2005-11-17 00:00:00**** UNSAT ****
  
 PLEASE SEE PLANS ARE COMING BACK FOR
 OTHER COMMENTS , PLEASE ADDRES BELOW AT
 THIS TIME.
  
 1)NOTE: PLEASE SEE NOTE # 4 FROM
 PREVIOUS REVIEW WHICH REQUESTED TO
 CLARIFY ONE UNIT SHOWN ON PLANS WHICH
 SEEMS TO GETTING BUILT OUT HOWEVER RISER
 DIAGRAM AND RISER NOTES DO NOT TEND TO
 CORRELATE WITH THIS.
 PLEASE SEE CIRCUTING FOR PANEL T-1
 CORRLELATES WITH THIS BLD OUT.
 PLEASE PROVIDE INFORMATION FOR
 DISCONNECT METER ETC.
 215.5
  
 2)NOTE: THIS IS ONLY A NOTE: RECEPT
 CIRCUITED TO #9, SEEMS TO BE INDICATED
 TO BE ABOVE CEILING.
 RECEPTS ARE NOT PERMITTED ABOVE.
  
 3)NOTE: PLEASE SEE A RE-RECORDED NOC
 WILL BE REQUIRED AS THE ONE PRESENTLY
 SUBMITTED HAS EXPIRED.
 PLEASE SEE FS 713.13(2).
 PLEASE KNOW, IF WORK HAS NOT COMMENCED
 WITH IN 90 DAYS OF RECORDING, THE NOC
 SHALL BECOME VOID.
 THIS NOTE ID NOT FOR THE ELECTRICAL
 ENGINEER.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  