Plan Review Notes
Plan Review Notes For Permit 05070516
Permit Number 05070516
Review Stop B
Sequence Number 1
Notes
Date Text
2005-07-28 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- NEED RE-RECORDED NOTICE OF
 COMMENCEMENT. IT EXPIRES AFTER 30DAYS OF
 RECORDING AND WORK IS NOT STARTED.
  
 2- PROVIDE CURRENT SURVEY TO DETERMINE
 EXACT LOCATION OF THE CARPORT.
  
 3- FLOOR PLAN IS MISSING DIMENSIONS. HOW
 DEEP ID THE PORCH?. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 4- PROVIDE FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL (GO TO
 WWW.FLORIDABUILDING.ORG) FOR:
 A) FLAT ROOF SYSTEM TO BE USED.
 B) SIMPSON CONNECTORS SPECIFIED IN PLANS
  
 5- CONNECTOR TS22 SPECIFIED ON ROOF
 FRAMING PLANS DOESN'T PROVIDE RESISTANCE
 TO LATERAL LOADS. PROVIDE CONNECTOR THAT
 PROVIDES LATERAL LOADS RESISTANCE. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 6- SPECIFY ROOF SHEATHING NAIL SIZE AND
 SPACING IN ALL ROOF ZONES. SEE TABLE
 2306.1 OF CITY AMENDMENTS TO FBC 2001.
  
 7- SECTION-1:A) MISSING THE (4)2X12
 BEAM BEARING HEIGHT. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 B) SPECIFY HOW LONG ARE THE 1/2"
 REDHEADS. SEC. 104.2.1.2 CITY AMENDMENTS
  
 8- FOUNDATION PLAN IS MISSING
 SPECIFICATIONS FOR TERMITE SOIL
 TREATMENT. SEC. 1816 FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.