Plan Review Notes
Plan Review Notes For Permit 05070591
Permit Number 05070591
Review Stop P
Sequence Number 3
Notes
Date Text
2006-01-23 00:00:00PAUL SCHMITZ
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 DENIED
 1) SHT.A2.02 MEN AND WOMENS TOILET ROOM
 #204,206.SEE FIG 30E TOILET STALL.
 THE TOILET STALL DOOR SHALL NOT SWING
 INTO THE REQUIRED CLEAR FLOOR SPACE FOR
 ANY FIXTURE.
 2)BREAK ROOMS #212, VIGNETTE KITCHEN.
 ?11-4.24 SINKS.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)
 DEEP.
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  
  