| Plan Review Notes For Permit 05070547 |
| Permit Number |
05070547 |
|
| Review Stop |
I |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-09 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05070547 | | | ADD: 2188 VERO BEACH LN | | | CONT: WELLINGTON ELEC | | | TEL: (561)798-8811 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) PROVIDE INFORMATION FOR THE SLAB AND | | | ANCHORING OF GENERATOR, SEE: | | | 1606.1.3 ANCHORAGE AGAINST OVERTURNING, | | | UPLIFT AND SLIDING. STRUCTURAL MEMBERS | | | AND SYSTEMS, AND COMPONENTS AND CLADDING | | | IN A BUILDING OR STRUCTURE SHALL BE | | | ANCHORED TO RESIST WIND-INDUCED | | | OVERTURNING, UPLIFT AND SLIDING AND TO | | | PROVIDE CONTINUOUS LOAD PATHS FOR THESE | | | FORCES TO THE FOUNDATION.WHERE A | | | PORTION OF THE RESISTANCE TO THESE | | | FORCES IS PROVIDED BY DEAD LOAD, THE | | | MINIMUM DEAD LOAD LIKELY TO BE IN PLACE | | | DURING A DESIGN WIND EVENT SHALL BE | | | USED. | | | | | | 3) SURVEY: FL S S 472. 025 REQUIRES | | | SURVEYS TO BE ORIGINALS, SIGNED ,SEALED | | | AND DATED. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | 2005-07-14 00:00:00 | TO "Z" BOX |
|