163. |
| | SUBMIT A DETAIL INDICATING WHERE THE |
| | STEAM UNITS FOR THESE ROOMS IS LOCATED. |
| | SHOW ALL PIPEING FOR STEAM LINES SHOWING |
| | ALL PIPE SIZES. SHOW PAN FOR STEAM UNITS |
| | IF LOCATED ABOVE THE CEILING AND |
| | INDICATE HOW THE P/T LINE WILL BE |
| | INSTALLED. SECTION 104.2.1. |
| | 4. SHTS A1.2 AND A1.9 SHOWER IN ROOM 236 |
| | TO BE ACCESSIBLE, AND ALSO REQUIRES A 5' |
| | TURNING AREA. SECTION 11-4.1.6(1)(B). |
| | 5. SHT A1.10 MENS RESTROOM INDICATES |
| | VANITY TO BE RAISED TO 37". ONE LAV |
| | SHALL 34" FOR ACCESSIBLILTY |
| | REQUIREMENTS. SECTION 11-4.19.2 |
| | 6. SHT A10.1 DETAILS SHALL SHOW THE |
| | FOLLOWING: |
| | -FOR W/C'S |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.5 FLUSH CONTROLS |
| | -FOR FAVS |
| | A. 11-4.19.3 CLEAR FLOOR SPACE |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | D. 11-4.19.6 MIRRORS (SHOWS 52" - |
| | REQUIRED TO BE 40"). |
| | 7. SHT A10.1 TURNING AREA REQUIRED IN |
| | EACH TOILET ROOM. (NOT IN THE ACCESSIBLE |
| | STALL). SECTION 11-4.22.3 - ALSO IN |
| | DETAIL "A" THE TURNING AREA SHOULD BE |
| | NEAR THE ACCESSIBLE SHOWER. |
| | 8. ALL PME SHEETS ENGINEER SHALL LEGIBLY |
| | INDICATE THEIR NAME, ADDRESS AND LICENSE |
| | NUMBER ON EACH SHEET. NAME AND LICENSE |
| | NUMBER NOT SHOWN IN THE TITLE BLOCK. FAC |
| | 61G15-23.002(2) AND FS 471.025. |
| | 9. SHT P0.1 PLUMBING GENERAL NOTES #13, |
| | PVC NOT APPROVED FOR WATER DISTRIBUTION |
| | PIPE PER TABLE 605.5. DELETE FROM |
| | REFERENCE, OR INDICATE FOR WATER SERVICE |
| | ONLY. |
| | 10. SHT PD1.1B KEYED NOTES #6 NOT FOUND. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | 11. SHT PD1.1C GREASE INTECEPTORS, |
| | ALTHOUGH EXISTING, SHALL BE SIZED BY THE |
| | EXVIRONMENTAL COMPLIANCE MANAGER. PLEASE |
| | CONTACT LYNN MASSON AT PHONE NUMBER |
| | (561) 822-2271, FAX 9561) 822-2279, OR |
| | E-MAIL [email protected]. PLEASE SUBMIT |
| | THE DETERMINATION SHEET FOR GREASE |
| | INTERCEPTORS WITH PLANS WHEN |
| | RESUBMITTING. WASTE ORD #3434. |
| | 11. SHT P1.1A WATER FILTERS SHALL COMPLY |
| | THE "NSF - 42" STANDARD. PLEASE SUBMIT |
| | MANUF. SPECIFICATIONS FOR FILTER. |
| | SECTION 611.1. |
| | 12. SHT P1.1C KEYED NOTES #3 SUBMIT A |
| | DETAIL FOR THE VENT CAP. VENT SHALL |
| | TERMINATE IN COMPLIANCE WITH SECTION |
| | 904.5. SUBMIT AN ELEVATION FOR THE TRASH |
| | AREA TO DETERMINE IF VENT WILL BE |
| | APPROVED IN AREA WITHOUT TERMINATING |
| | ABOVE THE ROOF OF THE TRASH AREA. |
| | SECTION 104.2.1. |
| | 13. SUBMIT A SANITARY ISOMETRIC RISER |
| | DIAGRAM SHOWING ALL PIPE SIZES, TRAPS, |
| | VENTS, POINTS OF CONNECTION, AND DFU'S |
| | AS THEY ACCUMULATE IN THE DRAINAGE |
| | SYSTEM. SECTION 104.3.1.1. |
| | 14. SUBMIT A GREASE ISOMETRIC RISER |
| | DIAGRAM. SHOW ALL PIPE SIZES, TRAPS, |
| | VENTS, POINTS OF CONNECTION, ECT. |
| | 15. SUBMIT A WATER ISOMETRIC RISER |
| | DIAGRAM, SHOWING ALL PIPE SIZES, VALVES, |
| | WATER HAMMER ARRESTORS, (REQD. BY |
| | SECTION 604.9), AND LOCATED NEAR THE |
| | FIXTURES AS REQUIRED BY PDI-WH 201 & |
| | MANUF. INSTALLATION INSTRUCTIONS, AND |
| | POINTS OF CONNECTION. |
| | 16. A SEPARATE GAS PERMIT IS REQUIRED. |
| | SUBMIT THE FOLLOWING INFORMATION: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2. |
| | H. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | I. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | J. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |