Plan Review Notes
Plan Review Notes For Permit 05070591
Permit Number 05070591
Review Stop M
Sequence Number 1
Notes
Date Text
2005-08-16 00:00:00DENIED:
 1.PLAN SHEET M201, PLAN INDICATES
 GARAGE EXHAUST TERMINATING OVER AN
 EGRESS DOORWAY.PER 2001 FBC(M)401.5.2,
 EXHAUST SHALL NOT BE DIRECTED ONTO
 WALKWAYS.PER 2001 FBC(M)501.3, EXHAUST
 SHALL BE LOCATED AS NOT TO BE DRAWN BACK
 IN BUILDING.
  
 2.PLAN SHEET M202 INDICATES DUCTWORK
 PENETRATING RATED WALLS.PLEASE
 INDICATE LOCATION OF ALL FIRE DAMPERS IN
 ACCORDANCE WITH 2001 FBC(M)607.6.
  
 3.PLAN SHEET M703 NOTES 3, 5, & 6,
 INDICATE CONDENSATE TO TERMINATE INTO
 WASTE.PER CITY CODE, CONDENSATE IS TO
 TERMINATE INTO THE STORM NOT THE
 SANITARY WASTE.
  
 4.AUXILIARY DRAIN LINE ON PLAN SHEET
 M703, INDICATES TERMINATION TO WASTE.
 PER 2001 FBC(M)307.2.3, AUXILIARY DRAIN
 TO TERMINATE AT A CONSPICUOUS POINT TO
 SERVE AS AN ALARM OR INSTALL AN APPROVED
 FLOAT SWITCH.
  
 5.PLEASE INDICATE ANY APPLIANCES
 LOCATED IN THE KITCHEN AREA.
  
 PLEASE SEE ALSO COMMENTS #1 & 2 BY DEWEY
 PALMER ELECTRICAL PLANS EXAMINER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.