| 2005-08-10 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT A0.20 ROOM FINISH SCHEDULE. |
| | SUBMIT MANUF. SPECIFICATIONS FOR SEALER |
| | FOR MEN/WOMEN TOILET ROOM FLOORS. - |
| | SUBMIT MANUF. SPECIFICATIONS FOR THE |
| | SATIN PAINT TO SHOW THAT IT IS |
| | NONABSORBENT AS REQUIRED BY SECTION |
| | 1204.2 BLDG CODE. - BASE FINISH |
| | INDICATES WOOD BASE. INDICATE HOW THE |
| | WOOD BASE WILL BE NONABSORBENT AS |
| | REQUIRED IN SECTION 1204.2. |
| | 2. ALL ARCHITECTURAL SHEETS. A TITLE |
| | BLOCK NUST APPEAR ON ALL ARCHITECTURAL |
| | DRAWINGS, AND MUST, AT A MINIMUM CONTAIN |
| | THE FOLLOWING INFORMATION: |
| | (6) A SPACE FOR THE PRINTED NAME OF THE |
| | PERSON SEALING THE DOCUMENT. FAC |
| | 61G1-16.004(6) & FS 481.2055. |
| | 3. ALL MECH. ELECT. & PLMG. SHEETS. |
| | ENGINEERS SHALL INDICATE THEIR NAME AND |
| | LICENSE NUMBER ON EACH SHEET. FAC |
| | 61G15-23.002(2) & FS 471.025. |
| | 4. SHT A2.01 A DRINKING FOUNTAIN IS |
| | REQURED FOR THE STORAGE OCCUPANCY PER |
| | TABLE 403.1. |
| | 5. SHT A2.02 2 DRINKING FOUNTAINS ARE |
| | REQUIRED IN THE OFFICE OCCUPANCY PER |
| | TABLE 403.1. A HIGH/LOW DRINKING |
| | FOUNTAIN WITH ONLY ONE WATER SUPPLY AND |
| | ONLY ONE DRAIN IS CONSIDERED 1 FIXTURE. |
| | 6. SHT A2.02 ROOM 202 BREAK ROOM SINK. |
| | SHOW THE CLEAR FLOOR SPACE REQUIRED BY |
| | SECTION 11-4.24.5. SUBMIT A DETAIL FOR |
| | THE BREAK ROOM SINK SHOWING THE |
| | FOLLOWING: |
| | A. 11-4.24.2 HEIGHT |
| | B. 11-4.24.3 KNEE CLEARACE |
| | C. 11-4.24.4 SINK DEPTH |
| | D. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | E. 11-4.24.7 FAUCETS |
| | 7. SHTS A2.02 & A4.02 WHERE 6 OR MORE |
| | STALLS ARE PROVIDED, IN ADDITION TO THE |
| | STALL COMPLYING WITH 11-4.17.3, AT LEAST |
| | ONE STALL 36" WIDE WITH AN OUTWARD |
| | SWINGING, SELF-CLOSING DOOR AND PARALLEL |
| | GRAB BARS COMPLYING WITH FIG 30(D) AND |
| | 11-4-26 SHALL BE PROVIDED. SECTION |
| | 11-4.22.4. |
| | 8. SHTS A4.02 ALL TOILET ROOMS - SHOW |
| | THE TURNING AREA IN THE TOILET ROOM, NOT |
| | IN THE STALL. SECTION 11-4.22.3 |
| | 9. SHT A4.02 SHOW ACCESSIBLE WC AT 18" |
| | OFF THE WALL TO CENTERLINE OF THE |
| | FIXTURE. FIG. 28. |
| | 10. SHT A4.02 SHOW THE CLEAR FLOOR SPACE |
| | FOR ALL ACCESSIBLE FIXTURES. SECTIONS |
| | 11-4.15.3, 11-4.16.2, 11-4.18.3, AND |
| | 11-4.19.3. |
| | 11. SHT A4.02 SHOW THE FOLLOWING |
| | INFORMATION FOR THE LAVS: |
| | A. 11-4.29.4 EXPOSED PIPES & SURFACES |
| | B. 11-4.19.5 FAUCETS |
| | 12. SHT P501 SANT. RISER DOES NOT |
| | REFLECT THE FLOOR PLAN, NOR DOES IT MEET |
| | CODE REQUIREMENTS. CORRECT THE |
| | FOLLOWING: |
| | A. LAVS FOR THE FIRST FLOOR ARE NOT |
| | SHOWN. SECTION 104.2.1. |
| | B. FIRST FLOOR UNINAL NOT VENTED. |
| | SECTION 901.2.1. |
| | C. CIRCUIT VENT FOR W/C'S 2ND FLOOR, |
| | EACH FIXTURE SHALL CONNECT HORIZONTALLY |
| | TO THE HORIZONTAL BRANCH BEING CIRCUIT |
| | VENTED OR INDIVIDUALLY VENTED. SECTION |
| | 911.1. THE VENT FOR THE CIRCUIT VENT |
| | SHALL CONNECT BETWEEN THE TWO MOST |
| | UPSTREAM FIXTURES, AND THE VENT SHALL |
| | NOT RECIEVE THE DISCHARGE OF ANY SOIL OR |
| | WASTE. SECTION 911.2. |
| | D. THE FLOOR DRAINS ON THE SECOND FLOOR |
| | ARE NOT VENTED. SECTION 901.2.1. |
| | E. DRINKING FOUNTAIN IS NOT VENTED. |
| | SECTION 901.2.1. |
| | F. URINALS ARE NOT VENTED 2ND FLOOR. |
| | SECTION 901.2.1. |
| | 13. SHT P501 WATER RISER DIAGRAM, SHOW |
| | ALL PIPE SIZES. FIRST FLOOR WATER RISER |
| | SHOWS DROPS TO 6 FIXTURES, BUT 8 |
| | FIXTURES ARE SHOWN ON THE FLOOR PLAN. |
| | PLEASE SHOW ALL WATER PIPING. |
| | |