| 2005-07-25 00:00:00 | ************ UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE SOME MISSING RECEPTS |
| | PER 210.52 FOR 2' OF WALL SPACE. MAST |
| | BEDRM, CAFE, |
| | |
| | 2)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | PLEASE SEE MISSING SD'S INSIDE/OUTSIDE |
| | MASTER BEDRM. |
| | |
| | 3)NOTE: PLEASE SEE PANEL SCHEDULE SHOWS |
| | A DEDICATED CIRCUIT FOR A WHIRLPOOL GFI, |
| | HOWEVER THIS RECEPT COULD NOT BE LOCATED |
| | ON PLANS?? |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SEE "GOLF CART CIRCUIT |
| | SHOWN ON PANEL SCHEDULE ALSO, WHICH |
| | COULD NOT BE LOCATED ON PLANS. |
| | 215.5 |
| | |
| | 5)NOTE; PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS FROM MAINS TO SUB |
| | PANELS. |
| | 250.110,250.24, SIZE PER 250.122 |
| | |
| | 6)NOTE: PLEASE SEE MIN AIC RATING FROM |
| | CALCULATIONS ARE OVER MIN AIC RATINGS |
| | SHOWN ON PLANS. |
| | AIC RATINGS SHALL BE OVER AVAILABLE |
| | FAULT CURRENT, RATINGS MAY NOT BE LESS. |
| | 110.9, 215.5 |
| | |
| | 7)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| | ON POOL PANEL @125%. PLEASE SEEE THIS |
| | WILL AFFECT FEEDER FROM PANEL "B" TO |
| | POOL PANEL. LOAD IS ALREADY SHOWN AT |
| | 59A'S. |
| | 215.3,230.42,680.9 ETC. |
| | |
| | 8)NOTE: PLEASE LIST ALL THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE. PLEASE SEE ALL ARC FAULT |
| | PROTECTION SHALL BE LISTED PER 2002 NEC |
| | 210.12 |
| | |
| | 9)NOTE: PLEASE SEE "WHITE-OUT" ON PLANS |
| | IS NOT PERMITTED TO PLANS SIGNED AND |
| | SEALED BY AN ARCHITEC. |
| | FS 481.221 |
| | |
| | 10)NOTE: PLEASE CLARIFY SIGNED PLANS. |
| | PLEASE SEEE PLANS APPEAR TO BE SIGNED |
| | WITH INITIALS? IF INDEED LEGAL SIGNATURE |
| | FOR ARCHITECT, PLEASE PROVIDE A LETTER |
| | TO VERIFY LEGAL SIGNATURE. THIS LETTER |
| | SHALL BE SIGNED, DATED AND SEALED BY |
| | ARCHITECT. THE LETTER SHOULD ALSO BE |
| | NOTORIZED UNDER FS 117. |
| | THIS LTR WILL BE PLACED IN SIGNATURE |
| | FILE FOR ANY FUTURE VERIFICATION. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2005-07-22 00:00:00 | IN ELEC FOR REVIEW |