| 2005-08-13 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY (CHANGE OF USE).THE PLANS |
| | MUST BE STAMPED AND THE RECEIPT ATTACHED |
| | TO THE APPLICATION. 233-5025 |
| | |
| | 3.)PROVIDE INFORMATION IN REGARDS TO |
| | THE EXISTING BUILDING; BUILDING TYPE FBC |
| | CHAPTER 6, HEIGHT. |
| | |
| | 4.)DECLARE AN OCCUPANCY ON THE PLAN, |
| | FBC304. |
| | |
| | 5.)DECLARE AN OCCUPANT LOAD, FBC TABLE |
| | 1003.1. |
| | |
| | 6.)TWO HOUR OCCUPANCY SEPARATION |
| | REQUIRED FBC TABLE 704.1 FOR A2. |
| | PROVIDE AN APPROVED ASSEMBLY OR |
| | CALCULATED FIRE RESISTANCE FOR WALL AND |
| | CEILING OCCUPANCY SEPARATIONS. |
| | |
| | 7.)M1 SHOWS WALL PENETRATIONS AND |
| | REFRIGERANT LINES IN THE STAIRWAY |
| | ENCLOSURE; NOT ALLOWED AS PER |
| | FBC1006.1.3.1. |
| | |
| | 8.)TWO EXITS REQUIRED; OCCUPANCY |
| | APPEARS TO BE GREATER THAN 50, |
| | FBC1004.2. |
| | |
| | 9.)PRODUCT APPROVALS REQUIRED FOR THE |
| | STOREFRONT.FLORIDA STATE OR LOCAL |
| | PRODUCT APPROVAL REQUIRED IN ADDITION TO |
| | EVALUATION OR TEST REPORT, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 10.)PROVIDE DESIGN PRESSURES FOR THE |
| | STOREFRONT. |
| | |
| | |