| 2005-08-11 00:00:00 | ******DENIED****** |
| | |
| | 1) PLANS INDICATE THAT INTERIOR FINISH |
| | ON WALLS AND CEILINGS TO BE CLASS A, B, |
| | OR C. PLEASE INDICATE THE CLASSIFICATION |
| | OF WALLS AND CEILINGS APPLICABLE TO THIS |
| | OCCUPANCY. |
| | |
| | 2) IT IS UNDERSTOOD THAT MONUMENT SIGNS |
| | ARE PLANNED TO BE INSTALLED UPON |
| | APPROVAL. IF A DELAY SHOULD OCCUR PRIOR |
| | TO OCCUPANCY, ADDRESSES ON THE BUILDING |
| | WILL BE REQUIRED THAT ARE AT LEAST 6" IN |
| | HEIGHT AND CONTRASTING TO THE |
| | BACKGROUND. |
| | |
| | 3) NOTE #4 REFERS TO A KEY LOCKING |
| | DEVICE ON THE EGRESS SIDE OF EACH MAIN |
| | EXIT DOOR. THIS ARRANGEMENT IS ONLY |
| | ACCEPTABLE IF ALL THE CRITERIA IN |
| | ACCORDANCE WITH NFPA 101, SECTION |
| | 7.2.1.5.4 IS MET. |
| | |
| | 4) SOME EXIT SIGNS APPEAR TO BE MISSING |
| | ON THE WAREHOUSE DOORS LEADING TO THE |
| | OFFICE AREAS. |
| | |
| | 5) PLEASE SHOW ALL THE EMERGENCY |
| | LIGHTING FACILITIES. THERE APPEARS TO BE |
| | SOME MISSING IN WAREHOUSE AREAS. |
| | |
| | 6) 2A-10B,C RATED FIRE EXTINGUISHERS |
| | SHALL BE MOUNTED AT DISTANCES TO SATISFY |
| | THE 75' TRAVEL DISTANCE REQUIREMENT. |
| | |
| | 7) PLEASE ILLUSTRATE REQUIRED FIRE |
| | SEPARATION REQUIREMENT FOR SEPARATE |
| | TENANT SPACES. |
| | |
| | 8) PLEASE SHOW LOCATION AND DISTANCE OF |
| | CLOSEST FIRE HYDRANT IN RELATION TO |
| | BUILDING. |
| | |
| | |