| Plan Review Notes For Permit 05070504 |
| Permit Number |
05070504 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-08-18 00:00:00 | | | | PLEASE SEE RISER. THE GENERATOR POWER | | | BACKFEEDS FPL THROUGH THE 100AMP TO THE | | | 200AMP, AND FROM THE DIRECT ATS FEED TO | | | THE 200AMP PANEL. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|