Plan Review Notes
Plan Review Notes For Permit 05070591
Permit Number 05070591
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-27 00:00:00*************UNSAT *****************
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR ADDRESSING, UNIT, SUITE #.
 THE BLDG IS ADDRESSED AS 1016 CLARE.
  
 2)NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCK FOR ARCHITECTUAL AND
 ENGINEERING FIRM. PLEASE SEE 61G1-16.004
 FOR ARCH'S, MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER, THE PRINTED NAME
 AND LICENSE NUMBER FOR ARCHITECT.
 CA # REQUIRE DUNDER FS 481.219
 PLEASE SEE FAC 61G15-23.002 FOR ENG'S
 TITLE BLOCK AND MISSING THE PRINTED NAME
 AND LICENSE NUMBER FOR ENG.
 PLEASE KNOW THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 3)NOTE: PLEASE SEE 210.8B3 FOR KITCHEN
 AREAS IN OTHER THAN DWELLING UNITS,
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 4)NOTE: PLEASE SEE ELEVATOR RMS AND
 REQUIRED DEDICATED CIRCUITS PER 620.23
 AND 620.24
 PLEASE SEE LITGHING AND RECEPTS, MAY NOT
 FEED ANY OTHER AREAS.
  
 5)NOTE: PLEASE SEE SMALL ROOMS/CLOSETS
 ETC SHOWN WITH ELECTRICAL PANELS, SHALL
 BE LABLED AS ELECTRICAL/MECHANICAL ROOMS
 AND SHALL HAVE NO STORAGE. 110.26,408.7
 ETC.
 PLEASE SEE THESE ROOMS WILL BE REQUIRED
 TO HAVE SIGNAGE PLACED ON DOORS FOR
 "ELECTRICAL ROOM","NO STORAGE".
  
 6)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF ALL EM/EXT ITS IS NOTED ON
 PLANS FOR EM FIXTURES TO BE ON WITH
 LOCAL LIGHTING, HOWEVER A COUPLE OF
 AREAS DO NOT SEEM TO CORRELATE WITH
 THIS.
  
 7)NOTE: PLEASE CLARIFY SERVICE SHOWN;
 PLEASE SEE RISER APPEARS TO SHOW AN ALL
 NEW 2000A'S PLUS SERVICE BEING INSTALLED
 TO A NEW ELECTRICAL ROOM FOR FUTURE
 TENANTS? PLEASE CLARIFY HOW THIS IS
 INCLUDE WITH SCOPE OF WORK FOR BLD-OUT
 OF THIS ELECTRICAL SPACE. PLEASE SEE
 PLANS DO NOT APPEAR TO HAVE ANY NEW
 TENANT AREAS IN THIS SCOPE.
 PLEASE ALSO SEE ANY CLEARENCES FOR
 GUTTER/ METER AND DISC'S IS REQUIRED TO
 MEET 110.26.
 THIS SEPARATE ELECTRICAL EQUIPMENT
 NEEDS TO BE UNDER A SEPARATE PERMIT
 WHICH WILL REQUIRE ADDITIONAL, LOAD
 CALCULATIONS ETC.
 215.5
  
 8)NOTE: PLEASE PROIVIDE HP RATING OF
 ELEVATOR MOTOR ALONG WITH ANY SPECIFIC
 CODE LTR ETC.
 KVA LOAD IS SHOWN, HOWEVER MORE
 INFORMATION IS NEEDED.
 215.5
  
 9)NOTE: PLEASE PROVIDE LOAD CALCUALTIONS
 FOR EXISTING 2000A SERVICE AND ANY
 CONNECTED LOADS EXISTING ALONG WITH NEW
 PROPOSED LOADS ADDED.
 215.5,220
  
 10)NOTE: PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125%.
 215.3,230.42 ETC. LIGHTNING, LARGEST
 MOTOR ETC.
  
 11)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU HEAT.125% MIN.
 PLEASE ADJUST OCP, AWG AND ANY CONDUIT
 SIZES.
 240.4,310.16
  
 12)NOTE: PLEASE SHOW TRACK LIGHTING LOAD
 CALCULATIONS PER 220.12.
  
 13)NOTE: PLEASE SEE NOTE MENTIONS "NO
 SCALE" ON PLANS. PLEASE SEE FBC
 104.2.1.3 WHICH REQUIRESA MIN 1/8"
 SCALE.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF ANY OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]