| Date |
Text |
| 2005-07-27 00:00:00 | *************UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | FOR ADDRESSING, UNIT, SUITE #. |
| | THE BLDG IS ADDRESSED AS 1016 CLARE. |
| | |
| | 2)NOTE: PLEASE SEE MISSING INFORMATION |
| | ON TITLE BLOCK FOR ARCHITECTUAL AND |
| | ENGINEERING FIRM. PLEASE SEE 61G1-16.004 |
| | FOR ARCH'S, MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER, THE PRINTED NAME |
| | AND LICENSE NUMBER FOR ARCHITECT. |
| | CA # REQUIRE DUNDER FS 481.219 |
| | PLEASE SEE FAC 61G15-23.002 FOR ENG'S |
| | TITLE BLOCK AND MISSING THE PRINTED NAME |
| | AND LICENSE NUMBER FOR ENG. |
| | PLEASE KNOW THIS IS REQUIRED ON ALL |
| | SHEETS AND FOR ALL TRADES WHEATHER OR |
| | NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 3)NOTE: PLEASE SEE 210.8B3 FOR KITCHEN |
| | AREAS IN OTHER THAN DWELLING UNITS, |
| | WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| | KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO EACH AND EVERY |
| | 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| | RECEPTACLE, WHETHER OR NOT THE |
| | RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| | |
| | |
| | 4)NOTE: PLEASE SEE ELEVATOR RMS AND |
| | REQUIRED DEDICATED CIRCUITS PER 620.23 |
| | AND 620.24 |
| | PLEASE SEE LITGHING AND RECEPTS, MAY NOT |
| | FEED ANY OTHER AREAS. |
| | |
| | 5)NOTE: PLEASE SEE SMALL ROOMS/CLOSETS |
| | ETC SHOWN WITH ELECTRICAL PANELS, SHALL |
| | BE LABLED AS ELECTRICAL/MECHANICAL ROOMS |
| | AND SHALL HAVE NO STORAGE. 110.26,408.7 |
| | ETC. |
| | PLEASE SEE THESE ROOMS WILL BE REQUIRED |
| | TO HAVE SIGNAGE PLACED ON DOORS FOR |
| | "ELECTRICAL ROOM","NO STORAGE". |
| | |
| | 6)NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF ALL EM/EXT ITS IS NOTED ON |
| | PLANS FOR EM FIXTURES TO BE ON WITH |
| | LOCAL LIGHTING, HOWEVER A COUPLE OF |
| | AREAS DO NOT SEEM TO CORRELATE WITH |
| | THIS. |
| | |
| | 7)NOTE: PLEASE CLARIFY SERVICE SHOWN; |
| | PLEASE SEE RISER APPEARS TO SHOW AN ALL |
| | NEW 2000A'S PLUS SERVICE BEING INSTALLED |
| | TO A NEW ELECTRICAL ROOM FOR FUTURE |
| | TENANTS? PLEASE CLARIFY HOW THIS IS |
| | INCLUDE WITH SCOPE OF WORK FOR BLD-OUT |
| | OF THIS ELECTRICAL SPACE. PLEASE SEE |
| | PLANS DO NOT APPEAR TO HAVE ANY NEW |
| | TENANT AREAS IN THIS SCOPE. |
| | PLEASE ALSO SEE ANY CLEARENCES FOR |
| | GUTTER/ METER AND DISC'S IS REQUIRED TO |
| | MEET 110.26. |
| | THIS SEPARATE ELECTRICAL EQUIPMENT |
| | NEEDS TO BE UNDER A SEPARATE PERMIT |
| | WHICH WILL REQUIRE ADDITIONAL, LOAD |
| | CALCULATIONS ETC. |
| | 215.5 |
| | |
| | 8)NOTE: PLEASE PROIVIDE HP RATING OF |
| | ELEVATOR MOTOR ALONG WITH ANY SPECIFIC |
| | CODE LTR ETC. |
| | KVA LOAD IS SHOWN, HOWEVER MORE |
| | INFORMATION IS NEEDED. |
| | 215.5 |
| | |
| | 9)NOTE: PLEASE PROVIDE LOAD CALCUALTIONS |
| | FOR EXISTING 2000A SERVICE AND ANY |
| | CONNECTED LOADS EXISTING ALONG WITH NEW |
| | PROPOSED LOADS ADDED. |
| | 215.5,220 |
| | |
| | 10)NOTE: PLEASE SHOW ALL CONTINUOUS |
| | LOADS AT 125%. |
| | 215.3,230.42 ETC. LIGHTNING, LARGEST |
| | MOTOR ETC. |
| | |
| | 11)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | FOR AHU HEAT.125% MIN. |
| | PLEASE ADJUST OCP, AWG AND ANY CONDUIT |
| | SIZES. |
| | 240.4,310.16 |
| | |
| | 12)NOTE: PLEASE SHOW TRACK LIGHTING LOAD |
| | CALCULATIONS PER 220.12. |
| | |
| | 13)NOTE: PLEASE SEE NOTE MENTIONS "NO |
| | SCALE" ON PLANS. PLEASE SEE FBC |
| | 104.2.1.3 WHICH REQUIRESA MIN 1/8" |
| | SCALE. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE SET OF ANY OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |