Plan Review Notes
Plan Review Notes For Permit 05070591
Permit Number 05070591
Review Stop B
Sequence Number 1
Notes
Date Text
2005-08-27 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)THE ARCHITECT'S TITLE BLOCK IS
 LACKING INFORMATION REQUIRED BY
 FAC61G1-16.003, 004.
  
 3.)THIS IS AN OVER 50% IMPROVEMENT
 FBC3401.7.2.6.SOME COMMENTS MAY RELATE
 TO THIS CODE SECTION.SEE PROPERTY
 APPRAISER'S VALUATION ($2,166,310).
  
 4.)THIS PROPERTY IS IN A FLOOD ZONE,
 A9. NOTE FLOOR ELEVATIONS, TO BE 6IN
 ABOVE BFE OF 13'.CITY OF WEST PALM
 BEACH MUNICIPAL CODE 94-546(B)(2).
 PROVIDE EXISTING FFE AND PROPOSED.
  
 5.)THIS PROPERTY IS IN AN AREA WHICH
 REQUIRES A SOILS INVESTIGATION REPORT
 FBC*1804.2.2.THIS PERMIT WILL BE
 ISSUED WITH A PROVISO THAT A SOILS
 INVESTIGATION REPORT WILL BE SUBMITTED,
 REVIEWED BY ENGINEER OF RECORD, PRIOR TO
 FOOTING INSPECTION.
  
 6.)A0.1, THE AREA CALCULATIONS FOR
 EGRESS CAPACITY DO NOT INCLUDE THE
 ENCLOSED PARKING GARAGE FBC411.4.
  
 7.)PROVIDE INFORMATION ABOUT THE
 EXISTING BUILDING - MINIMUM BUILDING
 TYPE AND PROTECTED OR UNPROTECTED FBC
 CHAPTER 6; HEIGHT, AREA.
  
 8.)PROVIDE THE FIRE SPRINKLER PLANS,
 FBC104.3.1.1(5).
  
 9.)REGARDING THE USE GROUP NOTE THAT
 STORAGE IS AN ACCESSORY OCCUPANCY, SHEET
 A0.01, THIS IS NOT ACCESSORY
 FBC704.1.2.2(4).
  
 10.)ENCLOSED PARKING GARAGES ARE
 REQUIRED TO COMPLY WITH FBC411.4.2, 6
 AIR CHANGES PER HOUR.PROVIDE
 CALCULATIONS.
  
 11.)THE ELECTRICAL SERVICE A0.01 IS
 SHOWN OVER AN EXIT DOOR.CLARIFY.
  
 12.)NO DOOR IS SHOWN AT THE END OF
 RAMP 130, A0.01.A DOOR IS ALSO
 REQUIRED AT THE TOP OF THE EXIT
 ENCLOSURE TO MAINTAIN FIRE RESISTANCE OF
 THE ACCESSIBLE EXIT.
  
 13.)TWO EXITS REQUIRED REMOTELY
 LOCATED FBC1004.1.4.STAIR 2, A0.02
 LEADS THROUGH THE ELEVATOR LOBBY.THE
 OTHER TWO STAIRS ARE LESS THAN 1/3
 DISTANCE APART.
  
 14.)PROVIDE INFORMATION REGARDS WHAT
 WILL BE STORED IN THE STORAGE AREAS AND
 DECLARE SUBCLASSIFICATIONS FBC312.2.
  
 15.)SHOW OCCUPANCY SEPARATION
 FBC704.1, HORIZONTAL SEPARATION BETWEEN
 BETWEEN THE STORAGE AND BUSINESS AREAS.
 PROVIDE A DETAIL WITH A LISTED ASSEMBLY
 OR CALCULATED FIRE RESISTANCE FBC709.
  
 16.)SHOW OCCUPANCY SEPARATION FBC704.1
 BETWEEN ROOMS 260, 211, 212 AND THE
 BUSINESS AREAS ON THE SECOND FLOOR.
  
 17.)SHOW OCCUPANCY SEPARATION
 FBC704.1, SEPARATION BETWEEN THE EXIT
 CORRIDORS AND THE STORAGE AREAS ON THE
 FIRST FLOOR.PROVIDE A DETAIL WITH A
 LISTED ASSEMBLY OR CALCULATED FIRE
 RESISTANCE FBC709.
  
 18.)SHOW OCCUPANCY OF ADJACENT TENANTS
 AND TENANT SEPARATION, FBC704.1.
  
 19.)ALL OPENING PROTECTIVES ARE TO
 COMPLY WITH FBC705.1.2.PLEASE NOTE
 REQUIREMENTS FOR STORAGE OCCUPANCY.
  
 20.)THE EXTERIOR STAIRS IS TO COMPLY
 WITH FBC1006.2.NOTE THAT FIRE
 RESISTANCE REQUIRED BY FBC1006.2.4 IS
 NOT SHOWN ON THE PLAN.
  
 21.)INTERIOR FINISH CLASSIFICATION
 (A0.01) IS TO COMPLY WITH FBC TABLE
 803.3.A0.20 HAS A NOTE IN REGARDS TO
 INTERIOR FINISHES AND THE UBC, WHICH IS
 NOT THE GOVERNING CODE.
  
 22.)THE ELEVATOR ROOM 120 IS TO COMPLY
 WITH FBC3003.7.1.THE PLAN SHOWS THE
 ELEVATOR?S ACCESS IN THE TENANT SPACE.
  
 23.)LANDINGS ARE REQUIRED AT TOP AND
 BOTTOM OF RAMPS IN COMPLIANCE WITH
 FBC11-4.8.4.NOTE THE FOLLOWING:
  
 A.THE LANDING AT THE BOTTOM OF THE
 RAMP IS TO BE 72IN CLEAR, ONLY 60IN
 SHOWN WHEN SCALED, FBC11-4.8.4(2).
  
 B.THE LANDING AT THE TOP SHALL BE NOT
 LESS THAN 60IN CLEAR,48IN SHOWN
 FBC11-4.8.4.(2).
  
 C.IF RAMPS CHANGE DIRECTION AT
 LANDINGS, THE MINIMUM LANDING SIZE SHALL
 BE 60IN BY 60IN.48IN BY 48IN SHOWN,
 FBC11-4.8.4(3).
  
 24.)N/A
  
 25.)SHOW ACCESSIBLE PASSENGER LOADING
 ZONES, FBC11-4.6.6 AND VERTICAL
 CLEARANCE FBC11-4.6.5.
  
 26.)THE HANDRAIL ON THE GUARDRAIL SIDE
 OF THE STAIR 4-A4.-01 IS TO COMPLY WITH
 FBC11-4.9.4(2), NO EXTENSION AT THE
 BOTTOM IS SHOWN.ALSO SEE FBC11 FIGURE
 11-19(C).
  
 27.)A TURNING SPACE OF 60IN REQUIRED
 FOR THE U-TURN AT THE WOMENS BATHROOM
 122, FBC11-4.2.1.
  
 28.)DOORS 208 AND 204, A2.02 ARE TO
 COMPLY WITH FBC11-4.13.7, FIGURE 26.
 THIS IS A WORK AREA TO COMPLY WITH
 FBC11-4.1(3), ACCESSIBLE APPROACH.
  
 29.)SALES OFFICES, SHEET S2, DOORS ARE
 TO COMPLY WITH MANEUVERING CLEARANCE ON
 THE PULL SIDE, FBC11-4.13.6, FIGURE 11.
 THE FURNITURE IS IN THE REQUIRED CLEAR
 FLOOR SPACE.
  
 30.)PROVIDE DETAILS FOR THE BREAK ROOM
 202 SINK TO COMPLY WITH FBC11-4.24.1
 THROUGH 11-4.24.7.
  
 31.)COFFEE BAR 232 SHOWS A SINK ON
 SOME SHEETS (FOR EXAMPLE, S2, M202) AND
 NOT ON OTHERS (A2.02, P202).PLEASE
 MAKE ALL SHEETS CONSISTENT AND IF THERE
 IS A SINK, PROVIDE A DETAIL COMPLIANT
 WITH FBC11-4.24.1 THROUGH FBC11-4.24.7.
  
 32.)3-A6.00, ELEVATOR CALL BUTTON TO
 BE CENTERED AT 42IN.
  
 33.)PROVIDE THE ELEVATIONS OF THE
 SIDEWALK AND FINISHED FLOOR AT THE TWO
 EXIT DOORS,FBC11-4.1.2.
  
 34.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED FOR THE NEW EXTERIOR
 DOORS, INTAKE LOUVERS, FAC9B72.
 WWW.FLORIDABUILDING.ORG.
  
 35.)PROVIDE INFORMATION IN REGARDS TO
 THE CIRCULAR CARPETED AREAS A2.02 IN THE
 TWO WAITING AREAS.ARE THERE HANGING
 FIXTURES?PROVIDE LOADING INFORMATION
 FBC16, FASTENING.
  
 36.)A2.02, THE HALL 262 DOOR APPEARS
 TO SWING ONTO A COLUMN.
  
 37.)GARAGE EXHAUST IS SHOWN IN THE
 STAIR AND EXIT ENCLOSURES, SEE
 FBC1006.1.3.1.
  
 WHEN RESUBMITTING, REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND SUBMIT OLD SHEETS
 SEPARATELY.TO EXPEDITE PLAN REVIEW,
 PROVIDE A TRANSMITTAL INDICATING HOW
 (AND WHERE) EACH ITEM WAS ADDRESSED.