| 2006-10-19 20:48:46 | *** UNSAT **** |
| | |
| | ** PLANS ORIGINALLY REVIEWED BY JAKE LEAHY. |
| | |
| | |
| | 1) NOTE: PLEASE SEE ORIGINAL PLANS WERE REDLINED WIHT |
| | CIRCUITING FOR EM AND EXT LTS PER 700.12E WHICH |
| | REQUIRES THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT |
| | SHALL BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE |
| | NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY |
| | LOCAL SWITCHES. |
| | PLEASE ADJUST. |
| | |
| | 2) NOTE: PLEASE SEE AS THIS WAS A CHANGE IN OCCUPANCY |
| | AND IS NOW ONE OCCUPACNY, ONE SERVICE/ METER AND RISER |
| | SHOULD BE SHOWN. |
| | PLEASE SUBMIT A COMPLETED RISER DIAGRAM AS PLANS DIFFER |
| | FROM RISER SHOWN. PLEASE SEE RISER IS NOT COMPLETE. |
| | 210.70,210.72,240 ETC. |
| | PLEASE ALSO SEE PLANS DO NOT INDICATE THE LOCATION OF |
| | THE PANELS. |
| | 240.4,240.24, 110.26 |
| | |
| | 3) NOTE: PLEASE INDICATE ALL REVSIONS, BY CLOUDS AND |
| | TRIANGLES ON PLANS. |
| | FBC ADMIN SECT 104.1 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |