Plan Review Notes
Plan Review Notes For Permit 05070547
Permit Number 05070547
Review Stop E
Sequence Number 2
Notes
Date Text
2005-08-19 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SEE THE RISER PROVIDED DOES
 NOT HEVE THE SERVICE FROM THE METER
 FEEDING THE ATS.
  
 2} THERE MUST BE A SERVICE RATED
 DISCONNECT PER 225.36 LOCATED PER 225.31
 SHOWN ON THE RISER, AT THE ENTRANCE TO
 THE BUILDING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026