| 2005-07-28 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | |
| | 1- NEED RE-RECORDED NOTICE OF |
| | COMMENCEMENT. IT EXPIRES AFTER 30DAYS OF |
| | RECORDING AND WORK IS NOT STARTED. |
| | |
| | 2- PROVIDE CURRENT SURVEY TO DETERMINE |
| | EXACT LOCATION OF THE CARPORT. |
| | |
| | 3- FLOOR PLAN IS MISSING DIMENSIONS. HOW |
| | DEEP ID THE PORCH?. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 4- PROVIDE FLORIDA PRODUCT APPROVAL OR |
| | APPLY FOR LOCAL PRODUCT APPROVAL (GO TO |
| | WWW.FLORIDABUILDING.ORG) FOR: |
| | A) FLAT ROOF SYSTEM TO BE USED. |
| | B) SIMPSON CONNECTORS SPECIFIED IN PLANS |
| | |
| | 5- CONNECTOR TS22 SPECIFIED ON ROOF |
| | FRAMING PLANS DOESN'T PROVIDE RESISTANCE |
| | TO LATERAL LOADS. PROVIDE CONNECTOR THAT |
| | PROVIDES LATERAL LOADS RESISTANCE. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 6- SPECIFY ROOF SHEATHING NAIL SIZE AND |
| | SPACING IN ALL ROOF ZONES. SEE TABLE |
| | 2306.1 OF CITY AMENDMENTS TO FBC 2001. |
| | |
| | 7- SECTION-1:A) MISSING THE (4)2X12 |
| | BEAM BEARING HEIGHT. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | B) SPECIFY HOW LONG ARE THE 1/2" |
| | REDHEADS. SEC. 104.2.1.2 CITY AMENDMENTS |
| | |
| | 8- FOUNDATION PLAN IS MISSING |
| | SPECIFICATIONS FOR TERMITE SOIL |
| | TREATMENT. SEC. 1816 FBC 2001. |
| | |