Plan Review Notes
Plan Review Notes For Permit 05070398
Permit Number 05070398
Review Stop E
Sequence Number 2
Notes
Date Text
2005-09-09 00:00:00******** UNSAT **********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES.
  
 1)NOTE: PLEASE SEE RANGE OCP HAS NOW
 BEEN CHANGED FROM 70A TO 55A'S. PLEASE
 SEE 240.6, 55A'S IS NOT A SIZE OCP
 AVAILABLE.
  
 2)NOTE: PLEASE SEE "EQUIPMENT GROUNDING"
 CONDUCTOR IS STILL BEING SHOWN TO THE
 FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6,250.24. THIS IS
 INDICATED AS "BOND" ON PLANS.
 ONLY THE UN-GROUNDED (HOT) , AND THE
 GROUNDED (NEUTRAL) CONDUCTORS ARE
 INSTALLED UP TO THE FIRST MEANS OF
 DISCONNECT.
  
 3)NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM SHALL BE COMPLETE AND CONTINUOUS
 AT ONE LOCATION.
 PLEASE SEE RISER SHOWS SOME FROM METER
 AND THEN , FOOTER AND COLD WATER AT MDP?
 PLEASE MOVE GROUNDING ELECTRODES (FOOTER
 STEEL AND COLD WATER ) OVER TO GRND RODS
 SHOWN AT METER.
 250.50,250.58
  
 4)NOTE: PLEASE CORRELATE ALL A/C
 EQUIPMENT. PLEASE SEE RISER INDICATES
 3-#6'S AND 3-#8'S FOR AHU'S AND CU'S
 ALONG WITH EQUIPMENT GROUNDING
 CONDUCTORS(BOND AS SHOWN). PLEASE SEE
 THE AMOUNT OF CONDUCTORS TEND TO
 INDICATE EQUIPMENT AS 3-PHASE. PLEASE
 SEE RISER/SERVICE AND PANELS INDICATE A
 SINLGE PHASE SERVICE.
 PLEASE ADJUST.
 PLEASE ALSO SEE PANEL SCHEDULE INDICATES
 ALL CONDUCTORS AS #6'S, AS #8'S ARE
 NOTED FOR RISER.
 PLEASE ADJUST.
  
 5)NOTE: PLEASE SEE THE RECEPT WAS ADDED
 FOR WHIRLPOOL TUB, HOWEVER NO INDICATION
 OF REQUIRED GFI PROTECTION IS SHOWN?
 PLEASE SEE 680.71
  
 6)NOTE: PLEASE CLARIFY CONTINUOUS LOAD
 OF 125% IS ALREADY FIGURED FOR POOL
 PUMP?
 215.3, 230.42 ETC.
  
 7)NOTE: NEW. PLEASE SEE SD SHOWN FOR
 MASTER BEDRM WILL BE REQUIRED TO BE
 MOVED INTO BEDRM AREA WITHIN THE 12" OF
 HIGHEST CEILING POINT ON A FLAT CEILING.
 NFPA-72 11.8.3.5
 PLEASE SEE A SD WILL BE REQUIRED INSIDE
 "STUDY" AS THIS IS CONSIDERED AN
 ADAPTABLE SLEEPING RM.
 NFPA-72 11.5.1.1
  
 8)NOTE: PLEASE CORRLEATE LOAD AND OCP
 FOR WATER HEATER. SHOWS 9KW FOR WH.
 PLEASE VERIFY THIS , AS 9KW SEEMS TO BE
 HIGH FOR A 60 GAL UNIT. PLEASE SEE MIN
 OCP FOR WH IS 125%. 422.13 MAX 150%.
 (IS THIS 4500 UPPER AND 4500 LOWER?)
  
 9)NOTE: PLEASE SEE TWO GDO'S ARE SHOWN
 ON LOAD CALCS, HOWEVER ONY ONE IS
 INDICATED ON PANEL SCHEDULE.
 PLEASE SEE THREEDEDICATED REFRIGERATOR
 CIRCUITS ARE SHOWN ON PANEL SCHEDULE,
 HOWEVER ONLY TWO ARE IN LOAD CALCS.
  
 10)NOTE: PLEASE SEE LT FIXTURE IN STUDY
 CLOSET WILL BE REQUIRED TO MEET 410.8
 LT IS SHOWN OVER SHELF.
  
 NOTE TO FS 553.80(2)(B), ONLY A NOTICE.
  
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS . (AS PREVIOUSLY
 DONE).
  
 PLEASE SUBMIT THE ABOVEINFORMATION AND
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.