| 2005-08-26 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05070627 |
| | ADD: 2300 PRESIDENTIAL WAY |
| | CONT: CONKLING & LEWIS CONST |
| | TEL: (561)833-4441 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2)INDICATE BUILDING TYPE: |
| | 601.2.1 EVERY BUILDING SHALL BE |
| | CLASSIFIED BY THE BUILDING OFFICIAL |
| | INTO ONE OF THE TYPES OF CONSTRUCTION |
| | AS SET FORTH IN THIS SECTION. |
| | |
| | TYPE ITYPE V |
| | TYPE II1-HOUR PROTECTED |
| | TYPE IIIUNPROTECTED |
| | TYPE IV TYPE VI |
| | 1-HOUR PROTECTED1-HOUR PROTECTED |
| | UNPROTECTED UNPROTECTED |
| | IF BUILDING IS FIRE SPRINKLERED OR NOT? |
| | IF FIRE SPRINKLERED PROVIDE FIRE |
| | SPRINKLER PLANS. |
| | |
| | 3) PROVIDE LIFE SAFETY PLAN, ALSO |
| | PROVIDE THE SEATING FOR RESTARAUNTS OR |
| | OCCUPANT LOAD WILL BE TAKEN AS 15 NET, |
| | FOR PREFUNCTION AREAS 7 NET. |
| | |
| | 4) PLANS SHEET A5.1 DOOR SCHEDULE, NO |
| | FIRE RATINGS ASSIGNED TO DOORS, ALSO SEE |
| | DOOR RATING AS "B" OR "C" SEE TABLE |
| | 705.1.2. FOR MINUTE & HR RATING. |
| | M1106.4 MACHINE ROOMS REQUIRE 45 MIN |
| | OPENING PROTECTION. |
| | M1106.4 OPENING PROTECTIVES. OPENING |
| | PROTECTION BETWEEN THE MACHINERY |
| | ROOM AND OTHER OCCUPIED SPACES SHALL BE |
| | APPROVED, SELF-CLOSING, TIGHT- |
| | FITTING FIRE DOORS WITH A MINIMUM |
| | FIRE-RESISTANCE RATING OF 3/4 HOUR. |
| | |
| | 5) 11-4.3.11 AREAS OF RESCUE ASSISTANCE. |
| | 11-4.3.11.1 LOCATION AND CONSTRUCTION |
| | PLANS DO NOT INDICATE FIRE SPRINKLERS, |
| | PROVIDE DETAILS FOR REQUIRED AREA OF |
| | RESCUE ASSISTANCE. |
| | |
| | 6) SHEET A8.2 PLANS INDICATE THE USE OF |
| | IMPACT GLAZING FOR WINDOWS & DOORS, NO |
| | WIND PRESSURE INFORMATION PROVIDED. |
| | PROVIDE ELEVATIONS WITH THE ASSOCIATED |
| | POSITIVE & NEGATIVE PRESSURES INTERIOR |
| | AND END ZONES. |
| | |
| | 7) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 8)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS- NOT SHOWN MAY HAVE MORE THAN |
| | ONE TYPE |
| | B) DOORS ALL EXTERIOR DOORS BEING |
| | REPLACED, SOLID OR GLAZED |
| | C) EXTERIOR LOUVERS |
| | D) MULLIONS |
| | |
| | 9) MISSING A SHEETS 2 SERIES, 3 SERIES, |
| | 4 SERIES, 6 & 7 SERIES. |
| | |
| | 10) PROVIDE HANDRAIL/ GUARDRAIL DETAILS |
| | FOR NEW STAIRWELL# 7. |
| | |
| | 11)11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. CLEAR 18"LOCK SIDE. |
| | DOORS, 148B, 153, 172, 237, 241,& 249. |
| | |
| | 12) PLANS DO NOT PROVIDE ANY INFORMATION |
| | AS TO WALL OR FLOOR FINISHES, PROVIDE |
| | INFORMATION. |
| | |
| | 13) 1204.2 SURROUNDING MATERIALS. THE |
| | WALLS AND FLOORS OF ALL PUBLIC REST |
| | ROOMS SHALL BE LINED WITH NONABSORBENT |
| | MATERIAL TO A HEIGHT OF 4 FT (1219 |
| | MM) ABOVE THE FLOOR. |
| | |
| | 14) PROVIDE THE MINIMUM INTERIOR FINISH |
| | CLASSIFICATION TABLE 803.3. |
| | |
| | ADDITIONAL COMMENTS MAY APPEAR SINCE A |
| | COMPLETE SET OF PLANS WERE NOT PROVIDED |
| | FOR THIS REVIEW. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |