| Plan Review Notes For Permit 05070480 |
| Permit Number |
05070480 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-15 00:00:00 | DENIED: | | | 1.PLAN SHEET A-2 UBDUCATES NEW REFRIG | | | LINES TO ROOFTOP COND UNIT.PER 2001 | | | FBC 1006.1.3.1, PENETRATIONS INTO OR | | | OPENINGS THROUGH A STAIRWAY ENCLOSURE | | | ARE PROHIBITED EXCEPT FOR THOSE REQUIRED | | | FOR INDEPENDENT STAIRWELL | | | PRESSURIZATION, STANDPIPES & ELECTRICAL | | | CONDUIT SERVING THE STAIRWELL. | | | | | | 2.PLAN SHEET M-1 INDICATES FRESH AIR | | | INTAKE OPENINGS, PER 2001 FBC(M)401.5 - | | | INTAKE OPENINGS SHALL BE LOCATED A | | | MINIMUM OF 10 FT FROM THE LOT LINE. | | | WHERE OPENINGS FRONT ON A STREET OR | | | PUBLIC WAY, THE DISTANCE SHALL BE | | | MEASURED FROM THE CENTERLINE.SEE ALSO | | | 2001 FBC 705.1.1.2. | | | | | | 3.PLAN SHEET M-1, VENT LOUVERS | | | (EXHAUST) SHALL NOT BE DIRECTED ONTO | | | WALKWAYS - 2001 FBC(M)401.5.2. SEE ALSO | | | 2001 FBC(M)501.3.EXHAUST APPEARS TO | | | DISCHARGE ABOVE THE DOOR, PLEASE | | | CLARIFY. | | | | | | 4.PROVIDE ENERGY CALCULATIONS THAT | | | INCLUDE THE ADDITION.2001 FBC CHAPTER | | | 13 SUB-CHAPTER 400. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|