Plan Review Notes
Plan Review Notes For Permit 05070591
Permit Number 05070591
Review Stop E
Sequence Number 2
Notes
Date Text
2005-09-26 00:00:00******** UNSAT ******
  
 PLEASE SEE SOME NOTES FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE SEE ELECTRICAL PLANS INDICATE
 CLOAED IN PARKING AREAS, WHICH MAY
 REQUIRE CHANGES AND AFFECT ELECTRICAL
 PLANS.
 PLEASE ALSO SEE SOME NOTES FROM
 ELECTRICAL REVIEW.
  
 1)NOTE: PLEASE SEE MOST OF KITCHEN/
 BREAK RM AREA RECEPTS WERE CLOUDED FOR
 A/G , HOWEVER PLEASE SEE 2LA 19,21.
 210.8B3
  
 2)NOTE: PLEASE SEE ROOMS ON ELECTRICAL
 PLANS CONTAINING ELECTRICAL EQUIPMENT
 AND PANELS, SHALL CONTAIN LABELING FOR
 SCUH. RESPONSE LTR MENTIONS THIS IS THE
 ARCHITECT'S DECISION TO LABEL ETC.
 PLEASE SEE THIS IS REQUIRED AT THIS
 TIME.
 110.26
  
 3)NOTE: PLEASE SEE IT IS STILL UNCLEAR
 HOW NEW TENANT SPACE IS BEING FED AND
 FROM WHAT "SERVICE" IT IS BEING FED
 FROM.
 PLEASE SEE RESPONSE LTR MENTION THE NEW
 LOADFOR NEW TENANT SPACE IS BEING
 ADDED TO EXISTING 2000A SERVICE AND
 TOTAL NEW LOAD FOR EXSITING AND NEW IS
 1,496A'S.( RESPONSE LTR SEEMS TO BE
 MISPRINTED SHOWING 1,986A'S)
 NEW AND EXISTING LOADS ARE NOTED ON
 RISER SHEET E5.02 AS WELL.
 THIS IS A COMBINATION OF NEW AND
 EXISTING LOADS TO "EXISTING SERVICE".
 HOWEVER, PLEASE SEE NOTES TO RISER WHICH
 MENTIONS A "NEW SERVICE" IS BEING ADDED
 AND "CHANGE OVER ELECTRICAL SERVICE"
 WITH FPL??
 PLEASE CLARIFY.
 IF NEW TENANT ELECTRICAL METER AND MAIN
 IS GOING TO BE FED FROM EXISTING 2000A
 SERVICE, A"SERVICE CHANGE OVER" WITH
 FPL WOULD NOT BE REQUIRED.
 PLEASE ALSO SEE"SHEET NOTES" WHICH
 MENTIONS, NO NEW LOADS ARE CONNECTED TO
 "EXISTING SERVICE", YET PREVIOUS NOETS
 AND RESPONSE LTR MENTIONS SOMETHING
 DIFFERENT.?
  
 PLANS, RISER AND NOTES DO NOT SEEM TO
 CORRELATE.
 PLEASE SEE IF NEW TENANT SPACE IS BEING
 FROM EXISTING SERVICE, THE NEW TEANT
 METER AND MAIN WOULD NOT BE A NEW
 "SERVICE".
 230.2.
  
 4)NOTE: PLEASE SEE RESPONSE TO NOTE #11
 FROM PREVIOUS REVIEW MENTIONS, "ALL
 CONTINUOUS LOADS ARE SHOWN AND
 CALCUALTED AT 125%.
 PLEASE SEE PREVIOUS NOTE #, WAS FOR
 SIZING OF OCP OF AHU HEAT LOADS.
 PLEASE SEE AHU/ CU A/C SYSTEMS ARE
 THERMASTATICALLY CONTROLLED AND ARE NOTE
 CONSIDERED "CONTINUOUS LOADS" (3 OR MORE
 HRS)
 PLEASE SEE 424.3B, WHICH DOES REQUIRE
 THE MIN COP TO BE SIZED AT 125% FOR
 HEAT.
 PLEASE SEE LOADS AND OCPSHOWN FOR
 AHU'S, #4, #3 AND #5 DO NOT SEEM TO
 PROVIDE OCP AT 125%.?
 PLEASE ADJUST.
  
 5)NOTE: PLEASE SEE RESPONSE TO PREVIOUS
 NOTE #13 WHICH MENTIONS RISERS, ONE
 -LINES ETC ARE NOT REQUIRED TO BE
 SCALED. THIS IS CONFIRMED AND KNOWN THAT
 THESE TIEMS ARE NOT SCALED. PREVIOUS
 NOTE WAS NOT FOR THESE ITEMS.
  
 6)NOTE: PLEASE SEE 220.12B FOR LOAD
 CALCUALTIONS OF TRACK LIGHTING. PLEASE
 SEE NOTE AND RESPONSE LTR MENTIONS 50W
 PER FIXTURE, HOWEVER CODE REQUIRES MAX
 WATTAGE BASED ON LINEAR FT.
  
 7)NOTE: PLEASE SEE E3.01, WHICH SHOWS
 NEW LIGHTING FIXTURES BEING INSTALLED IN
 "FUTURE" TENANT SPACE?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW