| Plan Review Notes For Permit 05070440 |
| Permit Number |
05070440 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-16 00:00:00 | PLAN DENIED | | | 1) PLEASE REFER TO SECTION 401.5.1 | | | FBC(M) INTAKE OPENINGS PLAN PAGE A/C-1. | | | 2) PLEASE PROVIDE INFORMATION ON | | | E-30/12E/A AND E-30/12 O/A PLAN PAGE A/C | | | 1 | | | 3) PLAN PAGE A/C-4 AUXILIARY DRAIN PAN | | | SHALL BE 1 1/2 IN. DEEP PER SECTION | | | 307.2.3 FBC(M) | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|