Plan Review Notes
Plan Review Notes For Permit 05070480
Permit Number 05070480
Review Stop M
Sequence Number 1
Notes
Date Text
2005-08-15 00:00:00DENIED:
 1.PLAN SHEET A-2 UBDUCATES NEW REFRIG
 LINES TO ROOFTOP COND UNIT.PER 2001
 FBC 1006.1.3.1, PENETRATIONS INTO OR
 OPENINGS THROUGH A STAIRWAY ENCLOSURE
 ARE PROHIBITED EXCEPT FOR THOSE REQUIRED
 FOR INDEPENDENT STAIRWELL
 PRESSURIZATION, STANDPIPES & ELECTRICAL
 CONDUIT SERVING THE STAIRWELL.
  
 2.PLAN SHEET M-1 INDICATES FRESH AIR
 INTAKE OPENINGS, PER 2001 FBC(M)401.5 -
 INTAKE OPENINGS SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM THE LOT LINE.
 WHERE OPENINGS FRONT ON A STREET OR
 PUBLIC WAY, THE DISTANCE SHALL BE
 MEASURED FROM THE CENTERLINE.SEE ALSO
 2001 FBC 705.1.1.2.
  
 3.PLAN SHEET M-1, VENT LOUVERS
 (EXHAUST) SHALL NOT BE DIRECTED ONTO
 WALKWAYS - 2001 FBC(M)401.5.2. SEE ALSO
 2001 FBC(M)501.3.EXHAUST APPEARS TO
 DISCHARGE ABOVE THE DOOR, PLEASE
 CLARIFY.
  
 4.PROVIDE ENERGY CALCULATIONS THAT
 INCLUDE THE ADDITION.2001 FBC CHAPTER
 13 SUB-CHAPTER 400.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.