Plan Review Notes
Plan Review Notes For Permit 05070591
Permit Number 05070591
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-08-23 00:00:00******DENIED******
  
 1) PLANS INDICATE THAT DUCT SMOKE
 DETECTORS INITIATE SUPERVISORY SIGNAL
 WHEN ACTIVATED. IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS SHALL
 BE WIRED TO CAUSE A GENERAL FIRE ALARM
 WHERE APPLICABLE.
  
 2) IT APPEARS THAT SOME EXIT SIGNS AT
 FIRST LEVEL EAST SIDE MAY BE MISSING.
 EXIT SIGNS SHALL BE PLACED WHERE OBVIOUS
 AND VISIBLE FROM ALL POINTS OF MEANS OF
 EGRESS, AT A DISTANCE NOT TO EXCEED
 100'.
  
 3) AN ADDRESS ON BUILDING OR SPACE IS
 REQUIRED. MINIMUM 6" FOR MAIN BUILDING
 ADDRESS AND 3" FOR SPECIFIC UNIT OR
 SPACE.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 5) PLEASE INDICATE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILING IN TERMS OF CLASS A,B ORC.
  
 6) PLANS SHOW A PARKING AREA THAT WOULD
 APPEAR TO BE CLOSED. PLEASE NOTE THAT
 NFPA 88A AND OTHER APPLICABLE CODES
 SHALL BE COMPLIED WITH TO MAINTAIN
 REQUIRED 2 HOUR SEPARATION FROM
 REMAINING AREAS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  