| Plan Review Notes For Permit 05070591 |
| Permit Number |
05070591 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-09-27 00:00:00 | DENIED: | | | RESPONSE TO COMMENTS DATED 8-16-05 | | | COMMENT #1: | | | RESPONSE INDICATES THE GARAGE EXHAUST | | | FAN WILL ONLY RUN WHEN GARAGE DOOR IS | | | ACTIVATED.PER 2001 FBC 411.4.2, | | | PARKING GARAGE SHALL HAVE A MINIMUM OF 6 | | | AIR CHANGES PER HOUR.PLEASE CLARIFY | | | HOW THIS WILL COMPLY.PLEASE INDICATE | | | THE NUMBER OF CARS THAT WILL BE ABLE TO | | | PARK IN THE GARAGE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|