Plan Review Notes
Plan Review Notes For Permit 05070480
Permit Number 05070480
Review Stop P
Sequence Number 1
Notes
Date Text
2005-08-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHT A-1 IN THE REMOVAL OF ANY PART OF
 A DRAINAGE SYSTEM, DEAD ENDS ARE
 PROHIBITED. SECTION 704.5.
 2. TABLE 403.1 A SERVICE SINK IS
 REQUIRED.
 3. SHT A-4 TOILET ROOM DETAIL SHOW THE
 FOLLOWING:
 FOR THE W/C:
 A. 11-4.16.5 FLUSH CONTROLS
 FOR THE LAV:
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. FAUCETS
 4. SHT M-1 A VENT IS REQUIRED FOR THE
 FLOOR DRAIN. SECTION 901.2.1.
 5. SHT M-1 HVAC LAYOUT SHOWS CONDENSATE
 "TO FLOOR DRAIN BELOW". THIS IS NOT
 APPROVED. CONDENSATE SHALL BE PIPED
 SEPARATELY OUTSIDE THE BUILDING TO A
 STORM LINE, A CATCH BASIN, A DRYWELL, OR
 A PLANTED AREA. CITY CODE SECTION
 90-125(5). A RELIEF VENT IS REQUIRED IF
 TIED INTO THE STORM LINE.
 6. SHT M-1 PLUMBING NOTES:
 #8 1/4"/FT FOR 2-1/2" AND SMALLER PIPE
 PER TABLE 704.1. INDICATE ON NOTE.
 #12 AIR CHAMBERS ARE NOT APPROVED.
 DELETE FROM NOTE. SECTION 604.9 & PDI-WH
 201.
 7. SHT A-2 INDICATES "SHELL ONLY, TENANT
 IMPROVEMENTS BY SEPARATE PERMIT". PLANS
 FOR TENANT IMPROVMENTS MIGHT HAVE TO BE
 ROUTED TO DBPR, AND CONTACT WITH UTILITY
 DEPT. FOR SIZING OF GREASE INTERCEPTOR
 MAY BE REQUIRED ONCE SEATING INFORMATION
 IS SUBMITTED.
 8. THE FIXTURES THAT WILL BE DELETED FOR
 THIS ADDITION APPEAR TO BE COMMON
 FACILITIES FOR THE BUILDING. PLEASE
 SUBMIT A FLOOR PLAN FOR THE BUILDING
 SHOWING ALL SPACES AND THE FACILITIES
 FOR EACH SPACE TO VERIFY THAT THESE
 FIXTURES CAN BE DELETED. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS