Plan Review Notes
Plan Review Notes For Permit 05070398
Permit Number 05070398
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-22 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW ALL ROOM/AREA
 DESIGNATIONS ON PLANS.
 215.5
  
 2)NOTE: PLEASE SEE MISSING BEDRM RECEPT
 PER 210.52
  
 3)NOTE: PLEASE SEE 210.52C2 FOR MISSING
 ISLAND RECEPT. PLEASE ALSO SEE 210.8A6
 FOR REQUIRED GFI PROTECTION.
  
 4)NOTE: PLEASE SEE MISSING RECEPTS/LTS
 FOR AHU'S IN ATTIC SPACE. 210.70,210.63
  
 5)NOTE: PLEASE SEE 250.50 FOR MIN
 GROUNDING ELECTRODE SYSTEM. FOOTER
 STEEL, COLD WATER PIPE(IF METAL.
  
 6)NOTE: PLEASE SEE A MAIN IS REQUIRED IN
 MDP. THIS IS SHOWN AS MLO WITH MORE THAN
 6 SPACES. 230.71
 A MCB WILL BE REQUIRED.
  
 7)NOTE: PLEASE CORRELATE SEC'S FOR MDP.
 PLEASE SEE NOTES DO NOT CORRELATE WITH
 MDP.(METER TO MDP)
 215.5
  
 8)NOTE: PLEASE SEE NOTES TO RISER
 MENTIONS AN EQUIPMENT GROUNDING
 CONDUCTOR BEING INSTALLED FROM METER TO
 FIRST MEANS OF DICSCONNECT. PLEASE SEE
 250.6,250.24, AN "EQUIPMENT GROUNDING"
 CONDUCTOR SHALL ONLY BE INSTALLED AFTER
 THE FIRST MEANS OF DISCONNECT.
  
 9)NOTE: PLEASE CLARIFY MULTIPLE BRKRS
 FEEDING ONE A/CAHU??
 PLEASE SEE A 2P BRKR IS SHOWN FOR AHU
 AND A SEPARATE FEED AND BRKR FOR AHU
 HEAT??
 THIS IS NOT PERMITTED, ALL EQUIPMENT
 MUST BE DISCONNECTED WITH A SINGLE THROW
 OF A SWITCH DISC ETC.
 440.11ETC.
  
 10)NOTE: PLEASE SEE TWO AHU'S NO #1 ON
 PANEL SCHEDULE.
 215.5
  
 11)NOTE: PLEASE CORRLEATE OCP, AWG AND
 LOAD CALCUALTIONS FOR AHU'S AND HEAT.
 PLEASE SEE ONE SHOWS WHAT APPEARS TO BE
 5KW, HOWEVER LOAD CALCULATIONS INDICATE
 10KW??
 PLEASE ALSO SEE SIZING OF BRANCH CIRCUIT
 CONDUCTORS AS SHOWN ON RISER.
 240.4,424.3B,310.16, 215.5 ETC
  
 12)NOTE: PLEASE SEE A WHIRLPOOL TUB IS
 SHOWN ON PANEL SCHEDULE AND IS INDICATED
 IN LOAD CALCS, HOWEVER THIS COULD NOT BE
 LOCATED ON PLANS?
 PLEASE ALSO SEE 680.71 FOR REQUIRED GFI
 PROTECTION.
  
 13)NOTE: PLEASE CLARIFY SIZE OF BRANCH
 CIRCUIT SHOWN FOR RANGE? 70A?
 PLEASE SEE 422.11 FOR MAX SIZE OF BRANCH
 CIRCUIT FOR APPL.
 PLEASE SEE MAX SINGLE OCP IS
 60A'S.(48A'S).
 PLEASE ADJUST.
  
 14)NOTE: PLEASE SEE PLANS INDICATE BY
 NOTE "ARC-FAULT" PROTECTION FOR BEDRMS,
 HOWEVER ONLY TWO ARC FAULT CIRCUITS ARE
 SHOWN ON PLANS??
 PLEASE ALSO SEE SD'S ARE SHOWN ON PANEL
 SCHEDULE, HOWEVER THESE ARE NOT LISTED
 AS BEING ARC FAULT PROTECTED??
 PLEASE SEE 2002 NEC 210.12, WHICH
 REQUIRES ALL OUTLETS IN BEDRMS, FANS,
 LTS, RECEPTS, SD'S ETC.
  
 15)NOTE: PLEASE INDICATE GFI PROTECTION
 FOR FOUNTAIN PUMP,LTS.
 680.50-680.56
  
 16)NOTE:PLEASE CLARIFY IF LOAD SHOWN
 FOR POOL PUMP IS SHOWN @ CONTINUOUS
 LOAD? 125%?
 PLEASE SEE ALL CONTINUOUS LOADS SHOULD
 BE INDICATED AT 125%.
 215.3,230.42, ETC.
  
 17)NOTE:PLEASE VERIFY, PLANS INDICATE
 PANELS TO BE INSTALLED ARE SQ D
 "HOMELINE"?? PLEASE CLARIFY AND ADJUST
 IF NEEDED. THIS IS ONLY A NOTE AND NO
 CORRECTION NEEDS TO BE MADE UNLESS
 "HOMELINE" PANELS WILL NOT BE USED.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICLA
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIOW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 SHEETS FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]