2005-11-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 COMMENTS FROM PREVIOUS REVIEW, NUMBERING
 REMAINING THE SAME FOR CONSISTENCY
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 FS713.13 REQUIRES THE CONTRACTOR?S NAME
 AND ADDRESS SO THAT NOTICES CAN BE
 SERVED AS REQUIRED BY THE FLORIDA LEIN
 LAW.CONTRACTOR ADDRESS IS NOT ON THE
 NOC.
  
 5.)THIS PARCEL IS IN A FLOOD ZONE.A
 FORM BOARD ELEVATION CERTIFICATE WILL BE
 REQUIRED.THE FINISHED FLOOR IS TO BE
 SIX INCHES ABOVE BASE FLOOD ELEVATION,
 CITY OF WEST PALM BEACH MUNICIPAL CODE
 94-546(2). NOTE MINIMUM ELEVATION ON THE
 PLAN.
  
 NOT ADDRESSED.
  
 6.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS.
  
 7.)A WAREHOUSE SHOULD BE S OCCUPANCY,
 THE OFFICE AREA IS B.PLEASE SEE FBC312
 AND FBC305.BUSINESS OCCUPANCY WAS
 DECLARED ON SHEET A2.
  
 NOT ADDRESSED; STILL SHOWS A WAREHOUSE
 AND DECLARES B OCCUPANCY.BASED ON THE
 FLOOR PLAN WHICH SHOWS A WAREHOUSE, THE
 OFFICES ARE ACCESSORY TO THE PRIMARY
 OCCUPANCY OF STORAGE, SEE FBC704.1.2.1.
  
  
 8.)PROVIDE A SITE PLAN, FBC*104.3.1.1.
 SHOW ALL DISTANCES FROM THE PROPERTY
 LINE SO THAT TABLE 500 AND TABLE 600
 COMPLIANCE CAN BE DETERMINED.SHOW
 ACCESSIBLE PARKING, ACCESSIBLE ROUTE
 FROM THE PUBLIC WAY FBC CHAPTER 11.
  
 9.)THE AREA INCREASE CALCULATIONS ON
 A2 STATES THAT THE ALLOWABLE AREA FOR
 BUSINESS TYPE V IS 9000 SF.PLEASE NOTE
 THAT IT IS 14000 SF PER FBC TABLE 500
 AND 16000 FOR STORAGE.
  
 YOU HAVE CHANGED THE BUILDING TYPE TO
 VI.AREA ALLOWED FOR TYPE VI, STORAGE
 OCCUPANCY, UNPROTECTED UNSPRINKLED IS
 6000.THE BUILDING IS NOT COMPLIANT FBC
 TABLE 500.
  
 12.)CLARIFY THE ROOF AREA ON A3.
  
 13.)DOOR HARDWARE TO COMPLY WITH
 FBC11-4.13.9.
  
 THIS WAS ADDRESSED BY PROVIDING THE CODE
 SECTION.PLANS ARE TO BE PROVIDE DESIGN
 CRITERIA, FBC*104.2.1.
  
 16.)THE FOLLOWING NOAS WERE REVIEWED
 AND APPEAR CODE COMPLIANT EXCEPT AS
 NOTED BUT REQUIRE FLORIDA STATE OR LOCAL
 PRODUCT APPROVALS, FAC9B72.
 WWW.FLORIDABUILDING.ORG.
  
 ARCH ALUMINUM IMPACT WALL 3000
 ARCH ALUMINUM MAGNUM STILE ENTRANCE DOOR
 MODEL 651 ROLLING DOOR ? EXPIRED NOA
  
 FLORIDA PRODUCT APPROVALS REQUIRED IN
 ADDITION TO THE NOAS PROVIDED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 17.)PROVIDE PRODUCT APPROVALS FOR THE
 REAR METAL DOOR, FLAT ROOF, STANDING
 SEAM, ROLLING DOOR.ANY PRODUCT
 APPROVALS NOT REVIEWED PRIOR TO PERMIT
 ISSUANCE WILL REQUIRE SEPARATE PERMITS.
  
 FLORIDA PRODUCT APPROVALS REQUIRED
 FAC9B72, WWW.FLORIDABUILDNIG.ORG
  
 18.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF
 COMMENTS ARE NOT ADDRESSED IN THE NEXT
 REVIEW.
  