| Date |
Text |
| 2005-07-20 00:00:00 | DENIED |
| | |
| | 1)705.7.1 JOINTS INSTALLED IN OR |
| | BE- TWEEN FIRE RESISTANT WALLS, FIRE |
| | RESIS- TANT FLOORS OR FLOOR/ CEILING |
| | ASSEMBLIES AND FIRE RESISTANT ROOFS OR |
| | ROOF/ CEIL- ING ASSEMBLIES SHALL BE |
| | PROTECTED BY AN APPROVED FIRE RESISTANT |
| | JOINT SYSTEM DESIGNED TO RESIST THE |
| | PASSAGE OF FIRE FOR A PERIOD NOT LESS |
| | THAN THE RE- QUIRED FIRE RESISTANCE |
| | RATING OF THE WALL, FLOOR OR FLOOR IN OR |
| | BETWEEN WHICH IT IS INSTALLED. SHOW |
| | COMPLIANCE AT DETAIL 7 ON A4. |
| | |
| | 2) 1204.2 SURROUNDING MATERIALS; |
| | THE WALLS & FLOORS OF ALL PUBLIC REST- |
| | ROOMS SHALL BE LINED WITH NONABSORBANT |
| | MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE |
| | FLOOR. |
| | |
| | 3) 704.2.1.4 CORRIDOR PARTITIONS, |
| | SMOKE STOP PARTITIONS, HORIZONTAL EXIT |
| | PART- ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 4)TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY. |
| | |
| | 5) PROVIDE A DETAIL OF THE EXISTING ONE |
| | HOUR FIRE RATED COLUMNS. SPECIFY THE |
| | MATERIAL AND REQUIRED THICKNESS OF THE |
| | SPRAYED ON FIREPROOFING. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |