| 2005-10-20 00:00:00 | ********* UNSAT 2ND REVIEW *********** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | |
| | 1)NOTE: PLEASE SEE MISSING LICENSE |
| | INFORMATION REQUIRED ON TITLE BLOCKS |
| | UNDER FAC 61G15-23.002 AND FS 471.023. |
| | PLEASE SEE TITLE BLOCK WAS REVISED , |
| | HOWEVER TITLE BLOCK AS SHOWN REQUIRES A |
| | CA #. |
| | PLEASE EITHER REVISE AND INLCUDE CA# OR |
| | CORRECT TITLE BLOCKS. |
| | THIS IS REQUIRED ON ALL PAGES AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENT IS |
| | MADE BY ANY OTHER REVIEWER(S). |
| | PLEASE KNOW, ONE COPY ONCE AGAIN SHALL |
| | BE RETAINED AND PLACED IN FILE WITH |
| | OTHER PLANS FROM PREVIOUS REVIEW AND |
| | OTHER PROJECTS FOR THE SAME COMMENTS. |
| | PLEASE ADDRESS. |
| | |
| | 2)NOTE: PLEASE SEE PREVIOUS NOTES WHICH |
| | REQUESTED THE AIC RATINGS FOR ALL NEW |
| | SERVICE EQUIPMENT. |
| | PLEASE SEE THIS INCLUDES MAIN |
| | DISCONNECT, PANEL ETC. |
| | 110.9, 215.5 ETC. |
| | |
| | |
| | 3)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) NOW ATTACHED TO NOTES. |
| | PLEASE SEE THIS IS IN RESPECT TO THE |
| | DESIGN PROFESSIONAL AND REPEAT COMMENTS. |
| | THE STATT STATUES MANDATES A 4X FEE IF |
| | REPEAT COMMENTS ARE NOT ADDRESSED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |