| Plan Review Notes For Permit 05070591 |
| Permit Number |
05070591 |
|
| Review Stop |
M |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2006-03-31 00:00:00 | DENIED:5TH REQUEST: | | | PLEASE NOTE, THE FOLLOWING ITEM WAS | | | APPROVED WITH A PROVISO.THE PLANS HAVE | | | NOT BEEN REVISED TO ADDRESS THE PROVISO. | | | | | | THE PARKING GARAGE IS NOT CODE | | | COMPLIANT.A PROVISO WAS GIVEN TO HELP | | | EXPEDITE THE JOB.REVISED PLANS SHALL | | | REFLECT THE REQUIREMENTS OF THE PROVISO. | | | | | | GARAGE VENTILATION SHALL COMPLY WITH | | | 2001 FBC 403.4, 403.4.1, 502.11.PLEASE | | | REVISE PLANS TO INDICATE THE FOLLOWING | | | INFORMATION: | | | 1.WILL FANS RUN CONTINIOUS OR | | | INTERLOCKED WITH WITH CO SENSORS. | | | PLEASE NOTE, CO SENSORS SHALL ACTIVATE | | | FANS WHEN SET A MAXIMUM OF 25 PARTS PER | | | MILLION.CO SENSORS SHALL BE TESTED. | | | | | | 2.PLEASE INDICATE LAYOUT FOR THE CO | | | SENSORS. | | | | | | 3.PLEASE INDICATE FRESH AIR MAKE-UP | | | FOR COMPLIANCE WITH 2001 FMC 501.4 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|