| Plan Review Notes For Permit 05070499 |
| Permit Number |
05070499 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-28 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE BUILDING REVIEW COMMENTS | | | REGARDING OCCUPANCY CLASSIFICATION. | | | PLEASE NOTE THAT MORE INFORMATION IS | | | REQUIRED. | | | | | | 2) PLEASE ILLUSTRATE THE LOCATIONS OF | | | ALL ILLUMINATED EXIT SIGNS AND EMERGENCY | | | LIGHTING FACILITIES. | | | | | | 3) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 4) PLEASE INDICATE DOOR SWINGS. | | | | | | 5) 2A-10B,C RATED FIRE EXTINGUUISHER (S) | | | ARE REQUIRED TO BE MOUNTED TO SATISFY | | | THE 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | 6) IS THIS TENANT SPACE PART OF A | | | BUILDING PROTECTED BY FIRE SPRINKLER AND | | | FIRE ALARM SYSTEMS? IF SO, SEPARATE SHOP | | | DRAWINGS AND PERMITS ARE REQUIRED FOR | | | FIRE SPRINKLER AND FIRE ALARM REMODEL. | | | | | | 7) CONSTRUCTION, ALTERATION AND | | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 804-4756 | | | PLAN REVIEW(561) 805-6722 |
|