| Date |
Text |
| 2005-09-26 00:00:00 | ******** UNSAT ****** |
| | |
| | PLEASE SEE SOME NOTES FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | PLEASE SEE ELECTRICAL PLANS INDICATE |
| | CLOAED IN PARKING AREAS, WHICH MAY |
| | REQUIRE CHANGES AND AFFECT ELECTRICAL |
| | PLANS. |
| | PLEASE ALSO SEE SOME NOTES FROM |
| | ELECTRICAL REVIEW. |
| | |
| | 1)NOTE: PLEASE SEE MOST OF KITCHEN/ |
| | BREAK RM AREA RECEPTS WERE CLOUDED FOR |
| | A/G , HOWEVER PLEASE SEE 2LA 19,21. |
| | 210.8B3 |
| | |
| | 2)NOTE: PLEASE SEE ROOMS ON ELECTRICAL |
| | PLANS CONTAINING ELECTRICAL EQUIPMENT |
| | AND PANELS, SHALL CONTAIN LABELING FOR |
| | SCUH. RESPONSE LTR MENTIONS THIS IS THE |
| | ARCHITECT'S DECISION TO LABEL ETC. |
| | PLEASE SEE THIS IS REQUIRED AT THIS |
| | TIME. |
| | 110.26 |
| | |
| | 3)NOTE: PLEASE SEE IT IS STILL UNCLEAR |
| | HOW NEW TENANT SPACE IS BEING FED AND |
| | FROM WHAT "SERVICE" IT IS BEING FED |
| | FROM. |
| | PLEASE SEE RESPONSE LTR MENTION THE NEW |
| | LOADFOR NEW TENANT SPACE IS BEING |
| | ADDED TO EXISTING 2000A SERVICE AND |
| | TOTAL NEW LOAD FOR EXSITING AND NEW IS |
| | 1,496A'S.( RESPONSE LTR SEEMS TO BE |
| | MISPRINTED SHOWING 1,986A'S) |
| | NEW AND EXISTING LOADS ARE NOTED ON |
| | RISER SHEET E5.02 AS WELL. |
| | THIS IS A COMBINATION OF NEW AND |
| | EXISTING LOADS TO "EXISTING SERVICE". |
| | HOWEVER, PLEASE SEE NOTES TO RISER WHICH |
| | MENTIONS A "NEW SERVICE" IS BEING ADDED |
| | AND "CHANGE OVER ELECTRICAL SERVICE" |
| | WITH FPL?? |
| | PLEASE CLARIFY. |
| | IF NEW TENANT ELECTRICAL METER AND MAIN |
| | IS GOING TO BE FED FROM EXISTING 2000A |
| | SERVICE, A"SERVICE CHANGE OVER" WITH |
| | FPL WOULD NOT BE REQUIRED. |
| | PLEASE ALSO SEE"SHEET NOTES" WHICH |
| | MENTIONS, NO NEW LOADS ARE CONNECTED TO |
| | "EXISTING SERVICE", YET PREVIOUS NOETS |
| | AND RESPONSE LTR MENTIONS SOMETHING |
| | DIFFERENT.? |
| | |
| | PLANS, RISER AND NOTES DO NOT SEEM TO |
| | CORRELATE. |
| | PLEASE SEE IF NEW TENANT SPACE IS BEING |
| | FROM EXISTING SERVICE, THE NEW TEANT |
| | METER AND MAIN WOULD NOT BE A NEW |
| | "SERVICE". |
| | 230.2. |
| | |
| | 4)NOTE: PLEASE SEE RESPONSE TO NOTE #11 |
| | FROM PREVIOUS REVIEW MENTIONS, "ALL |
| | CONTINUOUS LOADS ARE SHOWN AND |
| | CALCUALTED AT 125%. |
| | PLEASE SEE PREVIOUS NOTE #, WAS FOR |
| | SIZING OF OCP OF AHU HEAT LOADS. |
| | PLEASE SEE AHU/ CU A/C SYSTEMS ARE |
| | THERMASTATICALLY CONTROLLED AND ARE NOTE |
| | CONSIDERED "CONTINUOUS LOADS" (3 OR MORE |
| | HRS) |
| | PLEASE SEE 424.3B, WHICH DOES REQUIRE |
| | THE MIN COP TO BE SIZED AT 125% FOR |
| | HEAT. |
| | PLEASE SEE LOADS AND OCPSHOWN FOR |
| | AHU'S, #4, #3 AND #5 DO NOT SEEM TO |
| | PROVIDE OCP AT 125%.? |
| | PLEASE ADJUST. |
| | |
| | 5)NOTE: PLEASE SEE RESPONSE TO PREVIOUS |
| | NOTE #13 WHICH MENTIONS RISERS, ONE |
| | -LINES ETC ARE NOT REQUIRED TO BE |
| | SCALED. THIS IS CONFIRMED AND KNOWN THAT |
| | THESE TIEMS ARE NOT SCALED. PREVIOUS |
| | NOTE WAS NOT FOR THESE ITEMS. |
| | |
| | 6)NOTE: PLEASE SEE 220.12B FOR LOAD |
| | CALCUALTIONS OF TRACK LIGHTING. PLEASE |
| | SEE NOTE AND RESPONSE LTR MENTIONS 50W |
| | PER FIXTURE, HOWEVER CODE REQUIRES MAX |
| | WATTAGE BASED ON LINEAR FT. |
| | |
| | 7)NOTE: PLEASE SEE E3.01, WHICH SHOWS |
| | NEW LIGHTING FIXTURES BEING INSTALLED IN |
| | "FUTURE" TENANT SPACE? |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |