| 2005-08-08 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | |
| | 1. SHT A-2 PER TABLE 403.2 SEPARATE |
| | FACILITIES ARE REQUIRED FOR MEN AND |
| | WOMEN. |
| | 2. SHT A-2 TABLE 403.1 STORAGE |
| | FACILITIES REQUIRES A SERVICE SINK. |
| | 3. SHT A-2 INDICATES 13,392SF BUILDING |
| | AREA, BUT SHT A-3 GUTTER & DOWNSPOUT |
| | CALCULATIONS SHOW FLAT ROOF AREA AS |
| | 6,128SF. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 4. SHT A-3 GUTTER & DOWNSPOUT |
| | CALCULATION FOR PARAPETS DO NOT INCLUDE |
| | THE PARAPET WALL FOR THE FRONT OF THE |
| | BUILDING. ALSO ALL VERTICAL WALLS FOR |
| | THE THREE SIDES OF THE CUPOLA, AND 5 |
| | SIDES FOR EACH WALL AT THE A/C EQUIPMENT |
| | SHALL BE INCLUDED IN THE CALCULATIONS. |
| | SECTION 1106.4. ALSO NOT INCLUDED IN THE |
| | CALCULATIONS SHALL BE THE AREA OF THE |
| | ROOF FROM THE CUPOLA THAT DRAINS ONTO |
| | THE FLAT ROOF AREA FROM ABOVE. PLEASE |
| | RECALCULATE SQUARE FOOTAGE FOR ROOF AREA |
| | TO BE DRAINED. |
| | 5. SUBMIT A DETAIL FOR THE GUTTER |
| | SHOWING SIZE OF GUTTER COMPLYING WITH |
| | TABLE 1106.6, SLOPE OF GUTTER WITH HIGH |
| | POINTS OF GUTTER CALLED OUT ON PLAN, |
| | WITH THE SIZE AND LOCATION OF EACH |
| | DOWNSPOUT. INDICATE THE TOTAL AREA |
| | DRAINING INTO EACH DOWNSPOUT. SECTION |
| | 104.2.1. |
| | 6. SHT A-6 DETAIL #9 CONTROLS FOR |
| | DRINKING FOUNTAIN DO NOT SEEM TO COMPLY |
| | WITH SECTION 11-4.27.4. (TWISTING OF THE |
| | WRIST). PLEASE CLARIFY. - PLEASE SHOW |
| | COMPLIANCE WITH SECTION 11-4.1.3(10)(A) |
| | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY |
| | BENDING OR STOOPING. |
| | 7. SHT A-6 DETAIL #2 SHOW THE FOLLOWING: |
| | |
| | FOR W/C, 11-4.16.5 FLUSH CONTROLS |
| | FOR LAV, 11-4.19.5 FAUCETS |
| | 8. SHT ME-2 SANT. RISER DIAGRAM, A 2-WAY |
| | CLEANOUT IS REQUIRED NEAR THE JUNCTION |
| | OF THE BUILDING DRAIN AND THE BUILDING |
| | SEWER. SECTION 708.3.5. |
| | 9. SHT MP-2 SANT. RISER DIAGRAM, ALL |
| | HORIZONTAL BUILDING DRAINS REQUIRE A |
| | CLEANOUT. SECTION 708.3.1. |
| | 10. SHT MP-2 WATER RISER DIAGRAM, AN RPZ |
| | BACKFLOW IS REQUIRED ON THE WATER |
| | SERVICE TO THE BUILDING. |
| | 11. A SEPARATE IRRIGATION PERMIT AND |
| | PLANS ARE REQUIRED. SECTION 104.3.1.1. |
| | |