| 2005-08-27 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.)THE ARCHITECT'S TITLE BLOCK IS |
| | LACKING INFORMATION REQUIRED BY |
| | FAC61G1-16.003, 004. |
| | |
| | 3.)THIS IS AN OVER 50% IMPROVEMENT |
| | FBC3401.7.2.6.SOME COMMENTS MAY RELATE |
| | TO THIS CODE SECTION.SEE PROPERTY |
| | APPRAISER'S VALUATION ($2,166,310). |
| | |
| | 4.)THIS PROPERTY IS IN A FLOOD ZONE, |
| | A9. NOTE FLOOR ELEVATIONS, TO BE 6IN |
| | ABOVE BFE OF 13'.CITY OF WEST PALM |
| | BEACH MUNICIPAL CODE 94-546(B)(2). |
| | PROVIDE EXISTING FFE AND PROPOSED. |
| | |
| | 5.)THIS PROPERTY IS IN AN AREA WHICH |
| | REQUIRES A SOILS INVESTIGATION REPORT |
| | FBC*1804.2.2.THIS PERMIT WILL BE |
| | ISSUED WITH A PROVISO THAT A SOILS |
| | INVESTIGATION REPORT WILL BE SUBMITTED, |
| | REVIEWED BY ENGINEER OF RECORD, PRIOR TO |
| | FOOTING INSPECTION. |
| | |
| | 6.)A0.1, THE AREA CALCULATIONS FOR |
| | EGRESS CAPACITY DO NOT INCLUDE THE |
| | ENCLOSED PARKING GARAGE FBC411.4. |
| | |
| | 7.)PROVIDE INFORMATION ABOUT THE |
| | EXISTING BUILDING - MINIMUM BUILDING |
| | TYPE AND PROTECTED OR UNPROTECTED FBC |
| | CHAPTER 6; HEIGHT, AREA. |
| | |
| | 8.)PROVIDE THE FIRE SPRINKLER PLANS, |
| | FBC104.3.1.1(5). |
| | |
| | 9.)REGARDING THE USE GROUP NOTE THAT |
| | STORAGE IS AN ACCESSORY OCCUPANCY, SHEET |
| | A0.01, THIS IS NOT ACCESSORY |
| | FBC704.1.2.2(4). |
| | |
| | 10.)ENCLOSED PARKING GARAGES ARE |
| | REQUIRED TO COMPLY WITH FBC411.4.2, 6 |
| | AIR CHANGES PER HOUR.PROVIDE |
| | CALCULATIONS. |
| | |
| | 11.)THE ELECTRICAL SERVICE A0.01 IS |
| | SHOWN OVER AN EXIT DOOR.CLARIFY. |
| | |
| | 12.)NO DOOR IS SHOWN AT THE END OF |
| | RAMP 130, A0.01.A DOOR IS ALSO |
| | REQUIRED AT THE TOP OF THE EXIT |
| | ENCLOSURE TO MAINTAIN FIRE RESISTANCE OF |
| | THE ACCESSIBLE EXIT. |
| | |
| | 13.)TWO EXITS REQUIRED REMOTELY |
| | LOCATED FBC1004.1.4.STAIR 2, A0.02 |
| | LEADS THROUGH THE ELEVATOR LOBBY.THE |
| | OTHER TWO STAIRS ARE LESS THAN 1/3 |
| | DISTANCE APART. |
| | |
| | 14.)PROVIDE INFORMATION REGARDS WHAT |
| | WILL BE STORED IN THE STORAGE AREAS AND |
| | DECLARE SUBCLASSIFICATIONS FBC312.2. |
| | |
| | 15.)SHOW OCCUPANCY SEPARATION |
| | FBC704.1, HORIZONTAL SEPARATION BETWEEN |
| | BETWEEN THE STORAGE AND BUSINESS AREAS. |
| | PROVIDE A DETAIL WITH A LISTED ASSEMBLY |
| | OR CALCULATED FIRE RESISTANCE FBC709. |
| | |
| | 16.)SHOW OCCUPANCY SEPARATION FBC704.1 |
| | BETWEEN ROOMS 260, 211, 212 AND THE |
| | BUSINESS AREAS ON THE SECOND FLOOR. |
| | |
| | 17.)SHOW OCCUPANCY SEPARATION |
| | FBC704.1, SEPARATION BETWEEN THE EXIT |
| | CORRIDORS AND THE STORAGE AREAS ON THE |
| | FIRST FLOOR.PROVIDE A DETAIL WITH A |
| | LISTED ASSEMBLY OR CALCULATED FIRE |
| | RESISTANCE FBC709. |
| | |
| | 18.)SHOW OCCUPANCY OF ADJACENT TENANTS |
| | AND TENANT SEPARATION, FBC704.1. |
| | |
| | 19.)ALL OPENING PROTECTIVES ARE TO |
| | COMPLY WITH FBC705.1.2.PLEASE NOTE |
| | REQUIREMENTS FOR STORAGE OCCUPANCY. |
| | |
| | 20.)THE EXTERIOR STAIRS IS TO COMPLY |
| | WITH FBC1006.2.NOTE THAT FIRE |
| | RESISTANCE REQUIRED BY FBC1006.2.4 IS |
| | NOT SHOWN ON THE PLAN. |
| | |
| | 21.)INTERIOR FINISH CLASSIFICATION |
| | (A0.01) IS TO COMPLY WITH FBC TABLE |
| | 803.3.A0.20 HAS A NOTE IN REGARDS TO |
| | INTERIOR FINISHES AND THE UBC, WHICH IS |
| | NOT THE GOVERNING CODE. |
| | |
| | 22.)THE ELEVATOR ROOM 120 IS TO COMPLY |
| | WITH FBC3003.7.1.THE PLAN SHOWS THE |
| | ELEVATOR?S ACCESS IN THE TENANT SPACE. |
| | |
| | 23.)LANDINGS ARE REQUIRED AT TOP AND |
| | BOTTOM OF RAMPS IN COMPLIANCE WITH |
| | FBC11-4.8.4.NOTE THE FOLLOWING: |
| | |
| | A.THE LANDING AT THE BOTTOM OF THE |
| | RAMP IS TO BE 72IN CLEAR, ONLY 60IN |
| | SHOWN WHEN SCALED, FBC11-4.8.4(2). |
| | |
| | B.THE LANDING AT THE TOP SHALL BE NOT |
| | LESS THAN 60IN CLEAR,48IN SHOWN |
| | FBC11-4.8.4.(2). |
| | |
| | C.IF RAMPS CHANGE DIRECTION AT |
| | LANDINGS, THE MINIMUM LANDING SIZE SHALL |
| | BE 60IN BY 60IN.48IN BY 48IN SHOWN, |
| | FBC11-4.8.4(3). |
| | |
| | 24.)N/A |
| | |
| | 25.)SHOW ACCESSIBLE PASSENGER LOADING |
| | ZONES, FBC11-4.6.6 AND VERTICAL |
| | CLEARANCE FBC11-4.6.5. |
| | |
| | 26.)THE HANDRAIL ON THE GUARDRAIL SIDE |
| | OF THE STAIR 4-A4.-01 IS TO COMPLY WITH |
| | FBC11-4.9.4(2), NO EXTENSION AT THE |
| | BOTTOM IS SHOWN.ALSO SEE FBC11 FIGURE |
| | 11-19(C). |
| | |
| | 27.)A TURNING SPACE OF 60IN REQUIRED |
| | FOR THE U-TURN AT THE WOMENS BATHROOM |
| | 122, FBC11-4.2.1. |
| | |
| | 28.)DOORS 208 AND 204, A2.02 ARE TO |
| | COMPLY WITH FBC11-4.13.7, FIGURE 26. |
| | THIS IS A WORK AREA TO COMPLY WITH |
| | FBC11-4.1(3), ACCESSIBLE APPROACH. |
| | |
| | 29.)SALES OFFICES, SHEET S2, DOORS ARE |
| | TO COMPLY WITH MANEUVERING CLEARANCE ON |
| | THE PULL SIDE, FBC11-4.13.6, FIGURE 11. |
| | THE FURNITURE IS IN THE REQUIRED CLEAR |
| | FLOOR SPACE. |
| | |
| | 30.)PROVIDE DETAILS FOR THE BREAK ROOM |
| | 202 SINK TO COMPLY WITH FBC11-4.24.1 |
| | THROUGH 11-4.24.7. |
| | |
| | 31.)COFFEE BAR 232 SHOWS A SINK ON |
| | SOME SHEETS (FOR EXAMPLE, S2, M202) AND |
| | NOT ON OTHERS (A2.02, P202).PLEASE |
| | MAKE ALL SHEETS CONSISTENT AND IF THERE |
| | IS A SINK, PROVIDE A DETAIL COMPLIANT |
| | WITH FBC11-4.24.1 THROUGH FBC11-4.24.7. |
| | |
| | 32.)3-A6.00, ELEVATOR CALL BUTTON TO |
| | BE CENTERED AT 42IN. |
| | |
| | 33.)PROVIDE THE ELEVATIONS OF THE |
| | SIDEWALK AND FINISHED FLOOR AT THE TWO |
| | EXIT DOORS,FBC11-4.1.2. |
| | |
| | 34.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVALS REQUIRED FOR THE NEW EXTERIOR |
| | DOORS, INTAKE LOUVERS, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG. |
| | |
| | 35.)PROVIDE INFORMATION IN REGARDS TO |
| | THE CIRCULAR CARPETED AREAS A2.02 IN THE |
| | TWO WAITING AREAS.ARE THERE HANGING |
| | FIXTURES?PROVIDE LOADING INFORMATION |
| | FBC16, FASTENING. |
| | |
| | 36.)A2.02, THE HALL 262 DOOR APPEARS |
| | TO SWING ONTO A COLUMN. |
| | |
| | 37.)GARAGE EXHAUST IS SHOWN IN THE |
| | STAIR AND EXIT ENCLOSURES, SEE |
| | FBC1006.1.3.1. |
| | |
| | WHEN RESUBMITTING, REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND SUBMIT OLD SHEETS |
| | SEPARATELY.TO EXPEDITE PLAN REVIEW, |
| | PROVIDE A TRANSMITTAL INDICATING HOW |
| | (AND WHERE) EACH ITEM WAS ADDRESSED. |