| 2005-07-28 00:00:00 | ********** UNSAT ************ |
| | |
| | |
| | 1)NOTE: PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON TITLE BLOCK FOR ENGINEERING |
| | FIRM. PLEASE SEE 61G15-23.002 FOR |
| | MISSING PRINTED NAME AND PRINTED LICENSE |
| | # FOR ENGINEER. |
| | PLEASE SEE ARCHITECTS TITLE BLOCK FOR |
| | ALL SHEETS SHALL ALSO CONTAIN THE |
| | PRINTED NAME AND LICENSE # FOR ARCH. |
| | 61G1-16.004 |
| | |
| | THIS SEE THIS IS REQUIRED FOR ALL SHEETS |
| | AND FOR ALL TRADES WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 2)NOTE: PLEASE SEE E1.A, APPEARS SOME |
| | IMAGES ARE "SHIFTED" OR "DOUBLE"? |
| | |
| | 3)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH PANEL |
| | SCHEDULES. |
| | PLEASE SEE ALL CONTROL WIRING FOR |
| | LIGHTING PLANS. |
| | PLEASE SEE LIGHTING PLANS DO NOT SEEM TO |
| | BE COMPLETE AT THIS TIME? PLEASE SEE |
| | MISSING "KEYED NOTES" ETC. |
| | PLEASE SEE SOME AREAS DO NOT INDICATE |
| | ANY LIGHTING? WOMENS RESTROOM? |
| | PLEASE SEE THIS MAINLY SEEMS TO BE |
| | MISSING FROM LIGHTING PLANS. |
| | PLEASE ALSO SEE CIRCUTING FOR A/C |
| | SYSTEMS, PANELS TEND TO BE INDICATED , |
| | HOWEVER NOT THE CIRCUITING. |
| | |
| | 4)NOTE:PLEASE SEE 700.12E FOR CIRCUITING |
| | OF EM/EXT LTS.THE BRANCH CIRCUIT FEEDING |
| | THE UNIT EQUIPMENT SHALL BE THE SAME |
| | BRANCH CIRCUIT AS THAT SERVING THE |
| | NORMAL LIGHTING IN THE AREA AND |
| | CONNECTED AHEAD OF ANY LOCAL SWITCHES. |
| | |
| | 5)NOTE: PLEASE INCLUDE ROOM/AREA |
| | DESIGNATIONS ON PLANS. THIS SHOULD BE ON |
| | ALL SHEETS. |
| | 215.5 |
| | |
| | 6)NOTE:PLEASE SEE SOME PANELS SEEM TO |
| | INDICATE A COUNTERTOP IN FRONT OF |
| | ELECTRICAL PANELS?? PLEASE SEE BAR |
| | PANELS, E2.1.A? PLEASE SEE OUTLINED |
| | AREAS ON PLANS.?? F, G, GA, J,,,ETC. |
| | |
| | 7)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | KITCHEN ELECTRICAL PLAN FOR ALL. PLEASE |
| | CORRELATE THIS WITH EQUIPMENT SCHEDULE |
| | SUBMITTED AND PANEL SCHEDULES. |
| | |
| | 8)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR |
| | KITCHENS IN OTHER THAN DWELLING UNITS |
| | WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| | KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO EACH AND EVERY |
| | 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| | RECEPTACLE, WHETHER OR NOT THE |
| | RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| | |
| | |
| | 9)NOTE: PLEASE SHOW AND INDICATE |
| | ELEVATOR EQUIPMENT ROMM. PLEASE SEE |
| | STATE ELEVATOR CODE , NO OTHER EQUIPMENT |
| | UNLESS PART OF THE DESIGNATED ELEVATOR |
| | EQUIPMENT SHALL BE IN ELEVATOR ROOMS. |
| | PLEASE SEE 620.23,620.24, PLEASE VERIFY |
| | AND SHOW IF THESE ARE TO BE NEW OR |
| | EXISTING. |
| | |
| | 10)NOTE: PLEASE SEE 700.16 FOR |
| | ELECTRICAL RMS, EQUIPMENT RMS, ELEVATOR |
| | RMS. |
| | |
| | 11)NOTE: PLEASE SEE RISER MENTIONS ? FOR |
| | PANEL "D". THIS INFORMATION IS REQUIRED |
| | AT THIS TIME. |
| | |
| | 12)NOTE: PLEASE SHOW ALL CONTINUOUS |
| | LOADS AND LARGEST MOTOR ARE TO BE SHOWN |
| | @125% |
| | 215.3,230.42 ETC, |
| | |
| | |
| | |
| | **************************************** |
| | THE FOLLOWING COMMENT HAS TO DO WITH |
| | ELECTRICAL RISER DIAGRAM,ONE-LINE |
| | DIAGRAM AND PANEL SCHEDULES. |
| | **************************************** |
| | |
| | 13)NOTE: PLEASE CORRELATE ALL PANELS ON |
| | ONELINE, RISER AND PANEL SCHEDULES |
| | SUBMITTED. |
| | PLEASE SEE THERE ARE TOO NUMEROUS ITEMS |
| | WHICH DO NOT MATCH UP WITH EACH OTHER. |
| | PLEASE SEE AMERAGES OF PANELS SHOWN |
| | DIFFERENTLY ON EACH, SEE SOME SHOWN AS |
| | 225A AND 300A ETC. |
| | PLEASE SEE SOME PANELS BEING SHOWN BEING |
| | FED FROM"DPB", YET OTHER SHEETS SHOW |
| | THESE PANELS FROM "DPA" AND YET PANEL |
| | SCHEDULES FOR THESE SHOW SOMETHING |
| | ELSE?? PLEASE SEE "DPA" TO G,GA,B, 2BA |
| | AND RISER SHOWS FROM "DPB" ETC. |
| | PLEASE SEE SOME PANEL SHOWN AS ONE SIZE |
| | MLO, YET INDICATE ON PANEL SCHEULE SHOWS |
| | A DIFFERENT SIZE.? |
| | PLEASE SEE PANELS LABELED AS ONE THING |
| | ON ONE-LINE ANDSOEMTHING ELSE ON RISER |
| | DIAGRAM AND PANEL SCHEDULE? KDP, KDP1, |
| | 600A/ 500A??? ETC,, |
| | PLEASE SEE POOL RM PANEL, PANEL N ETC. |
| | PLEASE SEE ONE LINE SHOWS DISCONNECT |
| | FROM WW MDP TO KDP/KDP1, YET RISER DOES |
| | NOT SHOW THIS? |
| | PLEASE SEE SOME PANELS SHOWN AS MLO, YET |
| | ALSO SHOWS HAVING A MAIN? |
| | PLEASE INCLUDE ALL INFORMATION FOR ALL |
| | DISCONNECTS ON RISER. |
| | PLEASE LABEL ALL PANELS,DISC'S, MDP ETC |
| | ON RISER. |
| | |
| | PLEASE GO THROUGH ALL PANELS,DISCONNECTS |
| | ETC AND CORRELATE. |
| | |
| | PLEASE KNOW, DUE THE NUMBER OF ITEMS ON |
| | ELECTRICAL PLANS, ONE COPY OF ELECTRICAL |
| | PLANSHAVE BEEN REMOVED FROM ONE SET. |
| | THIS IS BEING HELD FOR REFERENCE. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD/VOIDED SHEETS FROM OTHER |
| | TRADES SHOULD BE SUBMITTED FOR |
| | REFERENCE. THIS WILL NOT BE REQUIRED OF |
| | VOIDED ELECTRICAL SHEETS AS ONE SET IS |
| | ALREADY RETAINED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2005-07-27 00:00:00 | IN ELEC FOR REVIEW. |
| | PLANS WILL BE IN FAILED STATUS,NOTES TO |
| | FOLLOW. |