| 2005-07-27 00:00:00 | *********** UNSAT ****************** |
| | |
| | PLEASE SEE ADDRESS IN OUR SYSTEM FOR PCN |
| | USED SHOWS "5660" CORP WAY. PLEASE SEE |
| | PERMIT APPLICATION AND PLANS SHOWS |
| | "5760". PLEASE SEE ADDRESSING WILL NEED |
| | TO BE CORRELATED. |
| | |
| | 1)NOTE: PLEASE LABEL EACH |
| | WAREHOUSE/OFFICE SPACE. IE: UNIT |
| | A,B,C,,,,1,2,3,, ETC |
| | PLEASE CORRELATE THIS AND LABEL RISER |
| | ACCORD. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SHOW CIRCUITING ON PLANS |
| | AND CORRELATE WITH THE SUBMITTED |
| | TYPPICAL PANEL SCHEDULE. |
| | PLEASE ALSO SHOW CIRCUITING FOR HOUSE |
| | LOADS. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE CLARIFY, PLANS APPEAR TO |
| | SHOW EM/EXT LTS CIRCUITED TO HOUSE |
| | PANEL? YET, NOTE ON ON LIGHTING LEGEND |
| | MENTIONS AHEAD OF LOCAL LIGHTING. |
| | PLEASE SEE 700.12E, WHICH REQUIRES |
| | FIXTURES TO BE CONNECTED TOBRANCH |
| | CIRCUIT FOR LOCAL AREA LIGHTING. |
| | PLEASE ALSO SEE THIS WOULD INDICATEA |
| | CROSS OVER IN ELECTRICAL CIRCUITS INTO |
| | EACH TENANT SPACE? |
| | |
| | 4)NOTE: PLEASE CLARIFY PLANS WHICH |
| | APPEARS TO SHOW ONE UNIT, OFFICE |
| | WAREHOUSE BEING BUILT OUT. HOWEVER, |
| | RISER DIAGRAM DOES NOT CORREALTE WITH |
| | THIS? |
| | RISER SHOWS ALL DISCONNECTS AND PANELS |
| | AS FUTURE? |
| | |
| | 5)NOTE: PLEASE SEE 600.5 WHICH REQUIRES |
| | THE TENANT SIGN CIRCUIT TO BE LOCATED AT |
| | ENTRANCE INTO UNIT. |
| | PLEASE SEE J-BOX SEEMS TO BE ABOVE |
| | WINDOW AS FOR A WINDOW SIGN? PLEASE SEE |
| | NEXT COMMENT. |
| | |
| | 6)NOTE: PLEASE SEE IF ANY OF THESE UNITS |
| | ARE INTENDED FOR RETAIL SPACE, A WINDOW |
| | RECEPT WILL BE REQUIRED ABOVE WINDOW. |
| | PLEASE SEE THIS IS ONLY A COMMENT AT |
| | THIS TIME OF NOW UNITS ARE GOING TO |
| | BUILT OUT. IF ANY UNIT IS BUILT OUT AT |
| | THIS TIME, A RECEPT WILL BE REQUIRED. |
| | 210.62,220.12 |
| | |
| | 7)NOTE: PLEASE INCLUDE CONDUCTORS FROM |
| | MAIN TO GUTTER . 215.5,240.4,310.16 |
| | PLEASE ALSO SEE NEXT COMMENT FOR |
| | EQUIPMENT GROUNDING CONDUCTOR. |
| | |
| | 8)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS AFTER THE FIRST |
| | MEANS OF DISCONNECT.250.24,250.6, |
| | 250.110 ETC. |
| | PLEASE SEE NOTE #8 ON RISER NOTES DOES |
| | NOT SEEM TO INCLUDE THIS.? |
| | |
| | 9)NOTE: PLEASE ALSO SEE NOTE #8 ON RISER |
| | APPEARS TO SHOW CONDUITS/FEEDERS ETC ON |
| | LOAD SIDE OF TENANT DISCONNECTS ALSO |
| | BEING CONNECTED TO FPL TRANSFORMER? |
| | PLEASE SEE RISER DIAGRAM. |
| | |
| | 10)NOTE: PLEASE SEE NOTES #4&5 ON RISER |
| | NOTES PERTAINING TO GROUNDING ELECTRODE |
| | SYSTEM. PLEASE SEE 250.50, WHICH ALSO |
| | REQUIRES FOOTER STEEL. PLEASE INCLUDE |
| | THIS IN A DETAIL TO BE PROVIDED FOR |
| | GROUNDING ELECTRODE SYSTEM. |
| | |
| | 11)NOTE: PLEASE CLARIFY NOTE #15 ON |
| | RISER AND NOTES WHICH MENTIONS TO |
| | INSTALL, 2-2" CONDUITS FROM "GUTTER" TO |
| | EACH TEANT SPACE? PLEASE SEE RISER SHOWS |
| | THESE CONDUITS BEING INSTALLED TO EACH |
| | DISCONNECT? PLEASE ALSO CLARIFY (TWO) |
| | CONDUITS FOR EACH FEEDER? |
| | 215.5 |
| | |
| | 12)NOTE: PLEASE INCLUDE SIZING FOR |
| | GUTTER AT THIS TIME. PLEASE SEE 366. |
| | |
| | 13)NOTE: PLEASE CLARIFY PANEL "HP" |
| | SHOWING A BACK-FED 60A BRKR FOR MAIN, |
| | YET RISER AND PLANS BOTH INDICATE A |
| | FUSIBLE MAIN DISCONNECT RIGHT NEXT TO |
| | PANEL?? |
| | PLEASE SEE THE ADDITIONAL "MAIN" WITH A |
| | RETENTION CLIP MAY BE INSTALLED, HOWEVER |
| | THIS IS NOT REQUIRED. THIS IS ONLY A |
| | NOTE. IF SHOWN ON PLANS THEN IT WILL BE |
| | REQUIRED TO BE INSTALLED. |
| | 215.5 |
| | |
| | 14)NOTE: PLEASE CLARIFY FIXTURE "A" |
| | SHOWN ON PLANS; LIGHT FIXTURE ON PLAN |
| | AND ON "LIGHTING LEGEND" APPEARS TO SHOW |
| | THIS FIXTURE AS A SURFACE MOUNBTED |
| | SCONCE TYOE OF FIXTURE, HOWEVER PLEASE |
| | SEE " LIGHTING FIXTURE SCHEDULE" WHICH |
| | DOES NOT CORRELATE WITH THIS FOR FIX |
| | "A".? |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE COPY OF OLD/VOIDED |
| | SHEETS FOR REFERENCE WHICH SHOULD BE |
| | SEPARATE AND MRKED VOID/OLD. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2005-07-26 00:00:00 | IN ELECTRICAL FOR REVIEW. |
| | PLAN REVIEW NOTES FOR ELECTRICAL WILL |
| | FOLLOW ONCE REVIEW IS COMPLETE. |