Plan Review Notes For Permit 05070398
Permit Number 05070398
Review Stop P
Sequence Number 1
Notes
Date Text
2005-07-23 00:00:00DENIED;
 1.SIZE ALL PIPE ON RISER DIAGRAM. DEETE
 UN- NEEDED VENTS (SEE RED LINE ONE SET
 OF PLANS)
 2.WATER HEATER DETAIL. ADD NOTE FOR
 PIPING INSULATION FOR HOT WATER
 CIRCULATION SYSTEM PER TABLE 607.1. ALSO
 SHOW THERMAL EXPANSION CONTROL MEANS PER
 SEC. 607.3.
 3.PLUMBING NOTES; CHANGE NOTE TO TO
 COMPLY WITH TABLE 704.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695