2005-08-30 00:00:00******DENIED******
  
 1) CONSTRUCTION ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 2) THE DOOR SWINGS AT 1ST FLOOR
 MECHANICAL ROOM TO NEW LADIES CARD ROOM,
 AND MECHANICAL STORAGE NEXT TO MAIN
 ELECTRICAL ROOM, OBSTRUCT THE HALLWAY BY
 GREATER THAN 1/2 THE WIDTH.
  
 3) PLEASE NOTE THAT STAIR IDENTIFICATION
 DOESN'T APPEAR CONSISTENT THROUGHOUT
 PLANS.
  
 4) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDS.
  
 5) PLEASE INCLUDE LIFE SAFETY PLAN TO
 DETERMINE REQUIRED MEANS OF EGRESS AND
 PATH OF TRAVEL.
  
 6) IT WOULD APPEAR THAT WHEN EXITING
 FROM THE RESTAURANT TO THE CORRIDOR
 LEADING TO STAIR #1, THE DOOR MAY
 INTERFERE WITH THE DOOR TO THE MECH/AC
 ROOM. PLEASE CLARIFY ARRANGEMENT.
  
 7) PLEASE INDICATE THE OCCUPANT LOADS
 FOR THE RESTAURANT AND FITNESS CLUB.
  
 8) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 9) NOTE THAT DOORS SERVING AREAS OF
 OCCUPANT LOAD GREATER THAN 50 SHALL
 SWING IN THE DIRECTION OF TRAVEL.
  
 10) DOORS IN AREAS SERVING OCCUPANT LOAD
 GREATER THAN 100, SHALL HAVE PANIC
 HARDWARE WITH UL LISTED CLOSERS.
  
 11) PLEASE ILLUSTRATE FIRE RATINGS FOR
 APPROPRIATE DOORS.
  
 12) PLEASE INDICATE THE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 13) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR HOOD AND SUPPRESSION
 SYSTEMS IF APPLICABLE AND PART OF THIS
 JOB SCOPE.
  
 14) MONITORING OF SPRINKLER SYSTEM TO BE
 UL CERTIFIED FOR CENTRAL STATION
 SERVICE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722