Plan Review Notes
Plan Review Notes For Permit 05070366
Permit Number 05070366
Review Stop P
Sequence Number 1
Notes
Date Text
2005-08-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
  
 1. SHT A-2 PER TABLE 403.2 SEPARATE
 FACILITIES ARE REQUIRED FOR MEN AND
 WOMEN.
 2. SHT A-2 TABLE 403.1 STORAGE
 FACILITIES REQUIRES A SERVICE SINK.
 3. SHT A-2 INDICATES 13,392SF BUILDING
 AREA, BUT SHT A-3 GUTTER & DOWNSPOUT
 CALCULATIONS SHOW FLAT ROOF AREA AS
 6,128SF. PLEASE CLARIFY. SECTION
 104.2.1.
 4. SHT A-3 GUTTER & DOWNSPOUT
 CALCULATION FOR PARAPETS DO NOT INCLUDE
 THE PARAPET WALL FOR THE FRONT OF THE
 BUILDING. ALSO ALL VERTICAL WALLS FOR
 THE THREE SIDES OF THE CUPOLA, AND 5
 SIDES FOR EACH WALL AT THE A/C EQUIPMENT
 SHALL BE INCLUDED IN THE CALCULATIONS.
 SECTION 1106.4. ALSO NOT INCLUDED IN THE
 CALCULATIONS SHALL BE THE AREA OF THE
 ROOF FROM THE CUPOLA THAT DRAINS ONTO
 THE FLAT ROOF AREA FROM ABOVE. PLEASE
 RECALCULATE SQUARE FOOTAGE FOR ROOF AREA
 TO BE DRAINED.
 5. SUBMIT A DETAIL FOR THE GUTTER
 SHOWING SIZE OF GUTTER COMPLYING WITH
 TABLE 1106.6, SLOPE OF GUTTER WITH HIGH
 POINTS OF GUTTER CALLED OUT ON PLAN,
 WITH THE SIZE AND LOCATION OF EACH
 DOWNSPOUT. INDICATE THE TOTAL AREA
 DRAINING INTO EACH DOWNSPOUT. SECTION
 104.2.1.
 6. SHT A-6 DETAIL #9 CONTROLS FOR
 DRINKING FOUNTAIN DO NOT SEEM TO COMPLY
 WITH SECTION 11-4.27.4. (TWISTING OF THE
 WRIST). PLEASE CLARIFY. - PLEASE SHOW
 COMPLIANCE WITH SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
 7. SHT A-6 DETAIL #2 SHOW THE FOLLOWING:
  
 FOR W/C, 11-4.16.5 FLUSH CONTROLS
 FOR LAV, 11-4.19.5 FAUCETS
 8. SHT ME-2 SANT. RISER DIAGRAM, A 2-WAY
 CLEANOUT IS REQUIRED NEAR THE JUNCTION
 OF THE BUILDING DRAIN AND THE BUILDING
 SEWER. SECTION 708.3.5.
 9. SHT MP-2 SANT. RISER DIAGRAM, ALL
 HORIZONTAL BUILDING DRAINS REQUIRE A
 CLEANOUT. SECTION 708.3.1.
 10. SHT MP-2 WATER RISER DIAGRAM, AN RPZ
 BACKFLOW IS REQUIRED ON THE WATER
 SERVICE TO THE BUILDING.
 11. A SEPARATE IRRIGATION PERMIT AND
 PLANS ARE REQUIRED. SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]