| Plan Review Notes For Permit 05070547 |
| Permit Number |
05070547 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-08-19 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SEE THE RISER PROVIDED DOES | | | NOT HEVE THE SERVICE FROM THE METER | | | FEEDING THE ATS. | | | | | | 2} THERE MUST BE A SERVICE RATED | | | DISCONNECT PER 225.36 LOCATED PER 225.31 | | | SHOWN ON THE RISER, AT THE ENTRANCE TO | | | THE BUILDING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|