| 2005-12-20 00:00:00 | **** UNSAT **** |
| | |
| | AS GONE OVER WITH ENGINEER ON A PREVIOUS |
| | MEETING WHICH WAS CORRECTED FOR PREVIOUS |
| | COMMENTS, HOWEVER PLANS HAVE COME BACK |
| | IN WITHOUT SOME OF THOSE CORRECTIONS |
| | INCORPORATED INTO PLANS. |
| | |
| | |
| | 1)NOTE: PLEASE ADJUST OCP FOR ALL AHU'S, |
| | AS REQUIRED UNDER 424.3B |
| | PLEASE SEE CALCULATING HEAT LOAD FROM |
| | MOTOR LOAD AND THEN ADDING MOTOR LOAD, |
| | STILL EXCEEDS THE OCP SHOWN ON PANEL |
| | SCHEDULE. |
| | |
| | 2)NOTE: PLEASE REMOVE ALL ELECTRICAL |
| | DEVICES, FIXTURES ETC LOCATED IN "FUTURE |
| | TENANT SPACE". THIS WAS ALSO REQUESTED |
| | ON PREVIOUS REVIEW SINCE THESE SPACES |
| | ARE NOT IN SCOPE. |
| | |
| | 3)NOTE: PLEASE INDICATE THE GFI |
| | PROTECTION IN KITCHEN AREA. 2002 NEC |
| | 210.8B3 |
| | ALL 125V, 15 AND 20A RECEPTS, SHALL BE |
| | GFI OR GFI PROTECTED. |
| | |
| | 4)NOTE: PLEASE SEE E-2.01, PLEASE ADJUST |
| | WORDING FOR BAY #4 METER AND MAIN, AS |
| | PLANS INDICATE THIS AS SERVICE #4. |
| | PLEASE KNOW, THIS BLDG ONLY CONTAINS ONE |
| | SERVICE AND THIS SHOULD READ BAY #4 |
| | METER/MAIN OR WORDS TO THAT AFFECT. |
| | |
| | 5)NOTE: PLEASE SEE MECHANICAL/FIRE |
| | "PROVISO", NOTES, WITH RESPECT TO THE |
| | PARKING AREA AND AIR CHNAGES REQUIRED |
| | AND THE POSSIBLE AFFECT THIS WILL AHVE |
| | ON ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |