2005-09-30 00:00:00PROVISO:
 PLAN DOES NOT INDICATE NUMBER OF
 VEHICLES THAT CAN PARK IN THE GARAGE.
 PER 2001 FBC 411.4.2 & 411.5.4, UNDER
 NORMAL USE THE VENTILATION OF THE GARAGE
 SHALL BE CONTINIOUS WITH POSITIVE MEANS
 FOR BOTH INTAKE & EXHAUST.
  
 PLEASE NOTE EQUIPMENT LOCATED IN A FLOOD
 ZONE, SHALL BE PLACED ABOVE THE FLOOD
 ELEVATION OR PROTECTED IN A MANNER TO
 PREVENT WATER FROM ENTERING OR
 ACCUMULATING WITHIN THE EQUIPMENT.
  