| Plan Review Notes For Permit 05070440 |
| Permit Number |
05070440 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-15 00:00:00 | ******** UNSAT ******** | | | | | | PLEASE SEE PLANS ARE COMING BACK FOR | | | OTHER COMMENTS PLEASE MAKE THE FOLLOWING | | | CHANGES. | | | | | | 1)NOTE: PLEASE SEE 2002 NEC 210.8B3, | | | WHICH REQUIRES ALL 15- AND 20-AMPERE, | | | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE | | | KITCHENS TO BE GFCI PROTECTED. THIS | | | REQUIREMENT APPLIES TO EACH AND EVERY | | | 15- AND 20-AMPERE, 125-VOLT KITCHEN | | | RECEPTACLE, WHETHER OR NOT THE | | | RECEPTACLE SERVES COUNTERTOP APPLIANCES. | | | | | | | | | 2)NOTE: PLEASE CLARIFY LOAD ON EXISTING | | | SERVICE. IS THERE EXSITNG LOADS? NOTE | | | RISER SEEMS TO INDICATE THIS BLD-OUT AS | | | THE ONLY TENANT THUS FAR? | | | 215.5, 220 | | | | | | 3)NOTE: PLEASE CLARIFY EM LTS? | | | FIXTURE TYPE "C" INDICATE HATCHED | | | FIXTURES W/ BATTERY BACK UP, IS THIS THE | | | SAME FOR FIXTURE "B"? | | | | | | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | PLEASE SUBMIT ONE COPY OF ANY VOIDED | | | SHEETS FOR REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|