2005-09-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 COMMENTS RELATED TO PREVIOUS REVIEW,
 NUMBERING REMAINING THE SAME FOR
 CONSISTENCY.
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)THE ARCHITECT'S TITLE BLOCK IS
 LACKING INFORMATION REQUIRED BY
 FAC61G1-16.003,004.
  
 AN ARCHITECT BUSINESS NUMBER WAS
 PROVIDED, BUT IS FOR PIERCE GOODWIN
 ALEXANDER & LINVIL INC., NOT PGAL OR
 PIERCE GOODWIN ALEXANDER & LINVIL.IF
 YOU DISAGREE THAT THE REQUIREMENT FOR
 THE TWO NAMES AS THEY APPEAR ON THE PLAN
 APPLIES, PLEASE CONTACT THE ATTORNEY FOR
 THE FLORIDA BOARD OF ARCHITECTS; LES
 SMITH, 850-402-4100.
  
 3.)THIS IS AN OVER 50% IMPROVEMENT
 FBC3401.7.2.6.SOME COMMENTS MAY RELATE
 TO THIS CODE SECTION.SEE PROPERTY
 APPRAISER'S VALUATION ($2,166,310).
  
 A RESPONSE WAS PROVIDED STATING THAT
 THIS DOES NOT APPLY BECAUSE IT IS A
 TENANT IMPROVEMENT.PLEASE READ THE
 CODE REFERRED, STATES REPAIRS AND
 ALTERATIONS.THIS IS AN ALTERATION.
  
 A CERTIFIED APPRAISAL WAS PROVIDED TO
 LUIS MARTINEZ FOR SUBMITTAL TO THE
 BUILDING OFFICIAL FOR CONSIDERATION.
  
 4.)THIS PROPERTY IS IN A FLOOD ZONE,
 A9. NOTE FLOOR ELEVATIONS, TO BE 6IN
 ABOVE BFE OF 13'.CITY OF WEST PALM
 BEACH MUNICIPAL CODE 94-546(B)(2).
 PROVIDE EXISTING FFE AND PROPOSED.
  
 ENGINEERING FROM PARAMOUNT ENGINEERING
 GROUP WAS PROVIDED.IF YOU WISH TO USE
 THIS TO SHOW CODE COMPLIANCE, THE
 CERTIFICATE OF AUTHORIZATION NUMBER FOR
 THE FIRM IS TO BE INCLUDED ON THE
 DOCUMENT AS WELL AS THE PRINTED NAME AND
 LICENSE NUMBER OF THE INDIVIDUAL SEALING
 THE DOCUMENT, FAC61G15-23.002.ALL
 ENGINEERING SUBMITTED FOR PUBLIC RECORD
 ARE TO BE SIGNED, SEALED AND DATED
 ORIGINALS.
  
 NOTING THE FFE (FINISHED FLOOR
 ELEVATION) ON SHEET A0.01 IS ACCEPTABLE.
 HOWEVER, PLEASE CLARIFY WHAT BOW, EP AND
 ELEVATION (AT ELEVATION MARKS, A0.01)
 REPRESENT.SEE LEGEND ON PARAMOUNT'S
 ENGINEERING.THE PLANS SHOULD CLEARLY
 SHOW CODE COMPLIANCE.NOTE THAT
 PARAMOUNT'S BOW NOTES ARE FOR THE
 SIDEWALK, AND DO NOT SHOW A NEGATIVE
 ELEVATION.THE FLOOR PLAN SHOWS
 NEGATIVE ELEVATIONS AND BOW WITHIN THE
 BUILDING.I BELIEVE THIS NOTE, BOW,
 REFERS TO THE SIDEWALK ONLY.
  
 5.)THIS PROPERTY IS IN AN AREA WHICH
 REQUIRES A SOILS INVESTIGATION REPORT
 FBC*1804.2.2.THIS PERMIT WILL BE
 ISSUED WITH A PROVISO THAT A SOILS
 INVESTIGATION REPORT WILL BE SUBMITTED,
 REVIEWED BY ENGINEER OF RECORD, PRIOR TO
 FOOTING INSPECTION.
  
 A SOILS REPORT WAS SUBMITTED.THE
 CERTIFICATE OF AUTHORIZATION NUMBER FOR
 TIERRA IS TO BE ON THE TITLE BLOCK, AND
 A SIGNED SEALED DATED ORIGINAL IS
 REQUIRED FAC61G15-23.002.
  
 6.)ADDRESSED.
  
 7.)PROVIDE INFORMATION ABOUT THE
 EXISTING BUILDING - MINIMUM BUILDING
 TYPE AND PROTECTED OR UNPROTECTED FBC
 CHAPTER 6; HEIGHT, AREA.
  
 TYPE I WAS DECLARED.COMBUSTIBLES NOT
 ALLOWED IN TYPE I CONSTRUCTION,
 FBC707.1.REVISE ALL AFFECTED DETAILS
 ON ALL SHEETS, SUCH AS DETAILS ON A0.31
 WHICH SHOW WOOD BLOCKING, AND AJ-A0.10
 WHICH SHOWS WOOD FRAMING.
  
 40,000 SQUARE FEET WAS DECLARED AS
 BUILDING SIZE.ISN'T THIS THE TENANT
 SPACE, NOT THE TOTAL BUILDING SIZE?SEE
 FBC CHAPTER 2, DEFINITIONS.IT APPEARS
 THAT THE BUILDING IS 102820 SF, SHEET
 A100.
  
 8.)PROVIDE THE FIRE SPRINKLER PLANS,
 FBC104.3.1.1(5).
  
 NOT ADDRESSED.THIS IS REQUIRED BY BOTH
 FLORIDA BUILDING CODE AND FLORIDA
 STATUTE.AS SPRINKLERS ARE REQUIRED FOR
 THIS BUILDING, SPRINKLER DESIGN REQUIRED
 AT THIS TIME.SEE ATTACHED LETTER FROM
 THE DCA.
  
 9.)REGARDING THE USE GROUP NOTE THAT
 STORAGE IS AN ACCESSORY OCCUPANCY, SHEET
 A0.01, THIS IS NOT ACCESSORY
 FBC704.1.2.2(4).
  
 THE STORAGE AREAS ARE NOW MARKED FUTURE
 TENANT.SHOW REQUIRED HORIZONTAL TENANT
 SEPARATION, FBC704.3.PROVIDE
 CALCULATED FIRE RESISTANCE OR APPROVED
 ASSEMBLY, FBC7.
  
 10.)ENCLOSED PARKING GARAGES ARE
 REQUIRED TO COMPLY WITH FBC411.4.2, 6
 AIR CHANGES PER HOUR.PROVIDE
 CALCULATIONS.
  
 NOT ADDRESSED.M201 SHOWS AIR CHANGE OF
 8700 CFM.SHOW COMPLIANCE WITH
 FBC411.4.2, 6 AIR CHANGES PER HOUR.
 CODE COMPLIANCE IS TO BE CLEARLY SHOWN
 ON THE PLAN.
  
 11.)THE ELECTRICAL SERVICE A0.01 IS
 SHOWN OVER AN EXIT DOOR.CLARIFY.
  
 THIS WAS ADDRESSED, BUT THE COMMON PATH
 OF TRAVEL NOW EXCEEDS 75', FBC1004.1.3.
 ALSO, THE PATH OF TRAVEL IS SHOWN ACROSS
 THE DIAGONAL OF THE SPACE.THE ACTUAL
 PATH OF TRAVEL WILL BE GREATER AS THE
 OCCUPANT WILL BE TRAVELLING AROUND
 FURNITURE OR OTHER OBSTRUCTIONS.
  
 12.)NO DOOR IS SHOWN AT THE END OF
 RAMP 130, A0.01.A DOOR IS ALSO
 REQUIRED AT THE TOP OF THE EXIT
 ENCLOSURE TO MAINTAIN FIRE RESISTANCE OF
 THE ACCESSIBLE EXIT.
  
 IT WAS DISCUSSED THAT THE LOBBY AREA
 WOULD BE PROTECTED.NOTE THE FOLLOWING:
  
 THE LIFE SAFETY PLAN AND FLOOR PLAN
 SHOULD CLEARLY SHOW FIRE RESISTANCE
 RATING REQUIREMENTS.PLEASE NOTE THAT
 THE LEGEND INDICATES FIRE RESISTANCE,
 AND NO FIRE RESISTANCE IS SHOWN FOR THE
 NEW PARTITIONS AND INFILL.ON THE FLOOR
 PLAN THERE ARE REFERENCES TO PARTITION
 DETAILS, BUT THEY DO NOT HAVE A PAGE
 REFERENCE.FOR SOMEONE LOOKING AT THE
 PLAN, IT APPEARS THAT THESE NEW WALLS
 ARE NOT FIRE RATED.THE LEGEND SHOWS
 THE GRAPHIC FOR FIRE RESISTANCE (DASHED
 LINES), BUT THIS GRAPHIC HAS NOT BEEN
 INCLUDED FOR ALL WALLS INTENDED TO BE
 FIRE RATED.THE PLAN SHOULD CLEARLY
 SHOW CODE COMPLIANCE REQUIREMENTS FOR
 PERMITTING, CONSTRUCTION AND
 INSPECTIONS.BOTH THE LIFE SAFETY PLAN
 AND THE FLOOR PLAN ARE NOT CLEAR.
  
 A FIRE RATING IS SHOWN BETWEEN THIS
 TENANT SPACE AND THE ADJACENT TENANT
 SPACE WITH A NOTE ON A0.01, BUT NOT ON
 THE FLOOR PLAN A2.01.
  
 AS DISCUSSED IN THE MEETING 9/22/05,
 THIS PERMIT CAN BE ISSUED WITH A PROVISO
 THAT THE LIFE SAFETY AND FLOOR PLANS BE
 REVISED TO CLEARLY INDICATE WHICH WALLS
 ARE TO BE PROTECTED.
  
 THE ROLLUP DOORS ARE STILL SHOWN ON THE
 FLOOR PLANS WHERE YOU ARE ELIMINATING
 THE LOADING DOCK OPENINGS.IF THE
 OPENINGS ARE BLOCKED UP, WHY ARE DOORS
 STILL ON THE PLAN?THE DOOR SCHEDULE ON
 A2.01 SHOWS THE DOORS AS REMAINING.
  
 13.)TWO EXITS REQUIRED REMOTELY
 LOCATED FBC1004.1.4.STAIR 2, A0.02
 LEADS THROUGH THE ELEVATOR LOBBY.THE
 OTHER TWO STAIRS ARE LESS THAN 1/3
 DISTANCE APART.
  
 ADDRESSED, BUT PLEASE REVISE AS PER ITEM
 12 TO CLEARLY SHOW FIRE RESISTANCE
 REQUIREMENTS.
  
 14.)ADDRESSED.
  
 15.)SHOW OCCUPANCY SEPARATION
 FBC704.1, HORIZONTAL SEPARATION BETWEEN
 BETWEEN THE STORAGE AND BUSINESS AREAS.
 PROVIDE A DETAIL WITH A LISTED ASSEMBLY
 OR CALCULATED FIRE RESISTANCE FBC709.
  
 THE OCCUPANCY HAS NOW CHANGED FROM
 STORAGE TO FUTURE TENANT, BUSINESS.A 1
 HOUR TENANT SEPARATION REQUIRED, SEE
 ITEM 9.
  
 16.)ADDRESSED.
  
 17.)ADDRESSED.
  
 18.)ADDRESSED.
  
 19.)ADDRESSED.
  
 20.)ADDRESSED.
  
  
 21.)INTERIOR FINISH CLASSIFICATION
 (A0.01) IS TO COMPLY WITH FBC TABLE
 803.3.A0 HAS A NOTE IN REGARDS TO
 INTERIOR FINISHES AND THE UBC, WHICH IS
 NOT THE GOVERNING CODE.
  
 A0.01 WAS REVISED.SEE A0.20.THERE IS
 A NEW NOTE REFERRING TO CLASS II AND
 CLASS IV FLAME SPREADCLASSIFICATIONS.
 I BELIEVE THAT THIS IS FROM THE UBC.
 FBC USES FLAME SPREAD CLASSIFICATIONS A,
 B, AND C.PLEASE REVISE TO BE CODE
 COMPLIANT AS I CANNOT DETERMINE HOW THE
 FLAME SPREAD CLASSIFICATIONS YOU REFER
 TO IN THIS NEW NOTE RELATE TO THE
 REQUIREMENTS OF FBC.THE NOTE ON THE
 PLAN ALSO REFERS TO A CLASS REDUCTION IN
 TABLE FBC803.3.THE TABLE DOES NOT
 REFER TO A CLASS REDUCTION BUT DOES
 PROVIDE MINIMUM REQUIREMENTS.
  
 22.)ADDRESSED.
  
 23.)LANDINGS ARE REQUIRED AT TOP AND
 BOTTOM OF RAMPS IN COMPLIANCE WITH
 FBC11-4.8.4.NOTE THE FOLLOWING:
  
 A.THE LANDING AT THE BOTTOM OF THE
 RAMP IS TO BE 72IN CLEAR, ONLY 60IN
 SHOWN WHEN SCALED, FBC11-4.8.4(2).
  
 THE RAMP WAS WIDENED AT THE BOTTOM TO
 PROVIDE TURNING CLEARANCE AT THE DOOR.
  
 THE 72IN CLEAR REQUIREMENT WAS NOT
 ADDRESSED.THIS APPLIES TO THE LANDING
 RUN AT THE BOTTOM OF THE RAMP.THERE
 IS STILL ONLY 60IN WHEN SCALED.PLEASE
 PUT REQUIRED DIMENSIONS ON THE PLAN ON
 THE LANDINGS TO AVOID CONFUSION.
  
 B.ADDRESSED.
  
 C.ADDRESSED
  
 THE HANDRAILS DO NOT COMPLY WITH
 FBC11-4.8.5(2).THEY ARE TO EXTEND 18IN
 BEYOND THE SLOPED SEGMENT.
  
 24.)N/A
  
 25.)SHOW ACCESSIBLE PASSENGER LOADING
 ZONES, FBC11-4.6.6 AND VERTICAL
 CLEARANCE FBC11-4.6.5.
  
 PLEASE SHOW STRIPING FOR THE ACCESS
 AISLE FROM THE LOADING ZONE PARKING
 SPACE TO THE ACCESSIBLE ENTRANCE; CANNOT
 GO BEHIND PARKED CARS.
  
 VERTICAL CLEARANCE WAS ADDRESSED IN THE
 LETTER.PLEASE PUT ON THE PLAN SO THAT
 THE PLAN SHOWS CODE COMPLIANCE.
  
 26.)THE HANDRAIL ON THE GUARDRAIL SIDE
 OF THE STAIR 4-A4.-01 IS TO COMPLY WITH
 FBC11-4.9.4(2), NO EXTENSION AT THE
 BOTTOM IS SHOWN.ALSO SEE FBC11 FIGURE
 11-19(C).
  
 NOT ADDRESSED.SEE STAIR 4 ENLARGED
 PLAN, A4.01 AND SECTION AT STAIR 4,
 A4.01.STAIRS ARE REQUIRED TO HAVE
 HANDRAILS ON BOTH SIDES FBC11-4.9.4.
 THERE SHOULD BE A HANDRAIL ON THE
 GUARDRAIL SIDE OF THE STAIR, ONLY ONE
 SHOWN ALONG THE WALL.THE HANDRAIL ON
 THE GUARDRAIL SIDE IS TO HAVE AN
 EXTENSION, SEE FBC11 FIGURE 11-19C.
  
 27.)A TURNING SPACE OF 60IN REQUIRED
 FOR THE U-TURN AT THE WOMENS BATHROOM
 122, FBC11-4.2.1.
  
 BATHROOM WAS DELETED.A DRINKING
 FOUNTAIN NOW APPEARS NEXT TO THE
 ELEVATOR ROOM 120.WHAT IS THE GRAPHIC
 ADJACENT TO THE DRINKING FOUNTAIN?
  
 28.)ADDRESSED.
  
 29.)ADDRESSED.
  
 30.)ADDRESSED.
  
 31.)ADDRESSED.
  
 32.)ADDRESSED.
  
 33.)PROVIDE THE ELEVATIONS OF THE
 SIDEWALK AND FINISHED FLOOR AT THE TWO
 EXIT DOORS,FBC11-4.1.2.
  
 THIS WILL BE ADDRESSED WHEN
 CLARIFICATION ON ELEVATIONS IS PROVIDED,
 SEE ITEM 4.
  
 34.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED FOR THE NEW EXTERIOR
 DOORS, INTAKE LOUVERS, FAC9B72.
 WWW.FLORIDABUILDING.ORG.
  
 THE DADE COUNTY NOAS SUBMITTED APPEAR
 CODE COMPLIANT.HOWEVER, FLORIDA STATE
 OR LOCAL PRODUCT APPROVALS ARE REQUIRED
 IN ADDITION TO THE EVALUATION REPORT,
 FAC9B72.WWW.FLORIDABUILDING.ORG.
  
 35.)ADDRESSED.
  
 36.)ADDRESSED.
  
 37.)GARAGE EXHAUST IS SHOWN IN THE
 STAIR AND EXIT ENCLOSURES, SEE
 FBC1006.1.3.1.
  
 EXHAUST WAS REVISED.HOWEVER, DUCTWORK
 AND OUTLETS ARE NOW SHOWN THROUGH THE
 EXIT STAIR.SEE FBC1006.1.3.1.
  
 NEW COMMENTS:
  
 38.)TWO ACCESSIBLE MEANS OF EGRESS
 REQUIRED FOR THE FIRST FLOOR,
 FBC11-4.1.3(9).THIS APPLIES TO BOTH
 THE BUSINESS AREAS AND THE PARKING
 GARAGE.
  
 39.)COLUMN LOCATIONS ARE NOTED ON
 VARIOUS SHEETS.IT APPEARS THAT A
 COLUMN SHOULD BE ALONG THE WALL BETWEEN
 FUTURE TENANT 102 AND THE ADJACENT
 TENANT.IF NOT, HOW IS THAT LOAD
 SUPPORTED?
  
 40.)SHEET S1 CONFLICTS WITH THE
 ARCHITECTURALS (RAMP).
  
 41.)PROVIDE ASSEMBLY LISTING AND
 DETAIL FOR PENETRATIONS THROUGH THE
 RATED WALLS.
  
 42.)PLEASE NOTE THAT ALTHOUGH FBC
 TABLE 704.1 REQUIRES A 1 HOUR SEPARATION
 FOR AUTOMOBILE PARKING GARAGES, FIRE MAY
 HAVE OTHER REQUIREMENTS.SEE FIRE
 COMMENTS.A 2 HOUR IS CURRENTLY SHOWN.
 IF A 2 HOUR IS REQUIRED, OPENING
 PROTECTIVES ARE TO COMPLY WITH TABLE
 705.1.2, 1 1/2 HOUR.ONLY 1 HOUR FOR
 THE ELEVATOR DOOR IS SHOWN.
  
 DOOR 100F IS SHOWN AS A 45 MIN. DOOR.
 IF 2 HOUR IS REQUIRED, THIS SHOULD BE 1
 1/2 HR.
  
 DOOR 114, LOCATED IN A 1 HOUR WALL, DOES
 NOT SHOW A FIRE RATING.
  
 THE DOOR AT THE ELEVATOR ROOM DOES NOT
 HAVE A DOOR NUMBER DESIGNATION.
  
 43.)PLEASE SIGN THE OWNER/AGENT LINE
 OF THE ENERGY CALCS.
  
 WHEN RESUBMITTING, REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND SUBMIT OLD SHEETS
 SEPARATELY.TO EXPEDITE PLAN REVIEW,
 PROVIDE A TRANSMITTAL INDICATING HOW
 (AND WHERE) EACH ITEM WAS ADDRESSED.