| 2005-08-30 00:00:00 | ******DENIED****** |
| | |
| | 1) CONSTRUCTION ALTERATION AND |
| | DEMOLITION TO COMPLY WITH NFPA 241. |
| | |
| | 2) THE DOOR SWINGS AT 1ST FLOOR |
| | MECHANICAL ROOM TO NEW LADIES CARD ROOM, |
| | AND MECHANICAL STORAGE NEXT TO MAIN |
| | ELECTRICAL ROOM, OBSTRUCT THE HALLWAY BY |
| | GREATER THAN 1/2 THE WIDTH. |
| | |
| | 3) PLEASE NOTE THAT STAIR IDENTIFICATION |
| | DOESN'T APPEAR CONSISTENT THROUGHOUT |
| | PLANS. |
| | |
| | 4) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENTS FOR ALL HANDRAILS AND |
| | GUARDS. |
| | |
| | 5) PLEASE INCLUDE LIFE SAFETY PLAN TO |
| | DETERMINE REQUIRED MEANS OF EGRESS AND |
| | PATH OF TRAVEL. |
| | |
| | 6) IT WOULD APPEAR THAT WHEN EXITING |
| | FROM THE RESTAURANT TO THE CORRIDOR |
| | LEADING TO STAIR #1, THE DOOR MAY |
| | INTERFERE WITH THE DOOR TO THE MECH/AC |
| | ROOM. PLEASE CLARIFY ARRANGEMENT. |
| | |
| | 7) PLEASE INDICATE THE OCCUPANT LOADS |
| | FOR THE RESTAURANT AND FITNESS CLUB. |
| | |
| | 8) SEPARATE SHOP DRAWINGS AND PERMITS |
| | REQUIRED FOR FIRE SPRINKLER AND FIRE |
| | ALARM REMODEL. |
| | |
| | 9) NOTE THAT DOORS SERVING AREAS OF |
| | OCCUPANT LOAD GREATER THAN 50 SHALL |
| | SWING IN THE DIRECTION OF TRAVEL. |
| | |
| | 10) DOORS IN AREAS SERVING OCCUPANT LOAD |
| | GREATER THAN 100, SHALL HAVE PANIC |
| | HARDWARE WITH UL LISTED CLOSERS. |
| | |
| | 11) PLEASE ILLUSTRATE FIRE RATINGS FOR |
| | APPROPRIATE DOORS. |
| | |
| | 12) PLEASE INDICATE THE MINIMUM INTERIOR |
| | FINISH CLASSIFICATION FOR WALLS AND |
| | CEILINGS. |
| | |
| | 13) SEPARATE SHOP DRAWINGS AND PERMITS |
| | ARE REQUIRED FOR HOOD AND SUPPRESSION |
| | SYSTEMS IF APPLICABLE AND PART OF THIS |
| | JOB SCOPE. |
| | |
| | 14) MONITORING OF SPRINKLER SYSTEM TO BE |
| | UL CERTIFIED FOR CENTRAL STATION |
| | SERVICE. |
| | |
| | |