| 2005-09-22 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | COMMENTS RELATED TO PREVIOUS REVIEW, |
| | NUMBERING REMAINING THE SAME FOR |
| | CONSISTENCY. |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.)THE ARCHITECT'S TITLE BLOCK IS |
| | LACKING INFORMATION REQUIRED BY |
| | FAC61G1-16.003,004. |
| | |
| | AN ARCHITECT BUSINESS NUMBER WAS |
| | PROVIDED, BUT IS FOR PIERCE GOODWIN |
| | ALEXANDER & LINVIL INC., NOT PGAL OR |
| | PIERCE GOODWIN ALEXANDER & LINVIL.IF |
| | YOU DISAGREE THAT THE REQUIREMENT FOR |
| | THE TWO NAMES AS THEY APPEAR ON THE PLAN |
| | APPLIES, PLEASE CONTACT THE ATTORNEY FOR |
| | THE FLORIDA BOARD OF ARCHITECTS; LES |
| | SMITH, 850-402-4100. |
| | |
| | 3.)THIS IS AN OVER 50% IMPROVEMENT |
| | FBC3401.7.2.6.SOME COMMENTS MAY RELATE |
| | TO THIS CODE SECTION.SEE PROPERTY |
| | APPRAISER'S VALUATION ($2,166,310). |
| | |
| | A RESPONSE WAS PROVIDED STATING THAT |
| | THIS DOES NOT APPLY BECAUSE IT IS A |
| | TENANT IMPROVEMENT.PLEASE READ THE |
| | CODE REFERRED, STATES REPAIRS AND |
| | ALTERATIONS.THIS IS AN ALTERATION. |
| | |
| | A CERTIFIED APPRAISAL WAS PROVIDED TO |
| | LUIS MARTINEZ FOR SUBMITTAL TO THE |
| | BUILDING OFFICIAL FOR CONSIDERATION. |
| | |
| | 4.)THIS PROPERTY IS IN A FLOOD ZONE, |
| | A9. NOTE FLOOR ELEVATIONS, TO BE 6IN |
| | ABOVE BFE OF 13'.CITY OF WEST PALM |
| | BEACH MUNICIPAL CODE 94-546(B)(2). |
| | PROVIDE EXISTING FFE AND PROPOSED. |
| | |
| | ENGINEERING FROM PARAMOUNT ENGINEERING |
| | GROUP WAS PROVIDED.IF YOU WISH TO USE |
| | THIS TO SHOW CODE COMPLIANCE, THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER FOR |
| | THE FIRM IS TO BE INCLUDED ON THE |
| | DOCUMENT AS WELL AS THE PRINTED NAME AND |
| | LICENSE NUMBER OF THE INDIVIDUAL SEALING |
| | THE DOCUMENT, FAC61G15-23.002.ALL |
| | ENGINEERING SUBMITTED FOR PUBLIC RECORD |
| | ARE TO BE SIGNED, SEALED AND DATED |
| | ORIGINALS. |
| | |
| | NOTING THE FFE (FINISHED FLOOR |
| | ELEVATION) ON SHEET A0.01 IS ACCEPTABLE. |
| | HOWEVER, PLEASE CLARIFY WHAT BOW, EP AND |
| | ELEVATION (AT ELEVATION MARKS, A0.01) |
| | REPRESENT.SEE LEGEND ON PARAMOUNT'S |
| | ENGINEERING.THE PLANS SHOULD CLEARLY |
| | SHOW CODE COMPLIANCE.NOTE THAT |
| | PARAMOUNT'S BOW NOTES ARE FOR THE |
| | SIDEWALK, AND DO NOT SHOW A NEGATIVE |
| | ELEVATION.THE FLOOR PLAN SHOWS |
| | NEGATIVE ELEVATIONS AND BOW WITHIN THE |
| | BUILDING.I BELIEVE THIS NOTE, BOW, |
| | REFERS TO THE SIDEWALK ONLY. |
| | |
| | 5.)THIS PROPERTY IS IN AN AREA WHICH |
| | REQUIRES A SOILS INVESTIGATION REPORT |
| | FBC*1804.2.2.THIS PERMIT WILL BE |
| | ISSUED WITH A PROVISO THAT A SOILS |
| | INVESTIGATION REPORT WILL BE SUBMITTED, |
| | REVIEWED BY ENGINEER OF RECORD, PRIOR TO |
| | FOOTING INSPECTION. |
| | |
| | A SOILS REPORT WAS SUBMITTED.THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER FOR |
| | TIERRA IS TO BE ON THE TITLE BLOCK, AND |
| | A SIGNED SEALED DATED ORIGINAL IS |
| | REQUIRED FAC61G15-23.002. |
| | |
| | 6.)ADDRESSED. |
| | |
| | 7.)PROVIDE INFORMATION ABOUT THE |
| | EXISTING BUILDING - MINIMUM BUILDING |
| | TYPE AND PROTECTED OR UNPROTECTED FBC |
| | CHAPTER 6; HEIGHT, AREA. |
| | |
| | TYPE I WAS DECLARED.COMBUSTIBLES NOT |
| | ALLOWED IN TYPE I CONSTRUCTION, |
| | FBC707.1.REVISE ALL AFFECTED DETAILS |
| | ON ALL SHEETS, SUCH AS DETAILS ON A0.31 |
| | WHICH SHOW WOOD BLOCKING, AND AJ-A0.10 |
| | WHICH SHOWS WOOD FRAMING. |
| | |
| | 40,000 SQUARE FEET WAS DECLARED AS |
| | BUILDING SIZE.ISN'T THIS THE TENANT |
| | SPACE, NOT THE TOTAL BUILDING SIZE?SEE |
| | FBC CHAPTER 2, DEFINITIONS.IT APPEARS |
| | THAT THE BUILDING IS 102820 SF, SHEET |
| | A100. |
| | |
| | 8.)PROVIDE THE FIRE SPRINKLER PLANS, |
| | FBC104.3.1.1(5). |
| | |
| | NOT ADDRESSED.THIS IS REQUIRED BY BOTH |
| | FLORIDA BUILDING CODE AND FLORIDA |
| | STATUTE.AS SPRINKLERS ARE REQUIRED FOR |
| | THIS BUILDING, SPRINKLER DESIGN REQUIRED |
| | AT THIS TIME.SEE ATTACHED LETTER FROM |
| | THE DCA. |
| | |
| | 9.)REGARDING THE USE GROUP NOTE THAT |
| | STORAGE IS AN ACCESSORY OCCUPANCY, SHEET |
| | A0.01, THIS IS NOT ACCESSORY |
| | FBC704.1.2.2(4). |
| | |
| | THE STORAGE AREAS ARE NOW MARKED FUTURE |
| | TENANT.SHOW REQUIRED HORIZONTAL TENANT |
| | SEPARATION, FBC704.3.PROVIDE |
| | CALCULATED FIRE RESISTANCE OR APPROVED |
| | ASSEMBLY, FBC7. |
| | |
| | 10.)ENCLOSED PARKING GARAGES ARE |
| | REQUIRED TO COMPLY WITH FBC411.4.2, 6 |
| | AIR CHANGES PER HOUR.PROVIDE |
| | CALCULATIONS. |
| | |
| | NOT ADDRESSED.M201 SHOWS AIR CHANGE OF |
| | 8700 CFM.SHOW COMPLIANCE WITH |
| | FBC411.4.2, 6 AIR CHANGES PER HOUR. |
| | CODE COMPLIANCE IS TO BE CLEARLY SHOWN |
| | ON THE PLAN. |
| | |
| | 11.)THE ELECTRICAL SERVICE A0.01 IS |
| | SHOWN OVER AN EXIT DOOR.CLARIFY. |
| | |
| | THIS WAS ADDRESSED, BUT THE COMMON PATH |
| | OF TRAVEL NOW EXCEEDS 75', FBC1004.1.3. |
| | ALSO, THE PATH OF TRAVEL IS SHOWN ACROSS |
| | THE DIAGONAL OF THE SPACE.THE ACTUAL |
| | PATH OF TRAVEL WILL BE GREATER AS THE |
| | OCCUPANT WILL BE TRAVELLING AROUND |
| | FURNITURE OR OTHER OBSTRUCTIONS. |
| | |
| | 12.)NO DOOR IS SHOWN AT THE END OF |
| | RAMP 130, A0.01.A DOOR IS ALSO |
| | REQUIRED AT THE TOP OF THE EXIT |
| | ENCLOSURE TO MAINTAIN FIRE RESISTANCE OF |
| | THE ACCESSIBLE EXIT. |
| | |
| | IT WAS DISCUSSED THAT THE LOBBY AREA |
| | WOULD BE PROTECTED.NOTE THE FOLLOWING: |
| | |
| | THE LIFE SAFETY PLAN AND FLOOR PLAN |
| | SHOULD CLEARLY SHOW FIRE RESISTANCE |
| | RATING REQUIREMENTS.PLEASE NOTE THAT |
| | THE LEGEND INDICATES FIRE RESISTANCE, |
| | AND NO FIRE RESISTANCE IS SHOWN FOR THE |
| | NEW PARTITIONS AND INFILL.ON THE FLOOR |
| | PLAN THERE ARE REFERENCES TO PARTITION |
| | DETAILS, BUT THEY DO NOT HAVE A PAGE |
| | REFERENCE.FOR SOMEONE LOOKING AT THE |
| | PLAN, IT APPEARS THAT THESE NEW WALLS |
| | ARE NOT FIRE RATED.THE LEGEND SHOWS |
| | THE GRAPHIC FOR FIRE RESISTANCE (DASHED |
| | LINES), BUT THIS GRAPHIC HAS NOT BEEN |
| | INCLUDED FOR ALL WALLS INTENDED TO BE |
| | FIRE RATED.THE PLAN SHOULD CLEARLY |
| | SHOW CODE COMPLIANCE REQUIREMENTS FOR |
| | PERMITTING, CONSTRUCTION AND |
| | INSPECTIONS.BOTH THE LIFE SAFETY PLAN |
| | AND THE FLOOR PLAN ARE NOT CLEAR. |
| | |
| | A FIRE RATING IS SHOWN BETWEEN THIS |
| | TENANT SPACE AND THE ADJACENT TENANT |
| | SPACE WITH A NOTE ON A0.01, BUT NOT ON |
| | THE FLOOR PLAN A2.01. |
| | |
| | AS DISCUSSED IN THE MEETING 9/22/05, |
| | THIS PERMIT CAN BE ISSUED WITH A PROVISO |
| | THAT THE LIFE SAFETY AND FLOOR PLANS BE |
| | REVISED TO CLEARLY INDICATE WHICH WALLS |
| | ARE TO BE PROTECTED. |
| | |
| | THE ROLLUP DOORS ARE STILL SHOWN ON THE |
| | FLOOR PLANS WHERE YOU ARE ELIMINATING |
| | THE LOADING DOCK OPENINGS.IF THE |
| | OPENINGS ARE BLOCKED UP, WHY ARE DOORS |
| | STILL ON THE PLAN?THE DOOR SCHEDULE ON |
| | A2.01 SHOWS THE DOORS AS REMAINING. |
| | |
| | 13.)TWO EXITS REQUIRED REMOTELY |
| | LOCATED FBC1004.1.4.STAIR 2, A0.02 |
| | LEADS THROUGH THE ELEVATOR LOBBY.THE |
| | OTHER TWO STAIRS ARE LESS THAN 1/3 |
| | DISTANCE APART. |
| | |
| | ADDRESSED, BUT PLEASE REVISE AS PER ITEM |
| | 12 TO CLEARLY SHOW FIRE RESISTANCE |
| | REQUIREMENTS. |
| | |
| | 14.)ADDRESSED. |
| | |
| | 15.)SHOW OCCUPANCY SEPARATION |
| | FBC704.1, HORIZONTAL SEPARATION BETWEEN |
| | BETWEEN THE STORAGE AND BUSINESS AREAS. |
| | PROVIDE A DETAIL WITH A LISTED ASSEMBLY |
| | OR CALCULATED FIRE RESISTANCE FBC709. |
| | |
| | THE OCCUPANCY HAS NOW CHANGED FROM |
| | STORAGE TO FUTURE TENANT, BUSINESS.A 1 |
| | HOUR TENANT SEPARATION REQUIRED, SEE |
| | ITEM 9. |
| | |
| | 16.)ADDRESSED. |
| | |
| | 17.)ADDRESSED. |
| | |
| | 18.)ADDRESSED. |
| | |
| | 19.)ADDRESSED. |
| | |
| | 20.)ADDRESSED. |
| | |
| | |
| | 21.)INTERIOR FINISH CLASSIFICATION |
| | (A0.01) IS TO COMPLY WITH FBC TABLE |
| | 803.3.A0 HAS A NOTE IN REGARDS TO |
| | INTERIOR FINISHES AND THE UBC, WHICH IS |
| | NOT THE GOVERNING CODE. |
| | |
| | A0.01 WAS REVISED.SEE A0.20.THERE IS |
| | A NEW NOTE REFERRING TO CLASS II AND |
| | CLASS IV FLAME SPREADCLASSIFICATIONS. |
| | I BELIEVE THAT THIS IS FROM THE UBC. |
| | FBC USES FLAME SPREAD CLASSIFICATIONS A, |
| | B, AND C.PLEASE REVISE TO BE CODE |
| | COMPLIANT AS I CANNOT DETERMINE HOW THE |
| | FLAME SPREAD CLASSIFICATIONS YOU REFER |
| | TO IN THIS NEW NOTE RELATE TO THE |
| | REQUIREMENTS OF FBC.THE NOTE ON THE |
| | PLAN ALSO REFERS TO A CLASS REDUCTION IN |
| | TABLE FBC803.3.THE TABLE DOES NOT |
| | REFER TO A CLASS REDUCTION BUT DOES |
| | PROVIDE MINIMUM REQUIREMENTS. |
| | |
| | 22.)ADDRESSED. |
| | |
| | 23.)LANDINGS ARE REQUIRED AT TOP AND |
| | BOTTOM OF RAMPS IN COMPLIANCE WITH |
| | FBC11-4.8.4.NOTE THE FOLLOWING: |
| | |
| | A.THE LANDING AT THE BOTTOM OF THE |
| | RAMP IS TO BE 72IN CLEAR, ONLY 60IN |
| | SHOWN WHEN SCALED, FBC11-4.8.4(2). |
| | |
| | THE RAMP WAS WIDENED AT THE BOTTOM TO |
| | PROVIDE TURNING CLEARANCE AT THE DOOR. |
| | |
| | THE 72IN CLEAR REQUIREMENT WAS NOT |
| | ADDRESSED.THIS APPLIES TO THE LANDING |
| | RUN AT THE BOTTOM OF THE RAMP.THERE |
| | IS STILL ONLY 60IN WHEN SCALED.PLEASE |
| | PUT REQUIRED DIMENSIONS ON THE PLAN ON |
| | THE LANDINGS TO AVOID CONFUSION. |
| | |
| | B.ADDRESSED. |
| | |
| | C.ADDRESSED |
| | |
| | THE HANDRAILS DO NOT COMPLY WITH |
| | FBC11-4.8.5(2).THEY ARE TO EXTEND 18IN |
| | BEYOND THE SLOPED SEGMENT. |
| | |
| | 24.)N/A |
| | |
| | 25.)SHOW ACCESSIBLE PASSENGER LOADING |
| | ZONES, FBC11-4.6.6 AND VERTICAL |
| | CLEARANCE FBC11-4.6.5. |
| | |
| | PLEASE SHOW STRIPING FOR THE ACCESS |
| | AISLE FROM THE LOADING ZONE PARKING |
| | SPACE TO THE ACCESSIBLE ENTRANCE; CANNOT |
| | GO BEHIND PARKED CARS. |
| | |
| | VERTICAL CLEARANCE WAS ADDRESSED IN THE |
| | LETTER.PLEASE PUT ON THE PLAN SO THAT |
| | THE PLAN SHOWS CODE COMPLIANCE. |
| | |
| | 26.)THE HANDRAIL ON THE GUARDRAIL SIDE |
| | OF THE STAIR 4-A4.-01 IS TO COMPLY WITH |
| | FBC11-4.9.4(2), NO EXTENSION AT THE |
| | BOTTOM IS SHOWN.ALSO SEE FBC11 FIGURE |
| | 11-19(C). |
| | |
| | NOT ADDRESSED.SEE STAIR 4 ENLARGED |
| | PLAN, A4.01 AND SECTION AT STAIR 4, |
| | A4.01.STAIRS ARE REQUIRED TO HAVE |
| | HANDRAILS ON BOTH SIDES FBC11-4.9.4. |
| | THERE SHOULD BE A HANDRAIL ON THE |
| | GUARDRAIL SIDE OF THE STAIR, ONLY ONE |
| | SHOWN ALONG THE WALL.THE HANDRAIL ON |
| | THE GUARDRAIL SIDE IS TO HAVE AN |
| | EXTENSION, SEE FBC11 FIGURE 11-19C. |
| | |
| | 27.)A TURNING SPACE OF 60IN REQUIRED |
| | FOR THE U-TURN AT THE WOMENS BATHROOM |
| | 122, FBC11-4.2.1. |
| | |
| | BATHROOM WAS DELETED.A DRINKING |
| | FOUNTAIN NOW APPEARS NEXT TO THE |
| | ELEVATOR ROOM 120.WHAT IS THE GRAPHIC |
| | ADJACENT TO THE DRINKING FOUNTAIN? |
| | |
| | 28.)ADDRESSED. |
| | |
| | 29.)ADDRESSED. |
| | |
| | 30.)ADDRESSED. |
| | |
| | 31.)ADDRESSED. |
| | |
| | 32.)ADDRESSED. |
| | |
| | 33.)PROVIDE THE ELEVATIONS OF THE |
| | SIDEWALK AND FINISHED FLOOR AT THE TWO |
| | EXIT DOORS,FBC11-4.1.2. |
| | |
| | THIS WILL BE ADDRESSED WHEN |
| | CLARIFICATION ON ELEVATIONS IS PROVIDED, |
| | SEE ITEM 4. |
| | |
| | 34.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVALS REQUIRED FOR THE NEW EXTERIOR |
| | DOORS, INTAKE LOUVERS, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG. |
| | |
| | THE DADE COUNTY NOAS SUBMITTED APPEAR |
| | CODE COMPLIANT.HOWEVER, FLORIDA STATE |
| | OR LOCAL PRODUCT APPROVALS ARE REQUIRED |
| | IN ADDITION TO THE EVALUATION REPORT, |
| | FAC9B72.WWW.FLORIDABUILDING.ORG. |
| | |
| | 35.)ADDRESSED. |
| | |
| | 36.)ADDRESSED. |
| | |
| | 37.)GARAGE EXHAUST IS SHOWN IN THE |
| | STAIR AND EXIT ENCLOSURES, SEE |
| | FBC1006.1.3.1. |
| | |
| | EXHAUST WAS REVISED.HOWEVER, DUCTWORK |
| | AND OUTLETS ARE NOW SHOWN THROUGH THE |
| | EXIT STAIR.SEE FBC1006.1.3.1. |
| | |
| | NEW COMMENTS: |
| | |
| | 38.)TWO ACCESSIBLE MEANS OF EGRESS |
| | REQUIRED FOR THE FIRST FLOOR, |
| | FBC11-4.1.3(9).THIS APPLIES TO BOTH |
| | THE BUSINESS AREAS AND THE PARKING |
| | GARAGE. |
| | |
| | 39.)COLUMN LOCATIONS ARE NOTED ON |
| | VARIOUS SHEETS.IT APPEARS THAT A |
| | COLUMN SHOULD BE ALONG THE WALL BETWEEN |
| | FUTURE TENANT 102 AND THE ADJACENT |
| | TENANT.IF NOT, HOW IS THAT LOAD |
| | SUPPORTED? |
| | |
| | 40.)SHEET S1 CONFLICTS WITH THE |
| | ARCHITECTURALS (RAMP). |
| | |
| | 41.)PROVIDE ASSEMBLY LISTING AND |
| | DETAIL FOR PENETRATIONS THROUGH THE |
| | RATED WALLS. |
| | |
| | 42.)PLEASE NOTE THAT ALTHOUGH FBC |
| | TABLE 704.1 REQUIRES A 1 HOUR SEPARATION |
| | FOR AUTOMOBILE PARKING GARAGES, FIRE MAY |
| | HAVE OTHER REQUIREMENTS.SEE FIRE |
| | COMMENTS.A 2 HOUR IS CURRENTLY SHOWN. |
| | IF A 2 HOUR IS REQUIRED, OPENING |
| | PROTECTIVES ARE TO COMPLY WITH TABLE |
| | 705.1.2, 1 1/2 HOUR.ONLY 1 HOUR FOR |
| | THE ELEVATOR DOOR IS SHOWN. |
| | |
| | DOOR 100F IS SHOWN AS A 45 MIN. DOOR. |
| | IF 2 HOUR IS REQUIRED, THIS SHOULD BE 1 |
| | 1/2 HR. |
| | |
| | DOOR 114, LOCATED IN A 1 HOUR WALL, DOES |
| | NOT SHOW A FIRE RATING. |
| | |
| | THE DOOR AT THE ELEVATOR ROOM DOES NOT |
| | HAVE A DOOR NUMBER DESIGNATION. |
| | |
| | 43.)PLEASE SIGN THE OWNER/AGENT LINE |
| | OF THE ENERGY CALCS. |
| | |
| | WHEN RESUBMITTING, REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND SUBMIT OLD SHEETS |
| | SEPARATELY.TO EXPEDITE PLAN REVIEW, |
| | PROVIDE A TRANSMITTAL INDICATING HOW |
| | (AND WHERE) EACH ITEM WAS ADDRESSED. |