| 2005-08-31 00:00:00 | IN ELEC FOR REVIEW |
| | ******* UNSAT ******** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS AND |
| | SOME NEW NOTES DUE TO CHANGES IN PLANS. |
| | |
| | 1)NOTE: PLEASE SEE LOAD CALCUALTIONS FOR |
| | POOL SUB PANEL WERE REVISED, HOWEVER OCP |
| | FOR FEED TO PANEL WAS NOT INCREASED? |
| | PLEASE SEE PANEL "B" STILL SHOWS 2P60A |
| | BRKR. |
| | PLEASE ALSO CORRELATE RISER WITH PANEL |
| | SCHEDULES. |
| | PLEASE SEE RISER SHOWS POOL PANEL "C" |
| | BEING FED FROM MCB OUTSIDE PANEL, |
| | HOWEVER PANEL SCHEDULE FOR INSIDE PANEL |
| | INDICATES POOL SUB PANEL BEING FED FROM |
| | INSIDE? |
| | PLEASE SEE RISER NOW SHOWS #3'S FOR |
| | INCREASED FEEDERS. |
| | PLEASE SEE NO PANEL SCHEDULE FOR EITHER |
| | OUTSIDE 8/16 CIRCUIT PANELS WERE |
| | SUBMITTED. |
| | PLEASE SEE RISER ONLY INDICATES THE 150A |
| | MCB'S. |
| | PLEASE ADJUST. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE IRRIGATION PUMP ON |
| | PLANS, NOT ON PANEL SCHEDULE OR LOADS. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE PREVIOUS NOTE # 10 |
| | REQUESTED LTR FROM ARCHITECT. PLEASE SEE |
| | LTR SUBMITTED IS REQUIRED TO BE SEALED |
| | AND DATED. FS 481.221 |
| | PLEASE ALSO SEE LETTER IS REQUIRED TO BE |
| | CORRECTLY NOTORIZED AS SET-FORTH UNDER |
| | FS 117.05 FOR NOTORIES. |
| | PLEASE SEE MIN INFORMATION REQUIRED. |
| | THE STAMP AND SIGNATURE IS INSUFFICENT. |
| | |
| | 4)NOTE: PLEASE SEE RISER SHOWS 3-1/0'S |
| | AND #6 CONDUCTORS IN A 1" CONDUIT? |
| | PLEASE SEE TABLE 9 FOR PIPE FILL. |
| | PLEASE ADJUST. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHOULD BE SUBMITTED FOR |
| | REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |