| Plan Review Notes For Permit 05070547 |
| Permit Number |
05070547 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-08-29 00:00:00 | MECH. PLAN REVIEW: | | | PROVISO: | | | | | | 1. GENERATOR EXHAUST MUST BE TEN FEET | | | AWAY FROM ANY BUILDING OPENING, AND TEN | | | FEET AWAY FROM ADJACENT BUILDING | | | OPENINGS.2001FBC/M 804.3.3 | | | TERMANINATION. | | | 2001 FBC/M SECTION 915 REQUIREMENT OF | | | NFPA 37 8.2.3.2EXHAUST SYSTEM | | | TERMINATION. | | | 2. LP GAS REQUIRES LICENED GAS | | | CONTRACTOR AND MUST SUBMIT GAS PIPING | | | DRAWING WITH GAS PERMIT APP. | | | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | | PATTY KRAUSS. | | | | | | PLEASE CALL IF THEAR ANY QUESTIONS. |
|