| Date |
Text |
| 2005-07-25 00:00:00 | ************* UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON TITLE BLOCK. |
| | PLEASE SEE RECORDS FOR DEPARTMENT OF BUS |
| | AND PROFESSIONAL REGULATION AND FLORIDA |
| | BOARD OF PROFESSIONAL ENGINEERSDOES |
| | NOT SHOW ANY LICENSING FOR YURASEK AND |
| | HUBBARD ASSC, CONSULTING ENGINEERS AND |
| | PLANNERS. |
| | PLEASE SEE FAC 61G1-16.004 AND FS |
| | 471.023 FOR MISSING REQUIRED LICENSE |
| | INFORMATION. |
| | PLEASE SEE ONE SET OF PLANS WILL BE |
| | RETAINED AND PLACED INTO FILE FOR |
| | POSSIBLE REVIEW BY STATE DBPR AND FBPE. |
| | PLEASE ALSO INCLUDE ALL OTHER |
| | INFORMATION ON TITLE BLOCK, ADDRESS ETC. |
| | PLEASE SEE THIS IS REQUIRED FOR ALL |
| | TRADES AND ALL REVIEWS, WHEATHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 2)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52, MASTER BEDRM ETC. |
| | |
| | 3)NOTE: PLEASE SEE MISSING GFI RECEPTS |
| | PER 210.52C1 FOR KITCHEN COUNTERSPACE. |
| | |
| | 4)NOTE: PLEASE SEE PLANS INDICATE POWER |
| | FOR A WHIRLPOOL TUB, HOWEVER THIS COULD |
| | NOT BE LOCATED ON PANEL SCHEDULE AND DOE |
| | NOT SHOW LOAD.?? 215.5 |
| | PLEASE ALSO SEE 680.71 FOR REQUIRED GFI/ |
| | GFI PROTECTION. |
| | |
| | 5)NOTE: PLEASE VERIFY HEAT LOAD SHOWN |
| | FOR THIS 2-STORY HOUSE OF THIS SIZE. |
| | PLEASE VERIFY KW RATING OF HEAT STRIP. |
| | PLEASE ADJUST IF NEEDED. |
| | PLEASE UNDERSTAND THIS IS ONLY A NOTE: |
| | |
| | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 7)NOTE: PLEASE SEE 210.11C2, 220.16, FOR |
| | MIN OF 1.5KW FOR LAUNDRY/WASHER CIRCUIT. |
| | |
| | 8)NOTE: PLEASE SEE RISER DIAGRAM SHOWS A |
| | MAIN DISCONNECT, HOWEVER PLANS DO NOT |
| | SHOW THIS? |
| | PLEASE CORRELATE. |
| | 215.5 |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWS. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2005-07-22 00:00:00 | IN ELEC FOR REVIEW. |