| 2005-08-23 00:00:00 | ******DENIED****** |
| | |
| | 1) PLANS INDICATE THAT DUCT SMOKE |
| | DETECTORS INITIATE SUPERVISORY SIGNAL |
| | WHEN ACTIVATED. IN ACCORDANCE WITH LOCAL |
| | REQUIREMENTS, DUCT SMOKE DETECTORS SHALL |
| | BE WIRED TO CAUSE A GENERAL FIRE ALARM |
| | WHERE APPLICABLE. |
| | |
| | 2) IT APPEARS THAT SOME EXIT SIGNS AT |
| | FIRST LEVEL EAST SIDE MAY BE MISSING. |
| | EXIT SIGNS SHALL BE PLACED WHERE OBVIOUS |
| | AND VISIBLE FROM ALL POINTS OF MEANS OF |
| | EGRESS, AT A DISTANCE NOT TO EXCEED |
| | 100'. |
| | |
| | 3) AN ADDRESS ON BUILDING OR SPACE IS |
| | REQUIRED. MINIMUM 6" FOR MAIN BUILDING |
| | ADDRESS AND 3" FOR SPECIFIC UNIT OR |
| | SPACE. |
| | |
| | 4) SEPARATE SHOP DRAWINGS AND PERMITS |
| | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE |
| | ALARM REMODEL. |
| | |
| | 5) PLEASE INDICATE MINIMUM INTERIOR |
| | FINISH CLASSIFICATION FOR WALLS AND |
| | CEILING IN TERMS OF CLASS A,B ORC. |
| | |
| | 6) PLANS SHOW A PARKING AREA THAT WOULD |
| | APPEAR TO BE CLOSED. PLEASE NOTE THAT |
| | NFPA 88A AND OTHER APPLICABLE CODES |
| | SHALL BE COMPLIED WITH TO MAINTAIN |
| | REQUIRED 2 HOUR SEPARATION FROM |
| | REMAINING AREAS. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |