| Plan Review Notes For Permit 05070366 |
| Permit Number |
05070366 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-27 00:00:00 | DENIED: | | | 1. PLAN SHEET A-3-ROOF EQUIPMENT DETAIL | | | CLEARENCE ABOVE FINISHED ROOF SHALL | | | COMPLY WITH ZOOL FBC 1511.7. | | | | | | 2. PROUIDE DETAIL FOR HANGING OF THE | | | AHU. | | | | | | 3. CONDENSATE SHALL TERMINATE A MINIMUM | | | OF 12" AWAY FROM THE BUILDING STRUCTURE, | | | 2001 FBC 1503.4.4. | | | | | | 4. PLAN SHEET MP-2 HVAC SPECIFICATIONS | | | #19 - EMERGENCY DRAIN PAN SHALL HAVE | | | OVERFLOW PROTECTION IN ACCORDANCE WITH | | | 2001 FBC(M)307.2.3. | | | | | | 5.PLEASE INDICATE VENTILATION FOR THE | | | WAREHOUSE AREAS PER 2001 FBC(M) TABLE | | | 403.3. | | | | | | 6. INDICATE ACCESS TO EQUIPMENT LOCATED | | | ON THE ROOF.PERMANENT MEANS OF ACCESS | | | IS REQUIRED FOR HEIGHTS GREATER THAN 16 | | | FEET. 2001 FBC(M)306.5 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|