| 2007-04-08 13:54:36 | |
| | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE THIS PROJECT WAS PERMITTED UNDER |
| | THE 2001 FBC . |
| | PLEASE SEE THIS WAS UNDER THE PREVIOUS VERSION. PLEASE |
| | SEE THAT THE ENERGY CALCULATIONS DO NOT COORDINATE WITH |
| | THE PLANS FOR THE FIXTURES, TYPES, WATTAGES, ETC. |
| | PLEASE SEE THE FIXTURE LEGEND. PLEASE SEE THE LIGHTING |
| | DENSITIES PROVIDED ON PLANS DO NOT CORRELATE WITH THE |
| | ACTUAL FIXTURES ON PLANS OR WHAT IS IN ENERGY |
| | CALCULATIONS. |
| | PLEASE REVISE ALL OF THE ENERGY CALCULATIONS AND |
| | DENSITIES ALONG WITH REVISED PLANS AS NEEDED TO |
| | COORDINATE ALL. |
| | FBC 13-415.1.AB.1.1, 13-415.2 |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 2) NOTE: PLEASE SEE REVISED RISER WHICH SHOWS A 200AMP |
| | DISCONNECT FEEDING A 100AMP RATED PANEL. PLEASE ALSO |
| | SEE PLANS WHICH INDICATE THE SAME. |
| | PLEASE SEE THE LOAD SHOWN AT 161AMPS EXCEEDS THAT OF |
| | THE RATING OF PANEL ALSO. |
| | PLEASE SEE PANEL SCHEDULE WHICH INDICATES A 200A RATED |
| | BREAKER IN THIS 100AMP PANEL. |
| | PLEASE SEE 240.4, 310.16 ETC |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE MISSING CIRCUITING ON PLANS FOR |
| | EM/EXT LTS.PLEASE SEE 700.12E FOR CIRCUITING. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |