Plan Review Notes
Plan Review Notes For Permit 05070627
Permit Number 05070627
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-28 00:00:00********** UNSAT ************
  
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCK FOR ENGINEERING
 FIRM. PLEASE SEE 61G15-23.002 FOR
 MISSING PRINTED NAME AND PRINTED LICENSE
 # FOR ENGINEER.
 PLEASE SEE ARCHITECTS TITLE BLOCK FOR
 ALL SHEETS SHALL ALSO CONTAIN THE
 PRINTED NAME AND LICENSE # FOR ARCH.
 61G1-16.004
  
 THIS SEE THIS IS REQUIRED FOR ALL SHEETS
 AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE E1.A, APPEARS SOME
 IMAGES ARE "SHIFTED" OR "DOUBLE"?
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL
 SCHEDULES.
 PLEASE SEE ALL CONTROL WIRING FOR
 LIGHTING PLANS.
 PLEASE SEE LIGHTING PLANS DO NOT SEEM TO
 BE COMPLETE AT THIS TIME? PLEASE SEE
 MISSING "KEYED NOTES" ETC.
 PLEASE SEE SOME AREAS DO NOT INDICATE
 ANY LIGHTING? WOMENS RESTROOM?
 PLEASE SEE THIS MAINLY SEEMS TO BE
 MISSING FROM LIGHTING PLANS.
 PLEASE ALSO SEE CIRCUTING FOR A/C
 SYSTEMS, PANELS TEND TO BE INDICATED ,
 HOWEVER NOT THE CIRCUITING.
  
 4)NOTE:PLEASE SEE 700.12E FOR CIRCUITING
 OF EM/EXT LTS.THE BRANCH CIRCUIT FEEDING
 THE UNIT EQUIPMENT SHALL BE THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES.
  
 5)NOTE: PLEASE INCLUDE ROOM/AREA
 DESIGNATIONS ON PLANS. THIS SHOULD BE ON
 ALL SHEETS.
 215.5
  
 6)NOTE:PLEASE SEE SOME PANELS SEEM TO
 INDICATE A COUNTERTOP IN FRONT OF
 ELECTRICAL PANELS?? PLEASE SEE BAR
 PANELS, E2.1.A? PLEASE SEE OUTLINED
 AREAS ON PLANS.?? F, G, GA, J,,,ETC.
  
 7)NOTE: PLEASE SHOW ALL CIRCUITING ON
 KITCHEN ELECTRICAL PLAN FOR ALL. PLEASE
 CORRELATE THIS WITH EQUIPMENT SCHEDULE
 SUBMITTED AND PANEL SCHEDULES.
  
 8)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLING UNITS
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 9)NOTE: PLEASE SHOW AND INDICATE
 ELEVATOR EQUIPMENT ROMM. PLEASE SEE
 STATE ELEVATOR CODE , NO OTHER EQUIPMENT
 UNLESS PART OF THE DESIGNATED ELEVATOR
 EQUIPMENT SHALL BE IN ELEVATOR ROOMS.
 PLEASE SEE 620.23,620.24, PLEASE VERIFY
 AND SHOW IF THESE ARE TO BE NEW OR
 EXISTING.
  
 10)NOTE: PLEASE SEE 700.16 FOR
 ELECTRICAL RMS, EQUIPMENT RMS, ELEVATOR
 RMS.
  
 11)NOTE: PLEASE SEE RISER MENTIONS ? FOR
 PANEL "D". THIS INFORMATION IS REQUIRED
 AT THIS TIME.
  
 12)NOTE: PLEASE SHOW ALL CONTINUOUS
 LOADS AND LARGEST MOTOR ARE TO BE SHOWN
 @125%
 215.3,230.42 ETC,
  
  
  
 ****************************************
 THE FOLLOWING COMMENT HAS TO DO WITH
 ELECTRICAL RISER DIAGRAM,ONE-LINE
 DIAGRAM AND PANEL SCHEDULES.
 ****************************************
  
 13)NOTE: PLEASE CORRELATE ALL PANELS ON
 ONELINE, RISER AND PANEL SCHEDULES
 SUBMITTED.
 PLEASE SEE THERE ARE TOO NUMEROUS ITEMS
 WHICH DO NOT MATCH UP WITH EACH OTHER.
 PLEASE SEE AMERAGES OF PANELS SHOWN
 DIFFERENTLY ON EACH, SEE SOME SHOWN AS
 225A AND 300A ETC.
 PLEASE SEE SOME PANELS BEING SHOWN BEING
 FED FROM"DPB", YET OTHER SHEETS SHOW
 THESE PANELS FROM "DPA" AND YET PANEL
 SCHEDULES FOR THESE SHOW SOMETHING
 ELSE?? PLEASE SEE "DPA" TO G,GA,B, 2BA
 AND RISER SHOWS FROM "DPB" ETC.
 PLEASE SEE SOME PANEL SHOWN AS ONE SIZE
 MLO, YET INDICATE ON PANEL SCHEULE SHOWS
 A DIFFERENT SIZE.?
 PLEASE SEE PANELS LABELED AS ONE THING
 ON ONE-LINE ANDSOEMTHING ELSE ON RISER
 DIAGRAM AND PANEL SCHEDULE? KDP, KDP1,
 600A/ 500A??? ETC,,
 PLEASE SEE POOL RM PANEL, PANEL N ETC.
 PLEASE SEE ONE LINE SHOWS DISCONNECT
 FROM WW MDP TO KDP/KDP1, YET RISER DOES
 NOT SHOW THIS?
 PLEASE SEE SOME PANELS SHOWN AS MLO, YET
 ALSO SHOWS HAVING A MAIN?
 PLEASE INCLUDE ALL INFORMATION FOR ALL
 DISCONNECTS ON RISER.
 PLEASE LABEL ALL PANELS,DISC'S, MDP ETC
 ON RISER.
  
 PLEASE GO THROUGH ALL PANELS,DISCONNECTS
 ETC AND CORRELATE.
  
 PLEASE KNOW, DUE THE NUMBER OF ITEMS ON
 ELECTRICAL PLANS, ONE COPY OF ELECTRICAL
 PLANSHAVE BEEN REMOVED FROM ONE SET.
 THIS IS BEING HELD FOR REFERENCE.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS FROM OTHER
 TRADES SHOULD BE SUBMITTED FOR
 REFERENCE. THIS WILL NOT BE REQUIRED OF
 VOIDED ELECTRICAL SHEETS AS ONE SET IS
 ALREADY RETAINED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-07-27 00:00:00IN ELEC FOR REVIEW.
 PLANS WILL BE IN FAILED STATUS,NOTES TO
 FOLLOW.