Plan Review Notes
Plan Review Notes For Permit 05070548
Permit Number 05070548
Review Stop M
Sequence Number 2
Notes
Date Text
2005-08-30 00:00:00MECH. PLAN REVIEW:
 PROVISO:
  
 GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM BUILDING OPENINGS,
 WIDOWS/DOOR/ROOF VENTS.
 PLUS TEN FEET FROM ADJACENT BUILDINGS
 OPENINGS.
  
 LP GAS REQUIRES LICENED GAS CONTRACTOR
 AND MUST SUBMIT GAS PIPING DRAWING WITH
 GAS PERMIT APP.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.