2005-07-25 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH THE RESPECTIVE PANEL
 SCHEDULES SUBMITTED.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
  
 2)NOTE: PLEASE SEE LOAD CALCULATIONS DO
 NOT CORRELATE WITH LOADS FINALED ON
 PANEL "B". PLEASE SEE A/C SHALL NOT BE
 FIGURE IN WITH LIGHTING/RECEPT LOADS.
 220.31B.
 PLEASE ALSO SEE POSSIBLE ADJUSTMENT OF
 FEED TO PANEL "B".
 SHOWN AS 60A, HOWEVER WITH LOADS SHOWN,
 THIS 60A'S MAY BE EXCEEDED.
  
 3)NOTE: PLEASE SEE EXISTING "OBEE'S"
 ELECTRICLA IS SHOWN , HOWEVER NO "SHOW
 WINDOW" RECEPT IS SHOWN FOR EXIST? THIS
 WAS REDLINED ON PREVIOUS PERMIT FOR THIS
 REST BUILD OUT AND SHOULD HAVE BEEN
 INSTALLED.
 PLEASE CLARIFY IF EXSITNG OR NEW TO BE
 INSTALLED.
 210.62,220.12.
  
 4)NOT: PLEASE CLARIFY 3-3/0'S SHOWN FOR
 60A FEED TO PANEL"B". PLEASE VERIFY.
  
 5)NOTE: PLEASE VERIFY WATER HEATER OCP,
 BRANCH CIRCUIT SIZE. SHOWN AS 2P-20A'S
 ON 4500VA LOAD. PLEASE SEE
 422.13,422.11, MIN 125%, MAX 150%.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS REQUIRED TO
 BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  