| Date |
Text |
| 2005-08-09 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1. SHT A-1 IN THE REMOVAL OF ANY PART OF |
| | A DRAINAGE SYSTEM, DEAD ENDS ARE |
| | PROHIBITED. SECTION 704.5. |
| | 2. TABLE 403.1 A SERVICE SINK IS |
| | REQUIRED. |
| | 3. SHT A-4 TOILET ROOM DETAIL SHOW THE |
| | FOLLOWING: |
| | FOR THE W/C: |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | FOR THE LAV: |
| | A. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | B. FAUCETS |
| | 4. SHT M-1 A VENT IS REQUIRED FOR THE |
| | FLOOR DRAIN. SECTION 901.2.1. |
| | 5. SHT M-1 HVAC LAYOUT SHOWS CONDENSATE |
| | "TO FLOOR DRAIN BELOW". THIS IS NOT |
| | APPROVED. CONDENSATE SHALL BE PIPED |
| | SEPARATELY OUTSIDE THE BUILDING TO A |
| | STORM LINE, A CATCH BASIN, A DRYWELL, OR |
| | A PLANTED AREA. CITY CODE SECTION |
| | 90-125(5). A RELIEF VENT IS REQUIRED IF |
| | TIED INTO THE STORM LINE. |
| | 6. SHT M-1 PLUMBING NOTES: |
| | #8 1/4"/FT FOR 2-1/2" AND SMALLER PIPE |
| | PER TABLE 704.1. INDICATE ON NOTE. |
| | #12 AIR CHAMBERS ARE NOT APPROVED. |
| | DELETE FROM NOTE. SECTION 604.9 & PDI-WH |
| | 201. |
| | 7. SHT A-2 INDICATES "SHELL ONLY, TENANT |
| | IMPROVEMENTS BY SEPARATE PERMIT". PLANS |
| | FOR TENANT IMPROVMENTS MIGHT HAVE TO BE |
| | ROUTED TO DBPR, AND CONTACT WITH UTILITY |
| | DEPT. FOR SIZING OF GREASE INTERCEPTOR |
| | MAY BE REQUIRED ONCE SEATING INFORMATION |
| | IS SUBMITTED. |
| | 8. THE FIXTURES THAT WILL BE DELETED FOR |
| | THIS ADDITION APPEAR TO BE COMMON |
| | FACILITIES FOR THE BUILDING. PLEASE |
| | SUBMIT A FLOOR PLAN FOR THE BUILDING |
| | SHOWING ALL SPACES AND THE FACILITIES |
| | FOR EACH SPACE TO VERIFY THAT THESE |
| | FIXTURES CAN BE DELETED. SECTION |
| | 104.2.1. |
| | |