| 2005-08-16 00:00:00 | DENIED: |
| | 1.PLAN SHEET M201, PLAN INDICATES |
| | GARAGE EXHAUST TERMINATING OVER AN |
| | EGRESS DOORWAY.PER 2001 FBC(M)401.5.2, |
| | EXHAUST SHALL NOT BE DIRECTED ONTO |
| | WALKWAYS.PER 2001 FBC(M)501.3, EXHAUST |
| | SHALL BE LOCATED AS NOT TO BE DRAWN BACK |
| | IN BUILDING. |
| | |
| | 2.PLAN SHEET M202 INDICATES DUCTWORK |
| | PENETRATING RATED WALLS.PLEASE |
| | INDICATE LOCATION OF ALL FIRE DAMPERS IN |
| | ACCORDANCE WITH 2001 FBC(M)607.6. |
| | |
| | 3.PLAN SHEET M703 NOTES 3, 5, & 6, |
| | INDICATE CONDENSATE TO TERMINATE INTO |
| | WASTE.PER CITY CODE, CONDENSATE IS TO |
| | TERMINATE INTO THE STORM NOT THE |
| | SANITARY WASTE. |
| | |
| | 4.AUXILIARY DRAIN LINE ON PLAN SHEET |
| | M703, INDICATES TERMINATION TO WASTE. |
| | PER 2001 FBC(M)307.2.3, AUXILIARY DRAIN |
| | TO TERMINATE AT A CONSPICUOUS POINT TO |
| | SERVE AS AN ALARM OR INSTALL AN APPROVED |
| | FLOAT SWITCH. |
| | |
| | 5.PLEASE INDICATE ANY APPLIANCES |
| | LOCATED IN THE KITCHEN AREA. |
| | |
| | PLEASE SEE ALSO COMMENTS #1 & 2 BY DEWEY |
| | PALMER ELECTRICAL PLANS EXAMINER. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |