| Date |
Text |
| 2007-05-16 09:14:22 | DENIED |
| | REFERENCE: FLORIDA STATUTES |
| | FLORIDA ADMINISTRATIVE CODE |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | |
| | 1. THE REVISION SUBMITTED SUPERCEDES THE SHEETS |
| | SUBMITTED AND APPROVED FOR THE ORIGINAL PERMIT. BY |
| | SUPERCEDING THESE SHEETS, ALL INFORMATION ORIGINALLY |
| | SUBMITTED WILL BE DELETED. THIS IS NOT ACCEPTABLE. |
| | |
| | 2. IF THERE IS REVISIONS FOR THE PLANS, THEY SHALL BE |
| | DESIGNED BY THE ARCHITECT AND ENGINEER OF RECORD. IF |
| | THERE WILL BE A NEW ARCHITECT AND ENGINEER OF RECORD, |
| | THEN A NEW PERMIT WILL BE REQUIRED AND A SHOP DRAWING |
| | APPROVED BY THE ORIGINAL ARCHITECT AND ENGINEER SHALL |
| | BE SUBMITTED. |
| | |
| | 3. A SEPARAGE PERMIT WITH THE NEW DESIGN PROFESSIONALS |
| | WILL BE ALLOWED AFTER THE CERTIFICATE OF OCCUPANCY |
| | WITHOUT APPROVAL OF THE ORIGINAL DESIGN TEAM. |
| | |
| | 4. SHT A-1 THE BUILDING DATA INDICATES THE OCCUPANCY AS |
| | STORAGE. THE FLOOR PLAN INDICATES A MIXED OCCUPANCY |
| | WITH BUSINESS AND STORAGE OCCUPANCY. PLEASE INDICATE |
| | CORRECT OCCUPANCE. |
| | |
| | 5. PER TABLE 403.1 A SERVICE SINK IS REQUIRED IN THE |
| | STORAGE OCCUPANCY. |
| | |
| | 6. SHT A-1 THE BREAK ROOM SINK REQUIRES A FORWARD |
| | APPROACH MAXIMUM 19" UNDERNEATH THE SINK, AND NOT |
| | PARALLEL APPROACH AS SHOWN. SECTION 11-4.16.5. |
| | |
| | 7. SHT A-1 THE ROOM FINISH SCHEDULE INDICATES PAINT ON |
| | THE WALLS OF THE TOILET ROOMS 106 & 107. PER SECTION |
| | 1210.2 WALLS WITHIN 2 FEET OF THE WATER CLOSETS SHALL |
| | HAVE A SMOOTH, HARD, NONABSORBENT SURFACE. PAINTED |
| | WALLS DOES NOT COMPLY WITH THE "HARD" REQUIREMENT. |
| | PLEASE INDICATE COMPLIANCE. |
| | |
| | 8. SUBMIT A DETAIL FOR THE TOILET ROOMS SHOW COMPLIANCE |
| | WITH THE FOLLOWING: |
| | ___FOR W/C'S |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.3 HEIGHT |
| | C. 11-4.16.4 GRAB BARS |
| | D. 11-4.16.5 FLUSH CONTROLS |
| | E. 11-4.16.6 DISPENSERS |
| | ___FOR LAVS |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | D. 11-4.16.5 FAUCETS |
| | THE W/C'S SHALL BE 18" OFF THE WALL TO THE CENTERLINE |
| | OF THE FIXTURE & THE LAV SHALL BE A MINIMUM OF 15" OFF |
| | THE WALL TO THE CENTERLINE OF THE FIXTURE. SEE FIGURE |
| | 29 AND THE LAV SHALL BE CENTERED ON THE 30" DIMENSION |
| | OF THE CLEAR FLOOR SPACE. |
| | |
| | 9. SHT A-2 DETAIL #1. SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | A. 11-4.24.4 SINK DEPTH |
| | B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH |
| | REQUIRED) |
| | C. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | D. 11-4.24.7 FAUCETS. |
| | |
| | 10. SHT P-1 SANITARY RISER DIAGRAM. ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT TO THE |
| | WET-VENTED HORIZONTAL BRANCH DRAIN. ADDITIONAL |
| | FIXTURES, (BREAK ROOM SINK), SHALL DISCHARGE DOWNSTREAM |
| | OF THE WET VENT. SECTION 909.1. |
| | |
| | 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE |
| | TO THE BUILDING/SPACE. SECTION 608.13.2.. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | . |