| 2005-07-25 00:00:00 | ********** UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS |
| | AND CORRELATE WITH THE RESPECTIVE PANEL |
| | SCHEDULES SUBMITTED. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF |
| | EM/EXT LTS. |
| | |
| | 2)NOTE: PLEASE SEE LOAD CALCULATIONS DO |
| | NOT CORRELATE WITH LOADS FINALED ON |
| | PANEL "B". PLEASE SEE A/C SHALL NOT BE |
| | FIGURE IN WITH LIGHTING/RECEPT LOADS. |
| | 220.31B. |
| | PLEASE ALSO SEE POSSIBLE ADJUSTMENT OF |
| | FEED TO PANEL "B". |
| | SHOWN AS 60A, HOWEVER WITH LOADS SHOWN, |
| | THIS 60A'S MAY BE EXCEEDED. |
| | |
| | 3)NOTE: PLEASE SEE EXISTING "OBEE'S" |
| | ELECTRICLA IS SHOWN , HOWEVER NO "SHOW |
| | WINDOW" RECEPT IS SHOWN FOR EXIST? THIS |
| | WAS REDLINED ON PREVIOUS PERMIT FOR THIS |
| | REST BUILD OUT AND SHOULD HAVE BEEN |
| | INSTALLED. |
| | PLEASE CLARIFY IF EXSITNG OR NEW TO BE |
| | INSTALLED. |
| | 210.62,220.12. |
| | |
| | 4)NOT: PLEASE CLARIFY 3-3/0'S SHOWN FOR |
| | 60A FEED TO PANEL"B". PLEASE VERIFY. |
| | |
| | 5)NOTE: PLEASE VERIFY WATER HEATER OCP, |
| | BRANCH CIRCUIT SIZE. SHOWN AS 2P-20A'S |
| | ON 4500VA LOAD. PLEASE SEE |
| | 422.13,422.11, MIN 125%, MAX 150%. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD/VOIDED SHEETS REQUIRED TO |
| | BE SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |