| 2005-08-26 00:00:00 | ********** UNSAT ********** | | | | | | PLEASE SEE SOME NOTES FROM "PROVISO" | | | WERE NOT CORRECTED FROM PREVIOUS | | | REDLINED REVIEWED PLANS. | | | | | | | | | | | | 1)NOTE: PLEASE SEE PANEL SCHEDULE | | | INDICATES A WHIRLPOOL TUB, HOWEVER PLANS | | | DO NOT SHOW THIS. | | | PLEASE ALSO SEE 680.71 FOR REQUIRED GFI | | | PROTECTION TO BE INDICATED. | | | | | | 2)NOTE: PLEASE SEE ALL RECEPTS WITH AREA | | | OF LAUNDRY RM SINK SHALL BE GFI/ GFI | | | PROTECTED.210.8 | | | | | | | | | 3)NOTE: PLEASE SEE PANEL SCHEDULES | | | INDICATE 80 RECESSED LTS, HOWEVER 80 | | | COULD NOT BE LOCATED ON PLANS. | | | PLEASE ADJUST WHEN FINAL # IS INSTALLED. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | ALONG WITH ANY OTHER REVISIONS BEFORE | | | ROUGH ELECTRICAL INSPECTION IS CALLED | | | IN. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|