Plan Review Notes
Plan Review Notes For Permit 05070591
Permit Number 05070591
Review Stop M
Sequence Number 6
Notes
Date Text
2006-03-31 00:00:00DENIED:5TH REQUEST:
 PLEASE NOTE, THE FOLLOWING ITEM WAS
 APPROVED WITH A PROVISO.THE PLANS HAVE
 NOT BEEN REVISED TO ADDRESS THE PROVISO.
  
 THE PARKING GARAGE IS NOT CODE
 COMPLIANT.A PROVISO WAS GIVEN TO HELP
 EXPEDITE THE JOB.REVISED PLANS SHALL
 REFLECT THE REQUIREMENTS OF THE PROVISO.
  
 GARAGE VENTILATION SHALL COMPLY WITH
 2001 FBC 403.4, 403.4.1, 502.11.PLEASE
 REVISE PLANS TO INDICATE THE FOLLOWING
 INFORMATION:
 1.WILL FANS RUN CONTINIOUS OR
 INTERLOCKED WITH WITH CO SENSORS.
 PLEASE NOTE, CO SENSORS SHALL ACTIVATE
 FANS WHEN SET A MAXIMUM OF 25 PARTS PER
 MILLION.CO SENSORS SHALL BE TESTED.
  
 2.PLEASE INDICATE LAYOUT FOR THE CO
 SENSORS.
  
 3.PLEASE INDICATE FRESH AIR MAKE-UP
 FOR COMPLIANCE WITH 2001 FMC 501.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.