| Plan Review Notes For Permit 05070485 |
| Permit Number |
05070485 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-26 00:00:00 | DENIED; | | | 1.SANITARY RISER DIAGRAM IS NOT | | | COMPLETE. MISSING ONE KITCHEN SINK AND 2 | | | LAUNDRY TUBS. | | | 2.BATHROOM #2 SHOWER IS NOT VENTED. | | | 3.MASTER BATHROOM BITET IS NOT VENTED. | | | 4.PLEASE SHOW THE FUTURE TRAINING ROOM | | | BATHROOM ON THE RISER DIAGRAM SINCE THE | | | PLUMBING MUST BE INSTALLED UNDER THE | | | SLAB. | | | 5. PAGE A4 "FIXTURE CONNECTION SCHEDULE" | | | AUTOMATIC CLOTHS WASHER SHALL HAVE A 2" | | | TRAP. TABLE 709.1. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|